Orno (OR-WE-514,OR-WE-515) data logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
305Phase voltage V1Vword
306Phase voltage V2Vword
307Phase voltage V3Vword
314Phase current I1Aword
316Phase current I2Aword
318Phase current I3Aword
321Split phase active powerp1kWinteger
323Split phase active powerp2kWinteger
325Split phase active powerp3kWinteger
327System active power psumkWinteger
329Split phase reactive power Q1kvarinteger
331Split phase reactive power Q2kvarinteger
333Split phase reactive power Q3kvarinteger
335System reactive power qsumkvarinteger
337Split phase apparent power S1kvainteger
339Split phase apparent power S2kvainteger
341Split phase apparent power S3kvainteger
343System apparent power ssumkvainteger
344Split phase power factor PF1 integer
345Split phase power factor PF2 integer
346Split phase power factor PF3 integer
347System power factor pf integer
40960Current total active powerkwhdword
40962Current rate 1 active powerkwhdword
40964Current rate 2 active powerkwhdword
40966Current rate 3 active powerkwhdword
40968Current rate 4 active powerkwhdword
40990Current total reactive powerkvarhdword
40992Current rate 1 reactive powerkvarhdword
40994Current rate 2 reactive powerkvarhdword
40996Current rate 3 reactive powerkvarhdword
40998Current rate 4 reactive powerkvarhdword
41008Last month demand dword
41010Last two month demand dword

Orno (OR-WE-514,OR-WE-515) data logging