Orno OR-WE-514, OR-WE-515 MODBUS registers: read online

Connect Orno to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Orno data logger and record.

Do you not know the meter address? Scan the device address online

Orno (OR-WE-514,OR-WE-515) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus RTU
Default baud rate
9600
Data bits
8
Stop bits
1
Parity
none
Frame format
N81
Data mode
16 decimal word mode
Function codes
03 read
Byte order
low address holds the high byte of the data
Real time data area
9000H-9FFFH
Multi rate data area
A000H-AFFFH

Registers in the map: 34. function 3 (holding registers). byte order big-endian. data types: dword, integer, word.

MODBUS offsetDescriptionUnitsData typeScale
305Phase voltage V1Vword×0.01
306Phase voltage V2Vword×0.01
307Phase voltage V3Vword×0.01
314Phase current I1Aword×0.001
316Phase current I2Aword×0.001
318Phase current I3Aword×0.001
321Split phase active powerp1kWinteger×0.001
323Split phase active powerp2kWinteger×0.001
325Split phase active powerp3kWinteger×0.001
327System active power psumkWinteger×0.001
329Split phase reactive power Q1kvarinteger×0.001
331Split phase reactive power Q2kvarinteger×0.001
333Split phase reactive power Q3kvarinteger×0.001
335System reactive power qsumkvarinteger×0.001
337Split phase apparent power S1kVAinteger×0.001
339Split phase apparent power S2kVAinteger×0.001
341Split phase apparent power S3kVAinteger×0.001
343System apparent power ssumkVAinteger×0.001
344Split phase power factor PF1 integer×0.001
345Split phase power factor PF2 integer×0.001
346Split phase power factor PF3 integer×0.001
347System power factor pf integer×0.001
40960Current total active powerkWhdword×0.01
40962Current rate 1 active powerkWhdword×0.01
40964Current rate 2 active powerkWhdword×0.01
40966Current rate 3 active powerkWhdword×0.01
40968Current rate 4 active powerkWhdword×0.01
40990Current total reactive powerkvarhdword×0.01
40992Current rate 1 reactive powerkvarhdword×0.01
40994Current rate 2 reactive powerkvarhdword×0.01
40996Current rate 3 reactive powerkvarhdword×0.01
40998Current rate 4 reactive powerkvarhdword×0.01
41008Last month demand dword×0.01
41010Last two month demand dword×0.01

Orno (WE-516,WE-517) - Measurement Data

Connection and addressing notes

Default baud rate
9600
Data bits
8
Stop bits
1
Parity
none
Default device address
1
Frame size
11 bits (1 start bit, 8 data bits, no parity, 1 stop bit)
Baud rate options
1200, 2400, 4800
CRC check
2 bytes
Function codes
03 read
Meter ID register
0002
Error response prefix
01 (default address)

Registers in the map: 56 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
4Software version single 
6Hardware version single 
0Serial number dword 
2Meter ID word 
8CT rate word 
9SO output rate single 
11A3 word 
13Cycle time word 
14L1 voltage single 
16L2 voltage single 
18L3 voltage single 
20Grid frequency single 
22L1 current single 
24L2 current single 
26L3 current single 
28Total active power single 
30L1 active power single 
32L2 active power single 
34L3 active power single 
36Total reactive power single 
38L1 reactive power single 
40L2 reactive power single 
42L3 reactive power single 
44Total apparent power single 
46L1 apparent power single 
48L2 apparent power single 
50L3 apparent power single 
52Total power factor single 
54Power factor L1 single 
56Power factor L2 single 
58Power factor L3 single 
66Combined code word 
256Total active energy single 
258L1 total active energy single 
260L2 total active energy single 
262L3 total active energy single 
264Forward active energy single 
266L1 forward active energy single 
268L2 forward active energy single 
270L3 forward active energy single 
272Reverse active energy single 
274L1 reverse active energy single 
276L2 reverse active energy single 
278L3 reverse active energy single 
280Total reactive energy single 
282L1 reactive energy single 
284L2 reactive energy single 
286L3 reactive energy single 
288Forward reactive energy single 
290L1 forward reactive energy single 

This is not the complete map: 50 of 56 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.