Ohio Semitronics WVx, WTx, WMx MODBUS registers: read online

Connect Ohio Semitronics to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Ohio Semitronics modbus logging and log.

Do you not know the meter address? Scan the device address online

Ohio Semitronics (WVx,WTx,WMx) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Default baud rate
19200
Data bits
8
Stop bits
1
Parity
even
Default device address
1
Default password
0000
Default communications mode
2, 1 start bit, 8 data bits, even parity, 1 stop bit
Device address range
1-247
Baud rate register options
9600, 14400, 19200, 28800, 38400, 57600, 115200
Addressing mode
default 1 = logical, 0 = Modicon addressing (zero based)
CRC mode
enabled by default
Function codes
03 read holding registers (offset 40000), 04 read input registers (offset 30000), 06 write single register

Registers in the map: 33. function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: dword, single, string(16), string(8).

MODBUS offsetDescriptionUnitsData typeScale
5016Meter firmware version string(8) 
5020Serial firmware version string(8) 
5000Meter name string(16) 
5008Meter serial number string(16) 
5200Watts total single 
5202Va total single 
5204Vars total single 
5206Power factor-1 to 1single 
5208Volts L1 L2 single 
5210Volts L2 L3 single 
5212Volts L3 L1 single 
5214Volts L1 N single 
5216Volts L2 N single 
5218Volts L3 N single 
5220Current L1 single 
5222Current L2 single 
5224Current L3 single 
5226Watts L1 single 
5228Watts L2 single 
5230Watts L3 single 
5232Frequency0 to 1,000single 
5234Va (l1) single 
5236Va (l2) single 
5238Va (l3) single 
5240Vars L1 single 
5242Vars L2 single 
5244Vars L3 single 
5246Power factor (l1) single 
5248Power factor (l2) single 
5250Power factor (l3) single 
5300Watt hr consumed pulse counter dword 
5302Watt hr generated pulse counter dword 
5304Var hr pulse counter dword 