RISH EM DC, EM1300, EM2300 MODBUS registers: read online

Connect RISH to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous RISH logging and read.

Do you not know the meter address? Scan the device address online

RISH (EM DC) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS-485 (2-wire)
Data bits
8
Stop bits
1 with parity, 1 or 2 without parity
Parity
even or odd
Baud rate
user selectable 4800, 9600, 19200, 38400, 57600 bps
Device address range
1-247
Broadcast address
0 not allowed
Function codes
03, 04, 16 (0x10)
Data format
32-bit IEEE 754 float, two consecutive 16-bit registers per parameter
Byte order
most significant byte first
CRC error check
enabled
Maximum parameters per query
40
Maximum response latency
200 ms
Register addressing
3X (30001+) and 4X (44097+)

Registers in the map: 101 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0VoltageVsingle 
2Current CH1Asingle 
4Current CH2Asingle 
6Current CH3Asingle 
8Current CH4Asingle 
10Power CH1 single 
12Power CH2 single 
14Power CH3 single 
16Power CH4 single 
18Total import power single 
20Total export power single 
22Energy imp CH1 single 
24Energy imp CH2 single 
26Energy imp CH3 single 
28Energy imp CH4 single 
30Energy exp CH1 single 
32Energy exp CH2 single 
34Energy exp CH3 single 
36Energy exp CH4 single 
38Total import energy single 
40Total export energy single 
58Amp hour imp CH1 single 
60Amp hour imp CH2 single 
62Amp hour imp CH3 single 
64Amp hour imp CH4 single 
66Amp hour exp CH1 single 
68Amp hour exp CH2 single 
70Amp hour exp CH3 single 
72Amp hour exp CH4 single 
74Total ImportAH single 
76Total ExportAH single 
78Import power demand CH1 single 
80Import power demand CH2 single 
82Import power demand CH3 single 
84Import power demand CH4 single 
86Export power demand CH1 single 
88Export power demand CH2 single 
90Export power demand CH3 single 
92Export power demand CH4 single 
94Total import power demand single 
96Total export power demand single 
98Import current demand CH1Asingle 
100Import current demand CH2Asingle 
102Import current demand CH3Asingle 
104Import current demand CH4Asingle 
106Export current demand CH1Asingle 
108Export current demand CH2Asingle 
110Export current demand CH3Asingle 
112Export current demand CH4Asingle 
114Total import current demandAsingle 

This is not the complete map: 50 of 101 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

RISH (EM1300,EM2300,EM13XX,EM23XX) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Register addressing
3X (30001+) for measured parameters
Data format
two consecutive 16-bit registers per parameter
Modbus start address
given in hex per parameter

Registers in the map: 163 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 single 
2Volts 2 single 
4Volts 3 single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W1 single 
14W2 single 
16W3 single 
18VA 1 single 
20VA 2 single 
22VA 3 single 
24VAR 1 single 
26VAR 2 single 
28VAR 3 single 
30PF 1 single 
32PF 2 single 
34PF 3 single 
36Phase angle 1 single 
38Phase angle 2 single 
40Phase angle 3 single 
42Volts av g single 
44Volts sum single 
46Current avg single 
48Current sum single 
50Watt avg single 
52Watt sum single 
54VA av g single 
56VA sum single 
58VAR av g single 
60VAR sum single 
62PF avg single 
64PF sum single 
66Phase angle avg single 
68Phase angle sum single 
70Freq single 
72Wh import / utility single 
74Wh export / gen single 
76Capacitive / utilityvarhsingle 
78Inductive / genvarhsingle 
80VAh / vah utility single 
82VAh gen (Only 2340) single 
84W demand (Import / utility / gen) single 
86W max demand (Import / utility) single 
88W demand (Export) single 
90W max demand (Export / gen) single 
92Old W max demand (Import / utility) single 
94Old W max demand (Export / gen) single 
96Old VA utility max demand single 
98Old A utility max demand single 

This is not the complete map: 50 of 163 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

RISH (LM1350,LM1360) - MODBUS Registers

Connection and addressing notes

Register addressing
3X and 4X addresses for measured parameters
Modbus start address
given in hex
Data format
two registers per parameter
Energy values
32-bit integers, separate table

Registers in the map: 359 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single.

MODBUS offsetDescriptionUnitsData typeScale
01 single 
22 single 
43 single 
64 single 
85 single 
106 single 
127 single 
148 single 
169 single 
1810 single 
2011 single 
2212 single 
2413 single 
2614 single 
2815 single 
3016 single 
3217 single 
3418 single 
3619 single 
3820 single 
4021 single 
4222 single 
4423 single 
4624 single 
4825 single 
5026 single 
5227 single 
5428 single 
5629 single 
5830 single 
6031 single 
6232 single 
6433 single 
6634 single 
6835 single 
7036 single 
7237 single 
7438 single 
7639 single 
7840 single 
8041 single 
8443 single 
8644 single 
8845 single 
9046 single 
9247 single 
9448 single 
9649 single 
9850 single 
10051 single 

This is not the complete map: 50 of 359 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

RISH (RM1300,RM2300) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register addressing
3X (30001+) for measured parameters
Data format
two consecutive 16-bit registers per parameter

Registers in the map: 157 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 single 
2Volts 2 single 
4Volts 3 single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W1 single 
14W2 single 
16W3 single 
18Va 1 single 
20Va 2 single 
22Va 3 single 
24Var 1 single 
26Var 2 single 
28Var 3 single 
30Pf 1 single 
32Pf 2 single 
34Pf 3 single 
36Phase angle 1 single 
38Phase angle 2 single 
40Phase angle 3 single 
42Volts av g single 
44Volts sum single 
46Current avg single 
48Current sum single 
50Watt avg single 
52Watt sum single 
54Va av g single 
56Va sum single 
58Var av g single 
60Var sum single 
62Pf avg single 
64Pf sum single 
66Phase angle avg single 
68Phase angle sum single 
70Freq single 
72Wh import / utility single 
74Wh export / gen single 
76Capacitive / utilityvarhsingle 
78Inductive / genvarhsingle 
80Vah / vah utility single 
82Vah gen (only 2340) single 
84W demand (import / utility / gen) single 
86W max demand (import / utility) single 
88W demand (export) single 
90W max demand (export / gen) single 
92Old W max demand (import / utility) single 
94Old W max demand (export / gen) single 
96Old va utility max demand single 
98Old A utility max demand single 

This is not the complete map: 50 of 157 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

RISH (RM3430i) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Register addressing
3X (30001+) for measured parameters
Data format
two consecutive 16-bit registers per parameter
Settings registers
4X
Settings access
code 03 reads a setting, code 16 writes or changes it
Response example function code
04

Registers in the map: 62 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 single 
2Volts 2 single 
4Volts 3 single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W1 single 
14W2 single 
16W3 single 
18VA1 single 
20VA2 single 
22VA3 single 
24Var1 single 
26Var2 single 
28Var3 single 
30PF1 single 
32PF2 single 
34PF3 single 
36Phase angle 1 single 
38Phase angle 2 single 
40Phase angle 3 single 
42Volts ave single 
44Volts sum single 
46Current ave single 
48Current sum single 
50Watts ave single 
52Watts sum single 
54Va ave single 
56Va sum single 
58Var ave single 
60Var sum single 
62Pf ave single 
64Pf sum single 
66Phase angle ave single 
68Phase angle sum single 
70Freq single 
72Wh import single 
74Wh export single 
76Varh import single 
78Varh export single 
80Vah single 
132Volts ave max single 
134Volts ave min single 
140Current ave max single 
142Current ave min single 
144Active import energyWhsingle 
146Active export energyWhsingle 
148Reactive import energyvarhsingle 
150Reactive export energyvarhsingle 
152Apparent energyVAhsingle 

This is not the complete map: 50 of 62 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.