Schneider Electric PowerLogic ION7400, EM4800 MODBUS registers: read online
Connect Schneider Electric PowerLogic to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Schneider Electric PowerLogic logging and read.
Registers in the map: 2919 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single, utf8(12), utf8(40), word.
MODBUS offset
Description
Units
Data type
Scale
50
Meter model
utf8(40)
1717
Current version
utf8(12)
30
Meter name
utf8(40)
1837
Year
year
word
1838
Month
month
word
1839
Day
days
word
1840
Hour
h
word
1841
Minute
min
word
1842
Second
s
word
1844
Day of week
word
2400
Digital input status validity base unit
word
2402
Digital output status validity base unit
word
2420
Setpoint status validity
word
2550
Digital input status validity option slot A
word
2552
Digital input status validity option slot B
word
2554
Digital input status validity option slot C
word
2556
Digital input status validity option slot D
word
2566
Digital output status validity option slot A
word
2568
Digital output status validity option slot B
word
2570
Digital output status validity option slot C
word
2572
Digital output status validity option slot D
word
2700
Active energy delivered (into load)
kWh
single
2702
Active energy received (out of load)
kWh
single
2704
Active energy delivered + received
kWh
single
2706
Active energy delivered received
kWh
single
2708
Reactive energy delivered
kvarh
single
2710
Reactive energy received
kvarh
single
2712
Reactive energy delivered + received
kvarh
single
2714
Reactive energy delivered received
kvarh
single
2716
Apparent energy delivered
kVAh
single
2718
Apparent energy received
kVAh
single
2720
Apparent energy delivered + received
kVAh
single
2722
Apparent energy delivered received
kVAh
single
2724
Active energy in Q1
kWh
single
2726
Active energy in Q2
kWh
single
2728
Active energy in Q3
kWh
single
2730
Active energy in Q4
kWh
single
2732
Reactive energy in Q1
kvarh
single
2734
Reactive energy in Q2
kvarh
single
2736
Reactive energy in Q3
kvarh
single
2738
Reactive energy in Q4
kvarh
single
2740
Apparent energy in Q1
kVAh
single
2742
Apparent energy in Q2
kVAh
single
2744
Apparent energy in Q3
kVAh
single
2746
Apparent energy in Q4
kVAh
single
2748
Conditional active energy delivered (into load)
kWh
single
2750
Conditional active energy received (out of load)
kWh
single
2754
Active energy delivered received, conditional
kWh
single
2756
Conditional reactive energy in (delivered)
kvarh
single
2758
Conditional reactive energy out (received)
kvarh
single
This is not the complete map: 50 of 2919 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic EM4800 - Measurement Data
Registers in the map: 211 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single, smallint.
MODBUS offset
Description
Units
Data type
Scale
2600
Model
smallint
2601
Model
smallint
2602
Model
smallint
2603
Model
smallint
2604
Model
smallint
2605
Model
smallint
2606
Model
smallint
2607
Model
smallint
2
Meter 2 WH delivered
integer
4
Meter 3 WH delivered
integer
6
Meter 4 WH delivered
integer
8
Meter 5 WH delivered
integer
10
Meter 6 WH delivered
integer
12
Meter 7 WH delivered
integer
14
Meter 8 WH delivered
integer
100
Meter 1 wh received
integer
102
Meter 2 wh received
integer
104
Meter 3 wh received
integer
106
Meter 4 wh received
integer
108
Meter 5 wh received
integer
110
Meter 6 wh received
integer
112
Meter 7 wh received
integer
114
Meter 8 wh received
integer
200
Meter 1 VARh delivered
integer
202
Meter 2 VARh delivered
integer
204
Meter 3 VARh delivered
integer
206
Meter 4 VARh delivered
integer
208
Meter 5 VARh delivered
integer
210
Meter 6 VARh delivered
integer
212
Meter 7 VARh delivered
integer
214
Meter 8 VARh delivered
integer
300
Meter 1 VARh received
integer
302
Meter 2 VARh received
integer
304
Meter 3 VARh received
integer
306
Meter 4 VARh received
integer
308
Meter 5 VARh received
integer
310
Meter 6 VARh received
integer
312
Meter 7 VARh received
integer
314
Meter 8 VARh received
integer
400
Meter 1
VAh
integer
402
Meter 2
VAh
integer
404
Meter 3
VAh
integer
406
Meter 4
VAh
integer
408
Meter 5
VAh
integer
410
Meter 6
VAh
integer
412
Meter 7
VAh
integer
414
Meter 8
VAh
integer
600
Meter 1
W
integer
602
Meter 2
W
integer
604
Meter 3
W
integer
This is not the complete map: 50 of 211 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic ION6200 - MODBUS Mapping
some registers return the low-order word first, their duplicates the high-order word first
Registers in the map: 102 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
0
Serial number
dword
2
Firmware revision
word
3
Oem identification
word
4
Meter options
dword
12
Device type
word
6
# meter power ups
word
7
# peak demand resets
word
8
Meter on-time
dword
10
# flash erase cycles
dword
14
Demand interval down counter
word
99
Vln a
word
100
Vln b
word
101
Vln c
word
102
Vln avg
word
103
Vll ab
word
104
Vll bc
word
105
Vll ca
word
106
Vll avg
word
107
I a
word
108
I b
word
109
I c
word
110
I avg
word
111
I demand
word
112
I peak demand
word
113
I4
word
114
Frequency
smallint
115
PF sign total
smallint
116
PF sign a
smallint
117
PF sign b
smallint
118
PF sign c
smallint
119
kW total
smallint
120
kVAR total
smallint
121
kVA total
smallint
122
kW a
smallint
123
kW b
smallint
124
kW c
smallint
125
kVAR a
smallint
126
kVAR b
smallint
127
kVAR c
smallint
128
kVA a
smallint
129
kVA b
smallint
130
kVA c
smallint
131
kW demand
smallint
132
kW peak demand
smallint
133
kVAR demand
smallint
134
kVA demand
smallint
135
kVAR peak demand
smallint
136
kVA peak demand
smallint
137
kWh del
dword
139
kWh rec
dword
This is not the complete map: 50 of 102 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic ION7300 - MODBUS Registers
Registers in the map: 62 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, word.
MODBUS offset
Description
Units
Data type
Scale
10
Vln a, Modbus Slave 1
word
×0.1
11
Vln b, Modbus Slave 1
word
×0.1
12
Vln c, Modbus Slave 1
word
×0.1
13
Vln avg, Modbus Slave 1
word
×0.1
14
Vll ab, Modbus Slave 1
word
×0.1
15
Vll bc, Modbus Slave 1
word
×0.1
16
Vll ca, Modbus Slave 1
word
×0.1
17
Vll avg, Modbus Slave 1
word
×0.1
18
I a, Modbus Slave 1
word
×0.1
19
I b, Modbus Slave 1
word
×0.1
20
I c, Modbus Slave 1
word
×0.1
21
I avg, Modbus Slave 1
word
×0.1
22
V unbal, Modbus Slave 1
V
word
×0.1
23
I unbal, Modbus Slave 1
word
×0.1
24
Freq, Modbus Slave 1
word
×0.1
25
Phase Rev, Modbus Slave 1
word
×0.1
26
kW a, Modbus Slave 2
kW
integer
×0.1
28
kW b, Modbus Slave 2
kW
integer
×0.1
30
kW c, Modbus Slave 2
kW
integer
×0.1
32
kW tot, Modbus Slave 2
kW
integer
×0.1
34
kVAR a, Modbus Slave 2
kvar
integer
×0.1
36
kVAR b, Modbus Slave 2
kvar
integer
×0.1
38
kVAR c, Modbus Slave 2
kvar
integer
×0.1
40
kVAR tot, Modbus Slave 2
kvar
integer
×0.1
42
kVA a, Modbus Slave 2
kVA
integer
×0.1
44
kVA b, Modbus Slave 2
kVA
integer
×0.1
46
kVA c, Modbus Slave 2
kVA
integer
×0.1
48
kVA tot, Modbus Slave 2
kVA
integer
×0.1
50
PF sign a, Modbus Slave 2
integer
×0.1
52
PF sign b, Modbus Slave 2
integer
×0.1
54
PF sign c, Modbus Slave 2
integer
×0.1
56
PF sign tot, Modbus Slave 2
integer
×0.1
58
kW td, Modbus Slave 3
kW
integer
×0.1
60
kVAR td, Modbus Slave 3
kvar
integer
×0.1
62
kVA td, Modbus Slave 3
kVA
integer
×0.1
64
kW td mx, Modbus Slave 3
kW
integer
×0.1
66
kVAR td mx, Modbus Slave 3
kvar
integer
×0.1
68
kVA td mx, Modbus Slave 3
kVA
integer
×0.1
70
Vln avg mx, Modbus Slave 3
integer
×0.1
72
I avg mx, Modbus Slave 3
integer
×0.1
74
kW tot mx, Modbus Slave 3
kW
integer
×0.1
76
kVAR tot mx, Modbus Slave 3
kvar
integer
×0.1
78
kVA tot mx, Modbus Slave 3
kVA
integer
×0.1
80
Freq mx, Modbus Slave 3
integer
×0.1
82
Vln avg mn, Modbus Slave 3
integer
×0.1
84
I avg mn, Modbus Slave 3
integer
×0.1
86
Freq mn, Modbus Slave 3
integer
×0.1
88
kWh imp (kWh del) 1, Modbus Slave 4
kWh
integer
90
kWh exp (kWh rec) 1, Modbus Slave 4
kWh
integer
92
kWh tot (kWh del+rec) 1, Modbus Slave 4
kWh
integer
This is not the complete map: 50 of 62 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic ION7500-ION7600 - MODBUS Registers
Registers in the map: 290 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
10
Vln a, Volts/Amps/Freq 1
word
×0.1
11
Vln b, Volts/Amps/Freq 1
word
×0.1
12
Vln c, Volts/Amps/Freq 1
word
×0.1
13
Vln avg, Volts/Amps/Freq 1
word
×0.1
14
Vll ab, Volts/Amps/Freq 1
word
×0.1
15
Vll bc, Volts/Amps/Freq 1
word
×0.1
16
Vll ca, Volts/Amps/Freq 1
word
×0.1
17
Vll avg, Volts/Amps/Freq 1
word
×0.1
18
I a, Volts/Amps/Freq 1
word
×0.1
19
I b, Volts/Amps/Freq 1
word
×0.1
20
I c, Volts/Amps/Freq 1
word
×0.1
21
I avg, Volts/Amps/Freq 1
word
×0.1
22
V unbal, Volts/Amps/Freq 1
V
word
×0.1
23
I unbal, Volts/Amps/Freq 1
word
×0.1
24
Freq, Volts/Amps/Freq 1
word
×0.1
25
I4, Volts/Amps/Freq 1
word
×0.1
26
kW a, Power/PF 2
kW
integer
×0.1
28
kW b, Power/PF 2
kW
integer
×0.1
30
kW c, Power/PF 2
kW
integer
×0.1
32
kW tot, Power/PF 2
kW
integer
×0.1
34
kVAR a, Power/PF 2
kvar
integer
×0.1
36
kVAR b, Power/PF 2
kvar
integer
×0.1
38
kVAR c, Power/PF 2
kvar
integer
×0.1
40
kVAR tot, Power/PF 2
kvar
integer
×0.1
42
kVA a, Power/PF 2
kVA
integer
×0.1
44
kVA b, Power/PF 2
kVA
integer
×0.1
46
kVA c, Power/PF 2
kVA
integer
×0.1
48
kVA tot, Power/PF 2
kVA
integer
×0.1
50
PF sign a, Power/PF 2
integer
×0.1
52
PF sign b, Power/PF 2
integer
×0.1
54
PF sign c, Power/PF 2
integer
×0.1
56
PF sign tot, Power/PF 2
integer
×0.1
58
Vll avg mx, Min/Max/Demand 3
integer
×0.1
60
I avg mx, Min/Max/Demand 3
integer
×0.1
62
kW tot mx, Min/Max/Demand 3
kW
integer
×0.1
64
kVAR tot mx, Min/Max/Demand 3
kvar
integer
×0.1
66
kVA tot mx, Min/Max/Demand 3
kVA
integer
×0.1
68
Freq mx, Min/Max/Demand 3
integer
×0.1
70
Vll avg mn, Min/Max/Demand 3
integer
×0.1
72
I avg mn, Min/Max/Demand 3
integer
×0.1
74
Freq mn, Min/Max/Demand 3
integer
×0.1
76
kW sd del-rec, Min/Max/Demand 3
kW
integer
×0.1
78
kVA sd del+rec, Min/Max/Demand 3
kVA
integer
×0.1
80
kVAR sd del-rec, Min/Max/Demand 3
kvar
integer
×0.1
82
kW sd mx d-r, Min/Max/Demand 3
kW
integer
×0.1
84
kVA sd mx d+r, Min/Max/Demand 3
kVA
integer
×0.1
86
kVAR sd mx d-r, Min/Max/Demand 3
kvar
integer
×0.1
88
Phase Rev, Min/Max/Demand 3
integer
×0.1
90
kWh del, Energy/THD 4
kWh
integer
×0.1
92
kWh rec, Energy/THD 4
kWh
integer
×0.1
This is not the complete map: 50 of 290 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Schneider Electric PowerLogic ION7550-ION7650 - Measurement Data
Registers in the map: 227 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
149
I a, Amp/freq/unbal
word
×0.1
150
I b, Amp/freq/unbal
word
×0.1
151
I c, Amp/freq/unbal
word
×0.1
152
I 4, Amp/freq/unbal
word
×0.1
153
I 5, Amp/freq/unbal
word
×0.1
154
I avg, Amp/freq/unbal
word
×0.1
155
I avg mn, Amp/freq/unbal
word
×0.1
156
I avg mx, Amp/freq/unbal
word
×0.1
157
I avg mean, Amp/freq/unbal
word
×0.1
158
Freq, Amp/freq/unbal
word
×0.1
159
Freq mn, Amp/freq/unbal
word
×0.1
160
Freq mx, Amp/freq/unbal
word
×0.1
161
Freq mean, Amp/freq/unbal
word
×0.1
162
V unbal, Amp/freq/unbal
V
word
×0.1
163
I unbal, Amp/freq/unbal
word
×0.1
164
Phase Rev, Amp/freq/unbal
word
×0.1
165
Vln a
V
dword
×0.1
167
Vln b
V
dword
×0.1
169
Vln c
V
dword
×0.1
171
Vln avg
V
dword
×0.1
173
Vln avg mx
V
dword
×0.1
177
Vll ab
V
dword
×0.1
179
Vll bc
V
dword
×0.1
181
Vll ca
V
dword
×0.1
183
Vll avg
V
dword
×0.1
185
Vll avg mx
V
dword
×0.1
187
Vll avg mean
V
dword
×0.1
197
kW a, kW/kVAr/kVA
kW
integer
×1000
199
kW b, kW/kVAr/kVA
kW
integer
×1000
201
kW c, kW/kVAr/kVA
kW
integer
×1000
203
kW tot, kW/kVAr/kVA
kW
integer
×1000
205
kW tot mx, kW/kVAr/kVA
kW
integer
×1000
207
kVAR a, kW/kVAr/kVA
kvar
integer
×1000
209
kVAR b, kW/kVAr/kVA
kvar
integer
×1000
211
kVAR c, kW/kVAr/kVA
kvar
integer
×1000
213
kVAR tot, kW/kVAr/kVA
kvar
integer
×1000
215
kVAR tot mx, kW/kVAr/kVA
kvar
integer
×1000
217
kVA a, kW/kVAr/kVA
kVA
integer
×1000
219
kVA b, kW/kVAr/kVA
kVA
integer
×1000
221
kVA c, kW/kVAr/kVA
kVA
integer
×1000
223
kVA tot, kW/kVAr/kVA
kVA
integer
×1000
225
kVA tot mx, kW/kVAr/kVA
kVA
integer
×1000
229
kWh del, kWh/kVArh
kWh
integer
×1000
231
kWh rec, kWh/kVArh
kWh
integer
×1000
233
kVARh del, kWh/kVArh
kvarh
integer
×1000
235
kVARh rec, kWh/kVArh
kvarh
integer
×1000
237
kVAh del+rec, kWh/kVArh
kvarh
integer
×1000
261
PF sign a, PF/THD/Kfactor
smallint
×0.01
262
PF sign b, PF/THD/Kfactor
smallint
×0.01
263
PF sign c, PF/THD/Kfactor
smallint
×0.01
This is not the complete map: 50 of 227 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
Your current browser does not support the Web Serial API required to access local COM ports. Please use a Chromium-based browser like Google Chrome, Microsoft Edge, or Opera.