Secure (Elite 103,Elite 303, Elite 307) data logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
16 | MODBUS ID ( start from 1 up to 247) | | single |
18 | Protocol version (MS byte) and revision (LS byte) | | word |
19 | MODBUS baud rate | | single |
29 | Metre type: 3W/4Wire info | | single |
31 | CT primary | Amp | single |
33 | Ct secondary | Amp | single |
35 | PT primary | Volt | single |
37 | PT secondary | Volt | single |
39 | Pole: number of poles for RPM | | single |
41 | Slip: slip of the motor | | single |
43 | Update rate: display update rates | | single |
45 | Energy reset : 0x01 | | single |
47 | Demand reset: 0x01 | | single |
49 | Demand time | | single |
51 | Alert ON/OFF | | single |
55 | Alert threshold high current | | single |
57 | Alert threshold high PF | | single |
59 | Alert threshold high frequency | | single |
61 | Alert threshold high W | | single |
63 | Alert threshold high VAr | | single |
65 | Alert threshold high VA | | single |
69 | Alert threshold low current | | single |
71 | Alert threshold low PF | | single |
73 | Alert threshold low frequency | | single |
75 | Alert threshold low W | | single |
77 | Alert threshold low VAr | | single |
79 | Alert threshold low VA | | single |
99 | V1: R phase to neutral voltage | Volt | single |
101 | V2: Y phase to neutral voltage | Volt | single |
103 | V3: B phase to neutral voltage | Volt | single |
105 | Vavg: average voltage | Volt | single |
107 | V12: RY voltage | Volt | single |
109 | V23: YB voltage | Volt | single |
111 | V31: BR voltage | Volt | single |
113 | L1: R phase line current | Amp | single |
115 | L2: Y phase line current | Amp | single |
117 | L3: B phase line current | Amp | single |
119 | LN: neutral line current | Amp | single |
133 | Q1: power factor | | single |
135 | Q2: power factor | | single |
137 | Q3: power factor | | single |
139 | QA: avg power factor | | single |
141 | KT1: R- phase active power | W | single |
143 | KT2: Y- phase active power | W | single |
145 | KT3: B- phase active power | W | single |
147 | KT: 3 phase active power | W | single |
149 | KV1: R- phase reactive power | VAr | single |
151 | KV2: Y- phase reactive power | VAr | single |
153 | KV3: B- phase reactive power | VAr | single |
155 | KV: 3 phase reactive power | VAr | single |
There are more MODBUS items for this device. Please, download the program. |
Secure (Elite 103,Elite 303, Elite 307) data logging
Secure (Elite 440) data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.