Sinotimer (DDS578) data logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
2 | Voltage B | V | single |
4 | Voltage C | V | single |
8 | Current A | A | single |
10 | Current B | A | single |
12 | Current C | A | single |
16 | Total active power | KW | single |
18 | Active power A | KW | single |
20 | Active power B | KW | single |
22 | Active power C | KW | single |
24 | Total reactive power | VAr | single |
26 | Reactive power A | VAr | single |
28 | Reactive power B | VAr | single |
30 | Reactive power C | VAr | single |
42 | Power factor A | | single |
44 | Power factor B | | single |
46 | Power factor C | | single |
54 | Frequency | Hz | single |
256 | Total active power | kWh | single |
1024 | Total reactive power | kVarh | single |