Sigineer Grid Inverter MODBUS registers: read online

Connect Sigineer to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Sigineer data logger and record.

Do you not know the meter address? Scan the device address online

Sigineer (Grid Inverter) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Function codes
04 read input registers
Register addressing
addresses listed in hex and decimal, used directly as 0-based offsets
Data format
16-bit values (2 bytes)
Scaling
scale ratio given per row

Registers in the map: 30. function 4 (input registers). byte order big-endian. data types: word.

MODBUS offsetDescriptionUnitsData typeScale
1Master version word×0.01
0Ambient temperaturedeg Cword×0.1
2Year, month'word 
3Date, time word 
4Minutes, seconds word 
5Battery status word 
6Battery voltageVword×0.1
7Battery currentAword×0.1
8Input frequencyHzword×0.01
9Input voltageVword×0.1
10Input appa.p AVAword 
11Input acti.pWword 
12Inverter frequencyHzword×0.01
13Inverter voltageVword×0.1
14Inverter currentAword×0.1
15Inverter acti.pWword 
16Pv voltageVword×0.1
17Pv currentAword×0.1
18Pv powerWword 
19Bus voltageVword×0.1
20System geneeraating capacity lowkWhword×0.01
21System generating capacity highKSHword 
22System total generating capacity lowKSHword 
23System total generating capacity highKSHword 
24Load voltageVword×0.1
25Load currentAword×0.1
26Load acti.pWword 
27Load appa.pVAword 
28Load percentage%word×0.1
33Soc%word 