Socomec Countis E50 E53 E50R E53R logging. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
9999 | SOCO | | string(8) |
10003 | Product order ID (Countis:100, protection:200, atys:300, diris:400) | | word |
10004 | Product ID | | word |
10005 | JBUS table version | | word |
10006 | Product software version | | word |
10009 | Serial_order | | word |
10010 | Serial_Reserve | | dword |
10017 | Product version (Major) | | word |
10018 | Product version (Minor) | | word |
10019 | Product version (Revision) | | word |
10020 | Product version (Build) | | word |
10024 | Software technical base version (Major) | | word |
10025 | Software technical base version (Minor) | | word |
10026 | Software technical base version (Revision) | | word |
10027 | Customization version (Major) | | word |
10028 | Customization version (Minor) | | word |
10029 | Product VLO | | string(8) |
10033 | Customization VLO | | string(8) |
10037 | Software technical base VLO | | string(8) |
10041 | Vendor name | | string(16) |
10049 | Product name | | string(16) |
10057 | Extended name | | string(16) |
17345 | Current transformer primary | A | word |
10511 | Hour meter | h / 100 | dword |
10513 | Phase to phase voltage: U12 | V / 100 | dword |
10515 | Phase to phase voltage: U23 | V / 100 | dword |
10517 | Phase to phase voltage: U31 | V / 100 | dword |
10519 | Simple voltage: V1 | V / 100 | dword |
10521 | Simple voltage: V2 | V / 100 | dword |
10523 | Simple voltage: V3 | V / 100 | dword |
10527 | Current: I1 | A / 1000 | dword |
10529 | Current: I2 | A / 1000 | dword |
10531 | Current: I3 | A / 1000 | dword |
10535 | Active power | W / 0.1 | integer |
10537 | Reactive power | var / 0.1 | integer |
10539 | Apparent power | VA / 0.1 | dword |
10541 | Power factor | - / 1000 | integer |
10543 | Active power phase 1 | W / 0.1 | integer |
10545 | Active power phase 2 | W / 0.1 | integer |
10547 | Active power phase 3 | W / 0.1 | integer |
10549 | Reactive power phase 1 | var / 0.1 | integer |
10551 | Reactive power phase 2 | var / 0.1 | integer |
10553 | Reactive power phase 3 | var / 0.1 | integer |
10555 | Apparent power phase 1 | VA / 0.1 | dword |
10557 | Apparent power phase 2 | VA / 0.1 | dword |
10559 | Apparent power phase 3 | VA / 0.1 | dword |
10561 | Power factor phase 1 | - / 1000 | integer |
10563 | Power factor phase 2 | - / 1000 | integer |
10565 | Power factor phase 3 | - / 1000 | integer |
10769 | Total positive active energy (no resetable) | Wh / 0.001 | dword |
There are more MODBUS items for this device. Please, download the program. |
Socomec (DIRIS I31) data logging
Socomec (DIRIS U10) data logging
Socomec (DIRIS U20) data logging
Socomec (DIRIS U30) data logging
Socomec (DIRIS,D30,D50,D70) data logging
Socomec (Multis L20, Multis L40) data logging
Socomec Countis E03 data logging
Socomec Countis E04 data logging
Socomec Countis E13 data logging
Socomec Countis E14 data logging
Socomec Countis E23 data logging
Socomec Countis E24 data logging
Socomec Countis E33 E43 data logging
Socomec Countis E34 E44 data logging
Socomec Countis E50 E53 E50R E53R data logging
Socomec Countis E63 data logging
Socomec Countis ECI2 data logging
Socomec Countis ECI3 data logging
Socomec DIRIS A20 modbus data logging
Socomec DIRIS A40-A41-RS485 data logging
Socomec Masterys data logging
Socomec NETYS PR NETYS RT ITYS data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.