Socomec DIRIS - MODBUS Registers Map - Logging

The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Socomec DIRIS logging and record.

Do you not know the meter address? Scan the device address online

Socomec DIRIS A20 modbus - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
768
Phase 1 current
 
dword
770
Phase 2 current
 
dword
772
Phase 3 current
 
dword
774
Neutral current
 
dword
776
Phase to phase voltage U12
V
dword
778
Phase to phase voltage U23
V
dword
780
Phase to phase voltage U31
V
dword
782
Phase to neutral voltage phase 1
V
dword
784
Phase to neutral voltage phase 2
V
dword
786
Phase to neutral voltage phase 3
V
dword
788
Frequency
Hz
dword
790
E active power
kW
dword
792
E reactive power
kvar
dword
794
E apparent power
kVA
dword
796
E power factor
 
dword
838
Average value I1 max
 
dword
840
Average value I2 max
 
dword
842
Average value I3 max
 
dword
844
E active power + max
kW
dword
856
Active energy +
 
dword
858
Reactive energy +
 
dword
916
Average value in max
 
dword
1792
Phase 1 current
 
word
1793
Phase 2 current
 
word
1794
Phase 3 current
 
word
1795
Neutral current
 
word
1796
Phase to phase voltage U12
V
word
1797
Phase to phase voltage U23
V
word
1798
Phase to phase voltage U31
V
word
1799
Phase to neutral voltage phase 1
V
word
1800
Phase to neutral voltage phase 2
V
word
1801
Phase to neutral voltage phase 3
V
word
1802
Frequency
Hz
word
1803
E active power
kW
word
1804
E reactive power
kvar
word
1805
E apparent power
kVA
word
1806
E power factor
 
word
1827
Average value I1 max
 
word
1828
Average value I2 max
 
word
1829
Average value I3 max
 
word
1830
E active power + average value max
kW
word
1835
Active power + < 10 000
 
word
1836
Active power + > 10 000
 
word
1837
Reactive power + < 10 000
 
word
1838
Reactive power + > 10 000
 
word
1891
Average value in max
 
word
2816
Phase 1 current
 
word
2817
Phase 2 current
 
word
2818
Phase 2 current
 
word
2819
Neutral current
 
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Socomec DIRIS A40-A41-RS485 - MODBUS Registers

MODBUS offset
Description
Units
Data type
10511
Hour meter
1
dword
10513
Phase to phase voltage u12
V
dword
10515
Phase to phase voltage u23
V
dword
10517
Phase to phase voltage u31
V
dword
10519
Phase to neutral voltage phase 1
V
dword
10521
Phase to neutral voltage phase 2
V
dword
10523
Phase to neutral voltage phase 3
V
dword
10525
Frequency
Hz
dword
10527
Phase current 1
 
dword
10529
Phase current 2
 
dword
10531
Phase current 3
 
dword
10533
Neutral current
 
dword
10535
- active power +/-
kW
dword
10537
- reactive power +/-
kvar
dword
10539
- apparent power
kVA
dword
10541
- power factor -: leading and + : lagging
 
dword
10543
Active power phase 1 +/-
kW
dword
10545
Active power phase 2 +/-
kW
dword
10547
Active power phase 3 +/-
kW
dword
10549
Reactive power phase 1 +/-
kvar
dword
10551
Reactive power phase 2 +/-
kvar
dword
10553
Reactive power phase 3 +/-
kvar
dword
10555
Apparent power phase 1
kVA
dword
10557
Apparent power phase 2
kVA
dword
10559
Apparent power phase 3
kVA
dword
10561
Power factor phase 1 -: leading and + : lagging
 
dword
10563
Power factor phase 2 -: leading and + : lagging
 
dword
10565
Power factor phase 3 -: leading and + : lagging
 
dword
10767
Hour meter
1
dword
10769
Active energy +
 
dword
10773
Apparent apparente
 
dword
10775
Active energy -
 
dword
10777
Active energy +
 
dword
10779
No. compteurs d'impulsions
 
dword
10783
Pulse meter 2
 
dword
10785
Pulse meter 3
 
dword
10787
Pulse meter 4
 
dword
10789
Pulse meter 5
 
dword
10803
S predicted reactive power
kvar
dword
10805
S predicted apparent power
kVA
dword
10807
Ea+ between 2 tops
 
dword
10809
Ea- between 2 tops
 
dword
10813
Er- between 2 tops
 
dword
11029
Avg v1
V
dword
11033
Avg v3
V
dword
11035
Avg f
Hz
dword
11037
Avg i1
 
dword
11039
Avg i2
 
dword
11043
Avg in
 
dword
11045
Avg - active power +
kW
dword
There are more MODBUS items for this device. Please download the program to discover all registers.