Sinotimer DDS519, DDS548, DDS578 MODBUS registers: read online

Connect Sinotimer to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Sinotimer logging and read.

Do you not know the meter address? Scan the device address online

Sinotimer (DDS519) - MODBUS Mapping

Registers in the map: 6. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0VoltageVsingle 
8CurrentAsingle 
18Active powerkWsingle 
42Power factor single 
54FrequencyHzsingle 
256Total active energykWhsingle 

Sinotimer (DDS548) - MODBUS Values

Registers in the map: 6. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0VoltageVsingle 
8CurrentAsingle 
16Active powerkWhsingle 
42Power factor single 
54FrequencyHzsingle 
256Total active powerkWhsingle 

Sinotimer (DDS578) - Measurement Data

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS-485
Default baud rate
1200, 2400, 4800 or 9600 bps (selectable)
Data bits
8
Stop bits
1
Parity
even
Frame format
address + function code + data + CRC
Data registers
read only, function code 04
Parameter registers
read with function code 03, written with function code 10
Data format
IEEE 754 32-bit floats (4 bytes, two registers)
Device address range
1-247
Example frame device address
01

Registers in the map: 20. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage AVsingle 
2Voltage BVsingle 
4Voltage CVsingle 
8Current AAsingle 
10Current BAsingle 
12Current CAsingle 
16Total active powerkWsingle 
18Active power AkWsingle 
20Active power BkWsingle 
22Active power CkWsingle 
24Total reactive powervarsingle 
26Reactive power Avarsingle 
28Reactive power Bvarsingle 
30Reactive power Cvarsingle 
42Power factor A single 
44Power factor B single 
46Power factor C single 
54FrequencyHzsingle 
256Total active powerkWhsingle 
1024Total reactive powerkvarhsingle 