Socomec Masterys - MODBUS Registers Map - Data Logging
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Socomec Masterys logging and capture.
Socomec Masterys - MODBUS Registers
MODBUS offset
Description
Units
Data type
96
Load phase 1 (M00)
%
word
97
Load phase 2 (M01)
%
word
98
Load phase 3 (M02)
%
word
99
Total load: - (phase 1+2+3) - (nD of phases) (M03)
%
word
100
Battery capacity(1) remaining battery capacity % (2) (M04)
%
word
101
Battery capacity(1) remaining battery capacity (2) (M05)
Ah
word
102
Auxiliary mains star voltage v1 (M06)
V
word
103
Auxiliary mains star voltage v2 (M07)
V
word
104
Auxiliary mains star voltage v3 (M08)
V
word
105
Output star voltage v1 (M09)
V
word
106
Output star voltage v2 (M10)
V
word
107
Output star voltage v3 (M11)
V
word
108
Input current phase l1 (M12)
A
word
109
Input current phase l2 (M13)
A
word
110
Input current phase l3 (M14)
A
word
111
Output current phase l1 (M15)
A
word
112
Output current phase l2 (M16)
A
word
113
Output current phase l3 (M17)
A
word
114
Auxiliary frequency (M18)
Hz
word
115
Output frequency (M19)
Hz
word
116
Positive battery voltage (3) (M20)
V
word
117
Negative battery voltage (3) (M21)
V
word
118
Internal UPS temperature (M22)
DC
word
119
Remaining back-up time (M23)
Minutes
word
120
Battery current (M24)
A
word
121
Inverter current phase l1 (M25)
A
word
122
Inverter current phase l2 (M26)
A
word
123
Inverter current phase l3 (M27)
A
word
124
Positive rectifier voltage (+) (M28)
V
word
125
Negative rectifier voltage (-) (M29)
V
word
129
Input mains star voltage v1 (M33)
V
word
130
Input mains star voltage v2 (M34)
V
word
131
Input mains star voltage v3 (M35)
V
word
132
Output active power (4) (M36)
kW
word
133
Output power phase 1 (M37)
KVA
word
134
Output power phase 2 (M38)
KVA
word
135
Output power phase 3 (M39)
KVA
word
136
Input power phase 1 (M40)
KVA
word
137
Input power phase 2 (M41)
KVA
word
138
Input power phase 3 (M42)
KVA
word
139
Input mains frequency (M43)
Hz
word
Related MODBUS registers maps