Tyco Electronics Integra 1630 MODBUS registers: read online

Connect Tyco Electronics to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Tyco Electronics data logger and record.

Do you not know the meter address? Scan the device address online

Tyco Electronics (Integra 1630) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
Register addressing, measured values
3xxxx input registers 30001-30255, start address in hex
Register addressing, settings
4X holding registers
Function codes
03 read, 16 write
Register layout
two consecutive registers per parameter
Write limit
one parameter per message
Maximum parameters per request
40
Device address range
1-247
Password register range
0000-9999
Password write rule
must be written before changing password protected settings
Password read value
returns 1 when unprotected

Registers in the map: 62 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 (L1 N 4w or L1 L2 3w) single 
2Volts 2 (L2 N 4w or L2 L3 3w) single 
4Volts 3 (L3 N 4w or L3 L1 3w) single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W phase 1 single 
14W phase 2 single 
16W phase 3 single 
18Va phase 1 single 
20Va phase 2 single 
22Va phase 3 single 
24Var phase 1 single 
26Var phase 2 single 
28Var phase 3 single 
30Power factor phase 1 single 
32Power factor phase 2 single 
34Power factor phase 3 single 
36Phase angle phase 1 single 
38Phase angle phase 2 single 
40Phase angle phase 3 single 
42Volts ave single 
46Current ave single 
48Current sum single 
52Watts sum single 
56Va sum single 
60Var sum single 
62Power factor ave single 
66Average phase angle single 
70Frequency single 
72Wh import single 
74Wh export single 
76Varh import single 
78Varh export single 
80Vah single 
84W demand import single 
86W max. Demand import single 
100Va demand single 
102Va max. Demand single 
104A demand single 
106A max. Demand single 
200V L1 L2 single 
202V L2 L3 single 
204V L3 L1 single 
206Average line to lineVsingle 
224Neutral current single 
234Thd volts 1 single 
236Thd volts 2 single 
238Thd volts 3 single 
240Thd current 1 single 

This is not the complete map: 50 of 62 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.