ABB UNO DM PLUS MODBUS registers: read online

Connect ABB to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous ABB logging and read.

Do you not know the meter address? Scan the device address online

ABB (UNO DM PLUS) - Measurement Data

Registers in the map: 248 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, smallint, utf8(8), word.

MODBUS offsetDescriptionUnitsData typeScale
40070AC CurrentAword×10A_SF
40071Phase A CurrentAword×10A_SF
40072Phase B CurrentAword×10A_SF
40073Phase C CurrentAword×10A_SF
40074Scale factor [A_SF] smallint 
40075Phase Voltage ABVword×10V_SF
40076Phase Voltage BCVword×10V_SF
40077Phase Voltage CAVword×10V_SF
40078Phase Voltage ANVword×10V_SF
40079Phase Voltage BNVword×10V_SF
40080Phase Voltage CNVword×10V_SF
40081Scale factor [V_SF] smallint 
40082AC PowerWsmallint×10W_SF
40083Scale factor [W_SF] smallint 
40084Line FrequencyHzword×10HZ_SF
40085Scale factor [HZ_SF] smallint 
40086AC Apparent PowerVAsmallint×10VA_SF
40087Scale factor [VA_SF] smallint 
40088AC Reactive Powervarsmallint×10VAR_SF
40089Scale factor [VAR_SF] smallint 
40090AC Power Factor%smallint×10PF_SF
40091Scale factor [PF_SF] smallint 
40092AC EnergyWhdword×10WH_SF
40094Scale factor [WH_SF] smallint 
40095DC CurrentAword×10DCA_SF
40096Scale factor [DCA_SF] smallint 
40097DC VoltageVword×10DCV_SF
40098Scale factor [DCV_SF] smallint 
40099DC PowerWsmallint×10DCW_SF
40100Scale factor [DCW_SF] smallint 
40101Cabinet Temperaturedeg Csmallint×10TMP_SF
40102Heat Sink Temperaturedeg Csmallint×10TMP_SF
40103Transformer Temperaturedeg Csmallint×10TMP_SF
40104Other Temperaturedeg Csmallint×10TMP_SF
40105Scale factor [TMP_SF] smallint 
40106Enumerated value. Operating state word 
40107Vendor specific operating state code word 
40108Bitmask value. Event fields dword 
40110Reserved for future use dword 
40112Vendor defined events dword 
40114Vendor defined events dword 
40116Vendor defined events dword 
40118Vendor defined events dword 
40122Type of DER device. Default value is 4 to indicate PV device. word 
40123Continuous power output capability of the inverter.Wword×10WRTG_SF
40124Scale factor smallint 
40125Continuous capability of the inverter.VAword×10VARTG_SF
40126Scale factor smallint 
40127Continuous VAR capability of the inverter in Q1.varsmallint×10VARRTG_SF
40128Continuous VAR capability of the inverter in Q2.varsmallint×10VARRTG_SF

This is not the complete map: 50 of 248 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.