Connect Acrel to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Acrel logger and poll.
Do you not know the meter address? Scan the device address online
Acrel (ADW300) - MODBUS Values
Registers in the map: 130 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 1 | 2 | | word | |
| 20 | Voltage of A phase | | word | |
| 21 | Voltage of B phase | | word | |
| 22 | Voltage of C phase | | word | |
| 23 | Voltage between A-B | | word | |
| 24 | Voltage between B-C | | word | |
| 25 | Voltage between C-A | | word | |
| 26 | Electricity of A phase | A | word | ×0.01 |
| 27 | Electricity of B phase | A | word | ×0.01 |
| 28 | Electricity of C phase | A | word | ×0.01 |
| 29 | Vector sum of 3-phase current | A | word | ×0.01 |
| 30 | Active power of A phase | kW | dword | ×0.001 |
| 32 | Active power of B phase | kW | dword | ×0.001 |
| 34 | Active power of C phase | kW | dword | ×0.001 |
| 36 | Total active power | kW | dword | ×0.001 |
| 38 | Reactive power of A phase | kvar | dword | ×0.001 |
| 40 | Reactive power of B phase | kvar | dword | ×0.001 |
| 42 | Reactive power of C phase | kvar | dword | ×0.001 |
| 44 | Total reactive power | kVA | dword | ×0.001 |
| 46 | Apparent power of A phase | kVA | dword | ×0.001 |
| 48 | Apparent power of B phase | kVA | dword | ×0.001 |
| 50 | Apparent power of C phase | kVA | dword | ×0.001 |
| 52 | Total apparent power | kVA | dword | ×0.001 |
| 54 | Power factor of A phase | | word | ×0.001 |
| 55 | Power factor of B phase | | word | ×0.001 |
| 56 | Power factor of C phase | | word | ×0.001 |
| 57 | Total power factor | | word | ×0.001 |
| 58 | State of DI | | word | |
| 59 | Frequency of power | | word | ×0.01 |
| 60 | Total energy consumption | kWh | dword | ×0.01 |
| 62 | Forward active energy consumption | kWh | dword | ×0.01 |
| 64 | Reversing active energy consumption | kWh | dword | ×0.01 |
| 66 | Forward reactive energy consumption | kvarh | dword | ×0.01 |
| 68 | Reversing reactive energy consumption | kvarh | dword | ×0.01 |
| 70 | Total energy consumption on phase | kWh | dword | ×0.01 |
| 72 | Forward active energy consumption on phase | kWh | dword | ×0.01 |
| 74 | Reversing active energy consumption on phase | kWh | dword | ×0.01 |
| 76 | Consumption on A phase | kvarh | dword | ×0.01 |
| 78 | Reversing reactive energy consumption on phase | kvarh | dword | ×0.01 |
| 80 | Total energy consumption on B phase | kWh | dword | ×0.01 |
| 82 | Forward active energy consumption on B phase | kWh | dword | ×0.01 |
| 84 | Reversing active energy consumption on B phase | kWh | dword | ×0.01 |
| 86 | Forward reactive energy consumption on B phase | kvarh | dword | ×0.01 |
| 88 | Reversing reactive energy consumption on B phase | kvarh | dword | ×0.01 |
| 90 | Total energy consumption on phase | kWh | dword | ×0.01 |
| 92 | Forward active energy consumption on C phase | kWh | dword | ×0.01 |
| 94 | Reversing active energy consumption on C phase | kWh | dword | ×0.01 |
| 96 | Forward reactive energy consumption on C phase | kvarh | dword | ×0.01 |
| 98 | Reversing reactive energy consumption on C phase | kvarh | dword | ×0.01 |
| 100 | Maximum forward active demand in current month | kW | dword | ×0.001 |
This is not the complete map: 50 of 130 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Acrel (DTSD1352) - MODBUS Maps
Connection and addressing notes
- Protocol
- Modbus RTU
- Interface
- RS-485 (two wires, shielded twisted pair)
- Parity
- none, even
- Communication settings register
- 003FH
- Address register
- 003FH high byte, range 1-247
- Baud rate register
- 003FH low byte, baud rate code
- Function codes
- 03H read, 10H write
- Bus length
- up to 1200 m
Registers in the map: 87 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Current total active energy | kWh | dword | formula |
| 2 | Current spike total active energy | kWh | dword | formula |
| 4 | Current peak total active energy | kWh | dword | formula |
| 6 | Current flat total active energy | kWh | dword | formula |
| 8 | Current valley total active energy | kWh | dword | formula |
| 10 | Current forward active total energy | kWh | dword | formula |
| 12 | Current forward active spike energy | kWh | dword | formula |
| 14 | Current forward active energy peak | kWh | dword | formula |
| 16 | Current forward active flat energy | kWh | dword | formula |
| 18 | Current forward active valley energy | kWh | dword | formula |
| 20 | Current reversing active total energy | kWh | dword | formula |
| 22 | Current reversing active spike energy | | dword | |
| 24 | Current reversing active energy peak | | dword | |
| 26 | Current reversing active flat energy | | dword | |
| 28 | Current reversing active valley energy | | dword | |
| 30 | Current total reactive energy | | dword | |
| 32 | Current total reactive spike energy | | dword | |
| 34 | Current total reactive peak energy | | dword | |
| 36 | Current total reactive flat energy | | dword | |
| 38 | Current total reactive energy valley | | dword | |
| 40 | Current forward reactive total energy | | dword | |
| 42 | Current forward reactive spike energy | | dword | |
| 44 | Current forward reactive energy peak | | dword | |
| 46 | Current forward reactive flat energy | | dword | |
| 48 | Current forward reactive valley energy | | dword | |
| 50 | Current reversing reactive total energy | | dword | |
| 52 | Current reversing reactive spike energy | | dword | |
| 54 | Current reversing reactive energy peak | | dword | |
| 56 | Current reversing reactive flat energy | | dword | |
| 58 | Current reversing reactive valley energy | | dword | |
| 60 | Time: second, minute | | word | |
| 61 | Time: hour; day | | word | |
| 62 | Time: month, year | | word | |
| 64 | Pulse constant | | word | |
| 97 | Voltage of A phase | V | word | formula |
| 98 | Voltage of B phase | V | word | formula |
| 99 | Voltage of C phase | V | word | formula |
| 100 | Current of phase A | A | word | formula |
| 101 | Current of phase B | A | word | formula |
| 102 | Current of phase C | A | word | formula |
| 119 | Frequency | Hz | word | formula |
| 120 | Voltage between A-B | V | word | formula |
| 121 | Voltage between C-B | V | word | formula |
| 122 | Voltage between A-C | V | word | formula |
| 123 | Forward active maximum demand | | word | |
| 124 | Time of occurrence: minute, hour | | word | |
| 125 | Time of occurrence: day, month | | word | |
| 126 | Reversing active maximum demand | | word | |
| 127 | Time of occurrence: minute, hour | | word | |
| 128 | Time of occurrence: day, month | | word | |
This is not the complete map: 50 of 87 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Acrel (PZ300) - Measurement Data
Registers in the map: 35. function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | 1 voltage effective value | V | dword | formula |
| 2 | 2 voltage effective value | | dword | formula |
| 4 | 3 voltage effective value | | dword | formula |
| 6 | Average voltage effective value | | dword | formula |
| 8 | 1 current effective value | A | dword | formula |
| 10 | 2 current effective value | | dword | formula |
| 12 | 3 current effective value | | dword | formula |
| 14 | Total current effective value | | dword | formula |
| 16 | 1 active power effective value | W | dword | formula |
| 18 | 2 active power effective value | | dword | formula |
| 20 | 3 active power effective value | | dword | formula |
| 22 | 1 reactive power effective value | var | dword | formula |
| 24 | 2 reactive power effective value | | dword | formula |
| 26 | 3 reactive power effective value | | dword | formula |
| 28 | 1 apparent power effective value | VA | dword | formula |
| 30 | 2 apparent power effective value | | dword | formula |
| 32 | 3 apparent power effective value | | dword | formula |
| 34 | 1 power factor effective value | | dword | formula |
| 36 | 2 power factor effective value | | dword | formula |
| 38 | 3 power factor effective value | | dword | formula |
| 40 | Total active power effective value | W | dword | formula |
| 42 | Total reactive power effective value | var | dword | formula |
| 44 | Total apparent power effective value | VA | dword | formula |
| 46 | Total power factor effective value | | dword | formula |
| 48 | Frequency effective value | Hz | dword | formula |
| 50 | Pt ratio | | word | |
| 51 | Ct ratio | | word | |
| 52 | 1 active electric energy | | dword | |
| 54 | 2 active electric energy | | dword | |
| 56 | 3 active electric energy | | dword | |
| 58 | Total active electric energy | | dword | |
| 60 | 1 reactive electric energy | Wh | dword | |
| 62 | 2 reactive electric energy | | dword | |
| 64 | 3 reactive electric energy | | dword | |
| 66 | Total reactive electric energy | | dword | |
Acrel (PZ72-E3,P80-E3,PZ96-E3) - MODBUS Registers Map
Connection and addressing notes
- Protocol
- Modbus RTU
- Interface
- RS-485
- Default baud rate
- 9600 bps
- Data bits
- 8
- Stop bits
- 1
- Parity
- none
- Default password
- 0001
- Checksum
- CRC16
- Device address range
- 1-247
- Baud rate register
- 0001H low byte, 0 = 38400, 1 = 19200, 2 = 9600, 3 = 4800 bps
- Additional selectable baud rates
- 1200, 2400, 4800, 19200 bps
- Function codes
- 03H read, 04H read, 10H write
Registers in the map: 39. function 3 (holding registers). byte order big-endian. data types: dword, single, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 3 | Pt ratio | | word | |
| 4 | Ct ratio | | word | |
| 35 | Decimal point U | | word | formula |
| 36 | Decimal point PQ | | word | formula |
| 34 | The statement of relays | | word | |
| 37 | Phase voltage A | V | word | formula |
| 38 | Phase voltage B | V | word | formula |
| 39 | Phase voltage C | V | word | formula |
| 40 | Line voltage AB | V | word | formula |
| 41 | Line voltage BC | V | word | formula |
| 42 | Line voltage AC | V | word | formula |
| 43 | Ia | A | word | formula |
| 44 | Ib | A | word | formula |
| 45 | Ic | A | word | formula |
| 46 | Pa | | word | formula |
| 47 | Pb | | word | formula |
| 48 | Pc | | word | formula |
| 49 | P total | | word | formula |
| 50 | Qa | | word | formula |
| 51 | Qb | | word | formula |
| 52 | Qc | | word | formula |
| 53 | Q total | | word | formula |
| 54 | Cosa | | word | ×0.001 |
| 55 | Cosb | | word | ×0.001 |
| 56 | Cosc | | word | ×0.001 |
| 57 | Cos total | | word | ×0.001 |
| 58 | Sa | | word | |
| 59 | Sb | | word | |
| 60 | Sc | | word | |
| 61 | S total | | word | |
| 62 | Frequency F | | word | ×0.01 |
| 63 | Measued im | kWh | dword | formula |
| 65 | Measued export | kWh | dword | formula |
| 67 | Measued import | kvarh | dword | formula |
| 69 | Measued export | kvarh | dword | formula |
| 71 | Real import | kWh | single | |
| 73 | Real export | kWh | single | |
| 75 | Real import | kvarh | single | |
| 77 | Real export | kvarh | single | |
Acrel (PZ80) - MODBUS Maps
Registers in the map: 17. function 3 (holding registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Voltage (effective value) | V | word | |
| 1 | Voltage (index) | | word | |
| 2 | Current (effective value) | A | word | |
| 3 | Current (index) | | word | |
| 4 | Frequency (effective value) | Hz | word | |
| 5 | Frequency (index) | | word | |
| 6 | Power factor (effective value) | | word | |
| 7 | Power factor (index) | | word | |
| 8 | Active power (effective value) | W | word | |
| 9 | Active power (index) | | word | |
| 10 | Reactive power (effective value) | var | word | |
| 11 | Reactive power (index) | | word | |
| 12 | Active energy | Wh | dword | |
| 14 | Reactive energy | varh | dword | |
| 16 | Pt ratio (pt) | | word | |
| 17 | Ct ratio (ct) | | word | |
| 18 | Alarm and I/O | | word | |