Acrel ADW300, DTSD1352, PZ300 MODBUS registers: read online

Connect Acrel to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Acrel logger and poll.

Do you not know the meter address? Scan the device address online

Acrel (ADW300) - MODBUS Values

Registers in the map: 130 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
12 word 
20Voltage of A phase word 
21Voltage of B phase word 
22Voltage of C phase word 
23Voltage between A-B word 
24Voltage between B-C word 
25Voltage between C-A word 
26Electricity of A phaseAword×0.01
27Electricity of B phaseAword×0.01
28Electricity of C phaseAword×0.01
29Vector sum of 3-phase currentAword×0.01
30Active power of A phasekWdword×0.001
32Active power of B phasekWdword×0.001
34Active power of C phasekWdword×0.001
36Total active powerkWdword×0.001
38Reactive power of A phasekvardword×0.001
40Reactive power of B phasekvardword×0.001
42Reactive power of C phasekvardword×0.001
44Total reactive powerkVAdword×0.001
46Apparent power of A phasekVAdword×0.001
48Apparent power of B phasekVAdword×0.001
50Apparent power of C phasekVAdword×0.001
52Total apparent powerkVAdword×0.001
54Power factor of A phase word×0.001
55Power factor of B phase word×0.001
56Power factor of C phase word×0.001
57Total power factor word×0.001
58State of DI word 
59Frequency of power word×0.01
60Total energy consumptionkWhdword×0.01
62Forward active energy consumptionkWhdword×0.01
64Reversing active energy consumptionkWhdword×0.01
66Forward reactive energy consumptionkvarhdword×0.01
68Reversing reactive energy consumptionkvarhdword×0.01
70Total energy consumption on phasekWhdword×0.01
72Forward active energy consumption on phasekWhdword×0.01
74Reversing active energy consumption on phasekWhdword×0.01
76Consumption on A phasekvarhdword×0.01
78Reversing reactive energy consumption on phasekvarhdword×0.01
80Total energy consumption on B phasekWhdword×0.01
82Forward active energy consumption on B phasekWhdword×0.01
84Reversing active energy consumption on B phasekWhdword×0.01
86Forward reactive energy consumption on B phasekvarhdword×0.01
88Reversing reactive energy consumption on B phasekvarhdword×0.01
90Total energy consumption on phasekWhdword×0.01
92Forward active energy consumption on C phasekWhdword×0.01
94Reversing active energy consumption on C phasekWhdword×0.01
96Forward reactive energy consumption on C phasekvarhdword×0.01
98Reversing reactive energy consumption on C phasekvarhdword×0.01
100Maximum forward active demand in current monthkWdword×0.001

This is not the complete map: 50 of 130 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Acrel (DTSD1352) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS-485 (two wires, shielded twisted pair)
Parity
none, even
Communication settings register
003FH
Address register
003FH high byte, range 1-247
Baud rate register
003FH low byte, baud rate code
Function codes
03H read, 10H write
Bus length
up to 1200 m

Registers in the map: 87 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
0Current total active energykWhdwordformula
2Current spike total active energykWhdwordformula
4Current peak total active energykWhdwordformula
6Current flat total active energykWhdwordformula
8Current valley total active energykWhdwordformula
10Current forward active total energykWhdwordformula
12Current forward active spike energykWhdwordformula
14Current forward active energy peakkWhdwordformula
16Current forward active flat energykWhdwordformula
18Current forward active valley energykWhdwordformula
20Current reversing active total energykWhdwordformula
22Current reversing active spike energy dword 
24Current reversing active energy peak dword 
26Current reversing active flat energy dword 
28Current reversing active valley energy dword 
30Current total reactive energy dword 
32Current total reactive spike energy dword 
34Current total reactive peak energy dword 
36Current total reactive flat energy dword 
38Current total reactive energy valley dword 
40Current forward reactive total energy dword 
42Current forward reactive spike energy dword 
44Current forward reactive energy peak dword 
46Current forward reactive flat energy dword 
48Current forward reactive valley energy dword 
50Current reversing reactive total energy dword 
52Current reversing reactive spike energy dword 
54Current reversing reactive energy peak dword 
56Current reversing reactive flat energy dword 
58Current reversing reactive valley energy dword 
60Time: second, minute word 
61Time: hour; day word 
62Time: month, year word 
64Pulse constant word 
97Voltage of A phaseVwordformula
98Voltage of B phaseVwordformula
99Voltage of C phaseVwordformula
100Current of phase AAwordformula
101Current of phase BAwordformula
102Current of phase CAwordformula
119FrequencyHzwordformula
120Voltage between A-BVwordformula
121Voltage between C-BVwordformula
122Voltage between A-CVwordformula
123Forward active maximum demand word 
124Time of occurrence: minute, hour word 
125Time of occurrence: day, month word 
126Reversing active maximum demand word 
127Time of occurrence: minute, hour word 
128Time of occurrence: day, month word 

This is not the complete map: 50 of 87 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Acrel (PZ300) - Measurement Data

Registers in the map: 35. function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
01 voltage effective valueVdwordformula
22 voltage effective value dwordformula
43 voltage effective value dwordformula
6Average voltage effective value dwordformula
81 current effective valueAdwordformula
102 current effective value dwordformula
123 current effective value dwordformula
14Total current effective value dwordformula
161 active power effective valueWdwordformula
182 active power effective value dwordformula
203 active power effective value dwordformula
221 reactive power effective valuevardwordformula
242 reactive power effective value dwordformula
263 reactive power effective value dwordformula
281 apparent power effective valueVAdwordformula
302 apparent power effective value dwordformula
323 apparent power effective value dwordformula
341 power factor effective value dwordformula
362 power factor effective value dwordformula
383 power factor effective value dwordformula
40Total active power effective valueWdwordformula
42Total reactive power effective valuevardwordformula
44Total apparent power effective valueVAdwordformula
46Total power factor effective value dwordformula
48Frequency effective valueHzdwordformula
50Pt ratio word 
51Ct ratio word 
521 active electric energy dword 
542 active electric energy dword 
563 active electric energy dword 
58Total active electric energy dword 
601 reactive electric energyWhdword 
622 reactive electric energy dword 
643 reactive electric energy dword 
66Total reactive electric energy dword 

Acrel (PZ72-E3,P80-E3,PZ96-E3) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS-485
Default baud rate
9600 bps
Data bits
8
Stop bits
1
Parity
none
Default password
0001
Checksum
CRC16
Device address range
1-247
Baud rate register
0001H low byte, 0 = 38400, 1 = 19200, 2 = 9600, 3 = 4800 bps
Additional selectable baud rates
1200, 2400, 4800, 19200 bps
Function codes
03H read, 04H read, 10H write

Registers in the map: 39. function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
3Pt ratio word 
4Ct ratio word 
35Decimal point U wordformula
36Decimal point PQ wordformula
34The statement of relays word 
37Phase voltage AVwordformula
38Phase voltage BVwordformula
39Phase voltage CVwordformula
40Line voltage ABVwordformula
41Line voltage BCVwordformula
42Line voltage ACVwordformula
43IaAwordformula
44IbAwordformula
45IcAwordformula
46Pa wordformula
47Pb wordformula
48Pc wordformula
49P total wordformula
50Qa wordformula
51Qb wordformula
52Qc wordformula
53Q total wordformula
54Cosa word×0.001
55Cosb word×0.001
56Cosc word×0.001
57Cos total word×0.001
58Sa word 
59Sb word 
60Sc word 
61S total word 
62Frequency F word×0.01
63Measued imkWhdwordformula
65Measued exportkWhdwordformula
67Measued importkvarhdwordformula
69Measued exportkvarhdwordformula
71Real importkWhsingle 
73Real exportkWhsingle 
75Real importkvarhsingle 
77Real exportkvarhsingle 

Acrel (PZ80) - MODBUS Maps

Registers in the map: 17. function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage (effective value)Vword 
1Voltage (index) word 
2Current (effective value)Aword 
3Current (index) word 
4Frequency (effective value)Hzword 
5Frequency (index) word 
6Power factor (effective value) word 
7Power factor (index) word 
8Active power (effective value)Wword 
9Active power (index) word 
10Reactive power (effective value)varword 
11Reactive power (index) word 
12Active energyWhdword 
14Reactive energyvarhdword 
16Pt ratio (pt) word 
17Ct ratio (ct) word 
18Alarm and I/O word 