Carlo Gavazzi EM33, WM14, CPT A, WM3-96 MODBUS registers: read online

Connect Carlo Gavazzi to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Carlo Gavazzi modbus logging and log.

Do you not know the meter address? Scan the device address online

Carlo Gavazzi (EM33) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 10. function 4 (input registers). byte order big-endian. data types: integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
770Version code word 
0V L1 N integer×0.1
2V L2 N integer×0.1
4V L3 N integer×0.1
6A L1 integer×0.001
8A L2 integer×0.001
10A L3 integer×0.001
12W integer×0.1
14Kwh(+) totkWinteger×0.1
16Phase sequence smallint 

Carlo Gavazzi (WM14, CPT A) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)
Data format
IEEE 754 floats

Registers in the map: 69 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single.

MODBUS offsetDescriptionUnitsData typeScale
0V L1 N single 
2V L2 N single 
4V L3 N single 
6V L1 L2 single 
8V L2 L3 single 
10V L3 L1 single 
12A L1 single 
14A L2 single 
16A L3 single 
18A N single 
20W L1 single 
22W L2 single 
24W L3 single 
26Va L1 single 
28Va L2 single 
30Va L3 single 
32Var L1 single 
34Var L2 single 
36Var L3 single 
38Phase sequence single 
40Pf L1 single 
42Pf L2 single 
44Pf L3 single 
46V L N single 
48V L L single 
50W single 
52Va single 
54Var single 
56Pf single 
58Hz single 
60Asymmetry L N single 
62Asymmetry L L single 
96A max single 
98A max dmd single 
100A L1 max single 
102A L2 max single 
104A L3 max single 
106W L1 max single 
108W L2 max single 
110W L3 max single 
112W max dmd single 
114Va max dmd single 
134V L1 max single 
136V L2 max single 
138V L3 max single 
116Pf L1 min single 
118Pf L2 min single 
120Pf L3 min single 
122A L1 min single 
124A L2 min single 

This is not the complete map: 50 of 69 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi (WM3-96) - MODBUS Registers Map

Connection and addressing notes

Byte order 0000h-00E7h and 2000h-3FFFh
MSB, LSB
Byte order 00E8h-1FFFh
LSB, MSB
Byte order 4000h-5FFFh (Real Time Clock area)
LSB only
Integer size
4 bytes
Short size
2 bytes
Word size
2 bytes

Registers in the map: 158 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0V L1-NVdword 
4A L1Adword 
8W L1 dword 
12V L2-NVdword 
16A L2Adword 
20W L2 dword 
24V L3-NVdword 
28A L3Adword 
32W L3 dword 
36V L1Vdword 
40V L2Vdword 
44V L3Vdword 
48VA L1 dword 
52Var L1 dword 
56PF L1 dword 
60VA L2 dword 
64Var L2 dword 
68PF L2 dword 
72VA L3 dword 
76Var L3 dword 
80PF L3 dword 
84VVdword 
88A NAdword 
92W dword 
96VA dword 
100Var dword 
104PF dword 
108THD V1 dword 
112THDe V1 dword 
116THDo V1 dword 
120THD V2 dword 
124THDe V2 dword 
128THDo V2 dword 
132THD V3 dword 
136THDe V3 dword 
140THDo V3 dword 
144THD A1 dword 
148THDe A1 dword 
152THDo A1 dword 
156THD A2 dword 
160THDe A2 dword 
164THDo A2 dword 
168THD A3 dword 
172THDe A3 dword 
176THDo A3 dword 
180A dmdAdword 
184VA dmd dword 
188TPF avg dword 
192W dmd dword 
196HzHzdword 

This is not the complete map: 50 of 158 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi (WM30, WM40) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 378 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: int64, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0Base firmware version word 
1Communication module firmware version (only in case mceth or mcbacip modules) word 
3Advanced six channel digital inputs + four channel outputs module firmware version (only in case mfi6r4 or mfi6o6) word 
2Analogue output module firmware version (position 1 only in case moa2 or mov2 modules) word 
4Process module (only in case matp or matpn) word 
5Analogue output module firmware version (position 2 only in case moa2 or mov2 modules) word 
11Carlo gavazzi controls identification code word 
32Letter 1 (from sx) letter 2 (from sx) word 
33Letter 3 (from sx) letter 4 (from sx) word 
34Letter 5 (from sx) letter 6 (from sx) word 
35Letter 7 (from sx) letter 8 (from sx) word 
36Letter 9 (from sx) letter 10 (from sx) word 
37Letter 11 (from sx) letter 12 (from sx) word 
38Letter 13 (from sx) word 
80V L1 N single 
82V L2 N single 
84V L3 N single 
86V L N single 
88V L1 L2 single 
90V L2 L3 single 
92V L3 L1 single 
94V L L single 
96A L1 single 
98A L2 single 
100A L3 single 
102A N single 
104W L1 single 
106W L2 single 
108W L3 single 
110W single 
112Va L1 single 
114Va L2 single 
116Va L3 single 
118Va single 
120Var L1 single 
122Var L2 single 
124Var L3 single 
126Var single 
128Pf L1 single 
130Pf L2 single 
132Pf L3 single 
134Pf single 
136Hz single 
138Asymmetry L N single 
140Asymmetry L L single 
142Phase sequence single 
144K factor L1 single 
146K factor L2 single 
148K factor L3 single 
150Temperature single 

This is not the complete map: 50 of 378 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.