Circutor CVM-NRG CVM, NRG MODBUS registers: read online

Connect Circutor CVM-NRG to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Circutor CVM-NRG modbus logging and log.

Do you not know the meter address? Scan the device address online

Circutor CVM-NRG - MODBUS Registers Map

Registers in the map: 44. function 3 (holding registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage phase, v l1Vdword 
2Current, a l1Adword×0.001
4Active power, kw l1Wdword 
6Reactive power, kvar l1Wdword 
8Power factor, pf l1 dword 
10Voltage phase, v l2Vdword 
12Current, a l2Adword×0.001
14Active power, kw l2Wdword 
16Reactive power, kvar l2Wdword 
18Power factor, pf l2 dword 
20Voltage phase, v l3Vdword 
22Current, a l3Adword×0.001
24Active power, kw l3Wdword 
26Reactive power, kvar l3Wdword 
28Power factor, pf l3 dword 
30Active power iii, kw iiiWdword 
32Inductive power iii, kvarl iiiWdword 
34Capacitive power iii, kvarc iiiWdword 
36Cos fi iii, cos fi iii dword 
38Power factor iii, pf iii dword 
40Frequency, hzHzdword 
42Voltage line l1-l2, v12Vdword 
44Voltage line l2-l3, v23Vdword 
46Voltage line l3-l1, v31Vdword 
48% thd v l1, %thd vl1%dword 
50% thd v l2, %thd vl2%dword 
52% thd v l3, %thd vl3%dword 
54% thd a l1, %thd al1%dword 
56% thd a l2, %thd al2%dword 
58% thd a l3, %thd al3%dword 
66Apparent power iii, kvaiiiWdword 
68Maximum demand, md (pd)w/VA/mAdword 
70Three phase current (average, a_avgAdword×0.001
72Neutral current, inAdword×0.001
82Maximum demand a2, md (pd)Adword×0.001
84Maximum demand a3, md (pd)Adword×0.001
60Active energy, kw-h iiiWhdword 
62Inductive reactive energy, kvarl-h iiiWhdword 
64React. energy capacitive, kvarc-h iiiWhdword 
86Apparent energy, kva-h iiiWhdword 
88Active energy generated, kw-h iii (-)Whdword 
90Inductive energy generated, kvarl-h iii (-)Whdword 
92Capacit. energy generated, kvarc-h iii (-)Whdword 
94Apparent energy generated, kva-h iii (-)Whdword 