Circutor CVM-MINI CVM-MINI MODBUS registers: read online

Connect Circutor CVM-MINI to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Circutor CVM-MINI modbus logging and log.

Do you not know the meter address? Scan the device address online

Circutor CVM-MINI - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Data bits
8
Error check
CRC
Character format
each 8-bit byte carries two hex characters
Function codes
01 read relay status, 03 read words, 04 read words, 05 write relay
Parameter size
32-bit value read as two 16-bit words

Registers in the map: 48. function 3 (holding registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage phase, v l1Vdword×0.1
2Current, a l1Adword×0.001
4Active power, kw l1Wdword 
6Reactive power, kvar l1Wdword 
74Apparent power, kv a l1 dword 
8Power factor, pf l1 dword×0.01
10Voltage phase, v l2Vdword×0.1
12Current, a l2Adword×0.001
14Active power, kw l2Wdword 
16Reactive power, kvar l2Wdword 
76Apparent power, kv a l2Wdword 
18Power factor, pf l2 dword×0.01
20Voltage phase, v l3Vdword×0.1
22Current, a l3Adword×0.001
24Active power, kw l3Wdword 
26Reactive power, kvar l3Wdword 
78Apparent power, kv a l3Wdword 
28Power factor, pf l3 dword×0.01
80Temperature, cdeg Cdword×0.1
30Active power iii, kw iiiWdword 
32Inductive power iii, kvarl iiiWdword 
34Capacitive power iii, kvarc iiiWdword 
36Cos iii, cos iii dword×0.01
38Power factor iii, pf iii dword×0.01
40Frequency, hzHzdword×0.1
42Voltage line l1-l2, v12Vdword×0.1
44Voltage line l2-l3, v23Vdword×0.1
46Voltage line l3-l1, v31Vdword×0.1
48% thd v l1, %thd vl1%dword×0.1
50% thd v l2, %thd vl2%dword×0.1
52% thd v l3, %thd vl3%dword×0.1
54% thd a l1, %thd al1%dword×0.1
56% thd a l2, %thd al2%dword×0.1
58% thd a l3, %thd al3%dword×0.1
66Apparent power iii, kvaiiiWdword 
68Maximum demand, md (pd)w/VA/mAdword 
70Three-phase current (average, a_avgAdword×0.001
72Neutral current, inAdword×0.001
82Maximum demand a2, md (pd)Adword×0.001
84Maximum demand a3, md (pd)Adword×0.001
60Active energy, kw h iiiWdword 
62Inductive reactive energy, kvarl h iiiWdword 
64Capacitive reactive energy, kvarc h iiiWdword 
86Apparent energy, kva h iiiWdword 
88Active energy generated, kw h iii (-)Wdword 
90Inductive energy generated, kvarl h iii (-)Wdword 
92Capacitive energy generated, kvarc h iii (-)Wdword 
94Apparent energy generated, kva h iii (-)Wdword 