Epsolar LS-B Series MODBUS registers: read online

Connect Epsolar to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Epsolar data logging and capture.

Do you not know the meter address? Scan the device address online

Epsolar (LS-B Series) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Default baud rate
115200 bps
Data bits
8
Stop bits
1
Parity
none
Default device address
1
Flow control
no handshaking
Register addressing
hexadecimal (0x3000 = 12288)
Controller ID setting
PC software (Solar Station Monitor) or MT50 remote meter

Registers in the map: 40. function 4 (input registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
12288Charging equipment rated input voltage word×0.01
12289Charging equipment rated input currentAword×0.01
12290Charging equipment rated input power dword×0.01
12292Charging equipment rated output voltageVword×0.01
12293Charging equipment rated output currentAword×0.01
12294Charging equipment rated output power word×0.01
12295Charging equipment rated output power word×0.01
12296Charging mode word 
12302Rated output current of loadAword×0.01
12544Charging equipment input voltageVword×0.01
12545Charging equipment input currentAword×0.01
12546Charging equipment input power dword×0.01
12548Charging equipment output voltage word×0.01
12549Charging equipment output currentAword×0.01
12550Charging equipment output power dword×0.01
12556Disharging equipment output voltageVword×0.01
12557Disharging equipment output currentAword×0.01
12558Disharging equipment output power word×0.01
12559Disharging equipment output power word×0.01
12560Battery temperaturedeg Cword×0.01
12561Temperature inside equipmentdeg Cword×0.01
12562Power components temperaturedeg Cword×0.01
12570Battery soc word×0.01
12571Remote battery temperaturedeg Cword×0.01
12573Battery's real rated power word×0.01
13056Maximum input volt (pv) today word×0.01
13057Minimum input volt (pv) todayVword×0.01
13058Maximum battery volt todayVword×0.01
13059Minimum battery volt todayVword×0.01
13060Consumed energy todaykWhdword×0.01
13062Consumed energy this month dword×0.01
13064Consumed energy this year dword×0.01
13066Total consumed energy dword×0.01
13068Generated energy today dword×0.01
13070Generated energy this month dword×0.01
13072Generated energy this year dword×0.01
13074Total generated energykWhdword×0.01
13076Carbon dioxide reductionTondword×0.01
13083Battery currentAdword×0.01
13085Battery tempdeg Cword×0.01