FF - MODBUS Registers Map - Data Logging
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable FF data logging and log.
Do you not know the meter address? Scan the device address online
FF (LE-01) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
256
Voltage
V
integer
258
Current
A
integer
260
Active power
W
integer
262
Apparent power
VA
integer
264
Reactive power
Var
integer
266
Frequency
Hz
smallint
267
Power factor
smallint
270
Total consumed (imported) active energy
kWh
integer
280
Total returned (exported) active energy
kWh
integer
290
Total active energy
kWh
integer
300
Total consumed (imported) reactive en- ergy
kvarh
integer
310
Total returned (exported) reactive energy
kvarh
integer
320
Total reactive energy
kvarh
integer
330
Total reactive energy in the first quadrant
kvarh
integer
340
Total reactive energy in the second quad- rant
kvarh
integer
350
Total reactive energy in the third quad- rant
kvarh
integer
360
Total reactive energy in the fourth quad- rant
kvarh
integer
370
Resettable auxiliary active energy meter
kWh
integer
372
Resettable auxiliary reactive energy meter
kvarh
integer
374
Consumed (imported) active power de- mand
W
integer
376
Maximum consumed (imported) active power demand
W
integer
378
Returned (exported) active power demand
W
integer
380
Maximum returned (exported) active power demand
W
integer
384
Consumed (imported) reactive power de- mand
var
integer
386
Maximum consumed (imported) reactive power demand
var
integer
388
Returned (exported) reactive power de- mand
var
integer
390
Maximum returned (exported) reactive power demand
var
integer
FF (LE-03MQ) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
0
L1 (L-n) phase voltage
V
single
2
L2 (L-n) phase voltage
V
single
4
L3 (L-n) phase voltage
V
single
6
L1 current strength
A
single
8
L2 current strength
A
single
10
L3 current strength
A
single
12
L1 active power
W
single
14
L2 active power
W
single
16
L3 active power
W
single
18
L1 apparent power
VA
single
20
L2 apparent power
VA
single
22
L3 apparent power
VA
single
24
L1 reactive power
Var
single
26
L2 reactive power
Var
single
28
L3 reactive power
Var
single
30
L1 power factor
single
32
L2 power factor
single
34
L3 power factor
single
36
L1 phase angle
Degrees
single
38
L2 phase angle
Degrees
single
40
L3 phase angle
Degrees
single
42
Average phase voltage among phase and neutral wire
V
single
46
Average line current
A
single
48
Sum of phase currents
A
single
52
Total system power
W
single
56
Total system volt amps
VA
single
60
Total system var
Var
single
62
Total system power factor (*1)
single
66
Total system phase angle
Degrees
single
70
Frequency of supply voltages
Hz
single
72
Imported active energy
kWh/ MWh
single
74
Exported active energy
kWH/ MWh
single
76
Imported reactive energy
kVarh/ MVarh
single
78
Exported reactive energy
kVarh/ MVarh
single
80
Apparent power
kVah/ MVAh
single
82
Ah since last reset
Ah/kAh
single
84
Total system power demand (*2)
W
single
86
Maximum total system power demand (*2)
W
single
100
Total system VA demand (*2)
VA
single
102
Maximum total system VA demand
VA
single
104
Neutral current demand
A
single
106
Maximum neutral current demand
A
single
200
L1-L2 interphase voltage
W
single
202
L2-L3 interphase voltage
W
single
204
L3-L1 interphase voltage
W
single
206
Average interphase voltage
W
single
224
Neutral current
A
single
234
Phase 1 L/N volts THD
%
single
236
Phase 2 L/N volts THD
%
single
238
Phase 3 L/N volts THD
%
single
There are more MODBUS items for this device. Please download the program to discover all registers.
Related MODBUS registers maps
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
MODBUS COM Port Connection
Feature Not Supported
Your current browser does not support the Web Serial API required to access local COM ports. Please use a Chromium-based browser like Google Chrome, Microsoft Edge, or Opera.