Kohler - MODBUS Registers Map - Data Logging

The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Kohler data logging and log.

Do you not know the meter address? Scan the device address online

Kohler (MPAC 1000) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
1
Sourcea line neutral L1 l0
Volts AC
word
2
Sourcea line neutral L2 l0
Volts AC
word
3
Sourcea line neutral L3 l0
Volts AC
word
4
Sourceb line neutral L1 l0
Volts AC
word
5
Sourceb line neutral L2 l0
Volts AC
word
6
Sourceb line neutral L3 l0
Volts AC
word
7
Sourcea line voltage L1 L2
Volts AC
word
8
Sourcea line voltage L2 L3
Volts AC
word
9
Sourcea line voltage L3 L1
Volts AC
word
10
Sourceb line voltage L1 L2
Volts AC
word
11
Sourceb line voltage L2 L3
Volts AC
word
12
Sourceb line voltage L3 L1
Volts AC
word
13
Sourcea frequency
Hz
word
14
Sourceb frequency
Hz
word
23
Sourcea nominal voltage
Volts AC
word
24
Sourceb nominal voltage
Volts AC
word
25
Sourcea nominal frequency
Hz
word
26
Sourceb nominal frequency
Hz
word
27
Sourcea number of phases
1 or 3
word
28
Sourceb number of phases
1 or 3
word
29
Rated amperage
0-4000
word
31
Sourcea engine start time delay (id 0x0001)
0-6 sec
word
32
Sourceb engine start time delay (id 0x0002)
0-6 sec
word
33
Sourcea ext engine start time delay (id 0x0003)
0-5999 sec
word
34
Sourceb ext engine start time delay (id 0x0004)
0-5999 sec
word
35
Sourcea engine cooldown time delay (id 0x0005)
0-5999 sec
word
36
Sourceb engine cooldown time delay (id 0x0006)
0-5999 sec
word
37
Preferred to standby time delay (id 0x0007)
0-5999 sec
word
38
Standby to preferred time delay (id 0x0008)
0-5999 sec
word
39
Off to preferred time delay (id 0x0009)
0-5999.9 sec
word
40
Off to standby time delay (id 0x000a)
0-5999.9 sec
word
41
Acquire standby source (id 0x000b)
1-5999 sec
word
42
Inphase monitor synch (id 0x000c)
1-5999 sec
word
44
Sourcea over volt dropout trip point
105 - 135) % of rated source voltage
word
45
Sourcea over volt pickup trip point
95 - 100)% of over voltage dropout point
word
46
Sourcea under volt pickup trip point
85 - 100) % of rated source voltage
word
47
Sourcea under volt dropout trip point
75 - 98) % of overvoltage pickup point
word
48
Sourcea voltage debounce time
Sec
word
49
Sourceb over volt dropout trip point
105 - 135) % of rated source voltage
word
50
Sourceb over volt pickup trip point
95 - 100)% of over voltage dropout point
word
51
Sourceb under volt pickup trip point
85 - 100) % of rated source voltage
word
52
Sourceb under volt dropout trip point
75 - 98) % of overvoltage pickup point
word
53
Sourceb voltage debounce time
Sec
word
54
Sourcea over freq dropout trip point
101 -105) % of overfreq pickup point
word
55
Sourcea over freq pickup trip point
105 - 120) % of rated source freq
word
56
Sourcea under freq dropout trip point
95 - 99) % of underfreq pickup point
word
57
Sourcea under freq pickup trip point
80 - 95)% of rated system frequency
word
58
Sourcea freq dropout time
Sec
word
59
Sourceb over freq dropout trip point
101 -105) % of overfreq pickup point
word
60
Sourceb over freq pickup trip point
105 - 120) % of rated source freq
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Kohler (MPAC 1500) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
1
Source N line neutral l1l0
Volts AC
word
2
Source N line neutral L2 l0
Volts AC
word
3
Source N line neutral l3l0
Volts AC
word
4
Source E line neutral L1 l0
Volts AC
word
5
Source E lineneutral l2l0
Volts AC
word
6
Source E line neutral L3 l0
Volts AC
word
7
Source N line voltage L1 L2
Volts AC
word
8
Source N line voltage L2 L3
Volts AC
word
9
Source N line voltage L3 L1
Volts AC
word
10
Source E line voltage L1 L2
Volts AC
word
11
Source E line voltage l2l3
Volts AC
word
12
Source E line voltage L3 L1
Volts AC
word
13
Source N frequency
Hz
word
14
Source E frequency
Hz
word
15
Current L1
Amps
word
16
Current L2
Amps
word
17
Current L3
Amps
word
18
Closed transition in phase degree delta
Degrees
word
38
Closed programmed transition override mode
 
word
39
Password for writing register 40042
0-32768
word
40
Synchronous voltage phase angle
0-10 degrees
word
41
Synchronous voltage differential
0%-5%
word
42
Synchronous frequency differential
0.0Hz.-0.3Hz.
word
43
Service entrance type
 
word
44
Phase rotation actual
 
word
45
Phase rotation expected
 
word
46
Nominal normal voltage
Volts AC
word
47
Nominal emergency voltage
Volts AC
word
48
Nominal normal frequency
Hz
word
49
Nominal emergency frequency
Hz
word
50
Normal number of phases
1 or 3
word
51
Emergency number of phases
1 or 3
word
52
Rated amperage
04000
word
57
Password for writing register 40057
0 32768
word
58
Normal engine start time delay
0-10 sec
word
59
Emergency engine start time delay
010 sec
word
60
Normal ext. Engine start time delay
0-3600 sec
word
61
Emergency ext. Engine start time delay
03600 sec
word
62
Normal engine cooldown
0-3600 sec
word
63
Emergency engine cooldown
03600 sec
word
64
Standby to preferred
0-3600 sec
word
65
Preferred to standby
03600 sec
word
66
Off (preferred to standby prog. Transition)
0-3600 sec
word
67
Off (standby to preferred prog. Transition)
03600 sec
word
68
Fail to acquire preferred
1 -3600 sec
word
69
Fail to acquire standby
13600 sec
word
70
Fail to synchronize
1 -3600 sec
word
71
Fail to synch. Enable
0 = disabled; 1 = enabled
word
74
Active time delay
 
word
75
Active time delay remaining
Seconds
word
There are more MODBUS items for this device. Please download the program to discover all registers.

Kohler (Power Monitor) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
1
System time
 
word
2
Day of week
 
word
3
Month
112
word
4
Day
131
word
5
Year
 
word
6
Week of month
 
word
7
Voltage l1l2
volts
word
8
Voltage l2l3
volts
word
9
Voltage l3l1
volts
word
10
Frequency
Hz
word
11
Voltage l1l0
volts
word
12
Voltage l2l0
volts
word
13
Voltage l3l0
volts
word
14
Alert code
Alert Code
word
15
Analog input #1 percentage
%
word
16
Analog input #2 percentage
%
word
18
Power supply voltage
VDC
word
19
L1 current
amps
word
20
L2 current
amps
word
21
L3 current
amps
word
22
Power factor
100
word
23
Total real power
kW
word
24
Total imaginary power
kVAR
word
39
Aux 1 delay time
sec.
word
40
Aux 2 delay time
sec.
word
41
Aux 3 delay time
sec.
word
42
Aux 4 delay time
sec.
word
43
Aux S delay time
sec.
word
44
Aux 6 delay time
sec.
word
45
System voltage
volts, 10514600
word
46
System frequency
Hz, 4862
word
47
Ats rating
A, 03000
word
61
Shutdown #1 code
code
word
62
Shutdown #1 month
1-12
word
63
Shutdown #1 day
1-31
word
64
Shutdown #1 year
 
word
65
Shutdown #2 code
code
word
66
Shutdown #2 month
1-12
word
67
Shutdown #2 day
1-31
word
68
Shutdown #2 year
 
word
69
Shutdown #3 code
code
word
70
Shutdown #3 month
1-12
word
71
Shutdown #3 day
1-31
word
72
Shutdown #3 year
 
word
73
Shutdown #4 code
code
word
74
Shutdown #4 month
1-12
word
75
Shutdown #4 day
1-31
word
76
Shutdown #4 year
 
word
299
Timed run time
minutes
word