Krohne (IFC050) - MODBUS Measurements
Connection and addressing notes
- Protocol
- Modbus
- Register type
- input registers only
- Function codes
- 04 read input
- Address mapping 1
- protocol 30000-38998 to offsets 0-8998
- Address mapping 2
- protocol 20000-20998 to offsets 9000-9998
- Float values
- occupy 2 registers
Registers in the map: 8. function 4 (input registers). byte order big-endian. data types: double, dword, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Flow speed | m/s | single | |
| 2 | Volume flow | m3 /s | single | |
| 4 | Mass flow | kg/s | single | |
| 6 | Operating time | s | single | |
| 8 | Counter 1 | m3 | double | |
| 12 | Counter 2 | m3 | double | |
| 16 | Long status sensor | | dword | |
| 18 | Long status device | | dword | |