Northern Design - MODBUS Registers Map - Read & Log
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Northern Design data logging and log.
Northern Design PM390 - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
5376
kW 3-Ph
kW
single
5378
kVA 3-Ph
kVA
single
5380
Kvar 3-Ph
kvar
single
5382
PF 3-Ph
single
5384
Frequency
single
5386
Phase 1 volts
Volts
single
5388
Phase 1 amps
Amps
single
5390
Phase 1 kW
kW
single
5392
Phase 2 volts
Volts
single
5394
Phase 2 amps
Amps
single
5396
Phase 2 kW
kW
single
5398
Phase 3 volts
Volts
single
5400
Phase 3 amps
Amps
single
5402
Phase 3 kW
kW
single
5404
Phase 1 PF
single
5406
Phase 2 PF
single
5408
Phase 3 PF
single
5410
Ph1-Ph2 volts
Volts
single
5412
Ph2-Ph3 volts
Volts
single
5414
Ph3-Ph1 volts
Volts
single
5416
Phase 1 kVA
kVA
single
5418
Phase 2 kVA
kVA
single
5420
Phase 3 kVA
kVA
single
5422
Phase 1 kvar
kvar
single
5424
Phase 2 kvar
kvar
single
5426
Phase 3 kvar
kvar
single
5632
Decimal point
dword
5634
3-Ph wh
Wh
dword
5636
3-Ph vah
Vah
dword
5638
3-Ph varh (Ind)
varh
dword
5640
3-Ph varh (Cap)
varh
dword
5642
Export wh
Wh
dword
5644
Export vah
Vah
dword
5646
Accum VA MD
dword
5648
Peak VA MD
dword
5650
Accum W MD
W
dword
5652
Peak W MD
W
dword
Related MODBUS registers maps
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
MODBUS COM Port Connection
Feature Not Supported
Your current browser does not support the Web Serial API required to access local COM ports. Please use a Chromium-based browser like Google Chrome, Microsoft Edge, or Opera.