Obvius A90DC-12 MODBUS registers: read online

Connect Obvius to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Obvius logging and read.

Do you not know the meter address? Scan the device address online

Obvius (A90DC-12) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Function codes
0x11 report slave id, 0x03 read holding registers, 0x06 preset single register
Register addressing
numbered from 40001, offset 0 = 40001
32-bit values
MSW first
Modbus address register
41010, range 1 to 247
Access
read only unless otherwise noted

Registers in the map: 34. function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
1003Firmware version major word 
1004Firmware version minor word 
1010Hardware version word 
8Pcb temperaturedeg Fsmallint×0.01
9Input power supplyVword×0.01
10Channel 1 current, instantaneousAsmallint×0.01
11Channel 1 current, long averageAsmallint×0.01
12Channel 2 current, instantaneousAsmallint×0.01
13Channel 2 current, long averageAsmallint×0.01
14Channel 3 current, instantaneousAsmallint×0.01
15Channel 3 current, long averageAsmallint×0.01
16Channel 4 current, instantaneous amps 100Asmallint 
17Channel 4 current, long averageAsmallint×0.01
18Channel 5 current, instantaneousAsmallint×0.01
19Channel 5 current, long averageAsmallint×0.01
20Channel 6 current, instantaneousAsmallint×0.01
21Channel 6 current, long averageAsmallint×0.01
22Channel 7 current, instantaneous amps 100Asmallint 
23Channel 7 current, long averageAsmallint×0.01
24Channel 8 current, instantaneousAsmallint×0.01
25Channel 8 current, long averageAsmallint×0.01
26Channel 9 current, instantaneous amps 100Asmallint 
27Channel 9 current, long averageAsmallint×0.01
28Channel 10 current, instantaneousAsmallint×0.01
29Channel 10 current, long average amps 100Asmallint 
30Channel 11 current, instantaneousAsmallint×0.01
31Channel 11 current, long averageAsmallint×0.01
32Channel 12 current, instantaneousAsmallint×0.01
33Channel 12 current, long averageAsmallint×0.01
44Input 1 mode (nv/r/w) word 
45Input 1 value inst dword 
47Input l ave ave dword 
49Input l min min dword 
51Input 1 max max dword 