Rayleigh Instruments RI-F300, RI-F400, RI-F500 MODBUS registers: read online

Connect Rayleigh Instruments to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Rayleigh Instruments modbus logging and log.

Do you not know the meter address? Scan the device address online

Rayleigh Instruments (RI-F300,RI-F400) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register addressing
input registers 30000-30xxx with hex addresses
Data format
2 registers per parameter (float)

Registers in the map: 82 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single, string(32).

MODBUS offsetDescriptionUnitsData typeScale
684Serial no. string(32) 
0Voltage v1nVsingle 
2Voltage v2nVsingle 
4Voltage v3nVsingle 
6Average voltage lnVsingle 
8Voltage V12Vsingle 
10Voltage V23Vsingle 
12Voltage V31Vsingle 
14Average voltage llVsingle 
16Current I1Asingle 
18Current I2Asingle 
20Current I3Asingle 
22Average currentAsingle 
24kW1 single 
26kW2 single 
28kW3 single 
30Kva1 single 
32Kva2 single 
34Kva3 single 
36Kvar1 single 
38Kvar2 single 
40Kvar3 single 
42TotalkWsingle 
44TotalkVAsingle 
46Totalkvarsingle 
48Pf 1 single 
50Pf 2 single 
52P f3 single 
54Average pf single 
56FrequencyHzsingle 
58Total netkWhsingle 
60Total netkVAhsingle 
62Total netkvarhsingle 
64Kw max active power single 
66Kw min active power single 
68Kvar max reactive power single 
70Kvar min reactive power single 
72Kva max apparent power single 
74Max I1 demand single 
76Max I2 demand single 
78Max I3 demand single 
80Max avg demand single 
82Run hour single 
84Kwh1 (imp) single 
86Kwh2 (imp) single 
88Kwh3 (imp) single 
90Kwh1 (exp) single 
92Kwh2 (exp) single 
94Kwh3 (exp) single 
96Total kwh (imp)kWhsingle 

This is not the complete map: 50 of 82 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Rayleigh Instruments (RI-F500) - MODBUS Registers Map

Connection and addressing notes

Byte order
big endian (low byte after high byte) for 32-bit IEEE 754 float data and 16/32-bit two's complement integers

Registers in the map: 117 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
6V1 single 
8V2Vsingle 
10V3 single 
12V12 single 
14V23 single 
16V31 single 
18I1 single 
2012Asingle 
2213Asingle 
24InAsingle 
26P1kWsingle 
28P2kWsingle 
30P3kWsingle 
32PkWsingle 
34Q1kvarsingle 
36Q2kvarsingle 
38Q3kvarsingle 
40Qkvarsingle 
42S1kVAsingle 
44S2kVAsingle 
46S3kVAsingle 
48SkVAsingle 
50PF1 single 
52PF2 single 
54PF3 single 
56PF single 
58FHzsingle 
60Import active energykWhsingle 
62Export active energykWhsingle 
64Import reactive energykvarhsingle 
66Export reactive energykvarhsingle 
68Apparent energykVAsingle 
70Q1 reactive energy EQL+kvarhsingle 
72Q2 reactive energy EQC+kvarhsingle 
74Q3 reactive energy EQL-kvarhsingle 
76Q4 reactive energy EQC -kvarhsingle 
78Fundamenta import active energykWhsingle 
80Fundamenta export active energykWhsingle 
82Fundamenta import reactive energykvarhsingle 
84Fundamenta export reactive energykvarhsingle 
86L1 import active energykWhsingle 
88L2 import active energykWhsingle 
90L3 import active energykWhsingle 
92L1 export active energykWhsingle 
94L2 export active energykWhsingle 
96L3 export active energykWhsingle 
98L1 import reactive energykvarhsingle 
100L2 import reactive energykvarhsingle 
102L3 import reactive energykvarhsingle 
104L1 export reactive energykvarhsingle 

This is not the complete map: 50 of 117 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.