RISH RM3440, RM3440i, RM3490 MODBUS registers: read online

Connect RISH to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous RISH data logger and record.

Do you not know the meter address? Scan the device address online

RISH (RM3440) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Register addressing
3X (30001+) for measured parameters
Modbus start address
given in hex

Registers in the map: 69 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 single 
2Volts 2 single 
4Volts 3 single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W1 single 
14W2 single 
16W3 single 
18VA1 single 
20VA2 single 
22VA3 single 
24Var1 single 
26Var2 single 
28Var3 single 
30PF1 single 
32PF2 single 
34PF3 single 
36Phase angle 1 single 
38Phase angle 2 single 
40Phase angle 3 single 
42Volts ave single 
44Volts sum single 
46Current ave single 
48Current sum single 
50Watts ave single 
52Watts sum single 
54Va ave single 
56Va sum single 
58Var ave single 
60Var sum single 
62Pf ave single 
64Pf sum single 
66Phase angle ave single 
68Phase angle sum single 
70Freq single 
72Wh import single 
74Wh export single 
76Varh import single 
78Varh export single 
80Vah single 
82Ah single 
84W demand (import) single 
86W max demand (import) single 
88W demand (export) single 
90W max demand (export) single 
100Va demand single 
102Va max demand single 
104A demand single 
106A max demand single 

This is not the complete map: 50 of 69 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

RISH (RM3440i) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Register addressing
3X (30001+) for measured parameters
Data format
two consecutive 16-bit registers per parameter
Settings registers
4X
Settings access
code 03 reads a setting, code 16 writes or changes it
Response example function code
04

Registers in the map: 69 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 single 
2Volts 2 single 
4Volts 3 single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W1 single 
14W2 single 
16W3 single 
18VA1 single 
20VA2 single 
22VA3 single 
24Var1 single 
26Var2 single 
28Var3 single 
30PF1 single 
32PF2 single 
34PF3 single 
36Phase angle 1 single 
38Phase angle 2 single 
40Phase angle 3 single 
42Volts ave single 
44Volts sum single 
46Current ave single 
48Current sum single 
50Watts ave single 
52Watts sum single 
54Va ave single 
56Va sum single 
58Var ave single 
60Var sum single 
62Pf ave single 
64Pf sum single 
66Phase angle ave single 
68Phase angle sum single 
70Freq single 
72Wh import single 
74Wh export single 
76Varh import single 
78Varh export single 
80Vah single 
82Ah single 
84W demand (import) single 
86W max demand (import) single 
88W demand (export) single 
90W max demand (export) single 
100Va demand single 
102Va max demand single 
104A demand single 
106A max demand single 

This is not the complete map: 50 of 69 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

RISH (RM3490) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Register addressing
3X input register addresses (30001+)
Address notation
Modbus start address in hex

Registers in the map: 41. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Volts 1 single 
2Volts 2 single 
4Volts 3 single 
6Current 1 single 
8Current 2 single 
10Current 3 single 
12W1 single 
14W2 single 
16W3 single 
18VA1 single 
20VA2 single 
22VA3 single 
24Var1 single 
26Var2 single 
28Var3 single 
30PF1 single 
32PF2 single 
34PF3 single 
36Phase angle 1 single 
38Phase angle 2 single 
40Phase angle 3 single 
42Volts ave single 
44Volts sum single 
46Current ave single 
48Current sum single 
50Watts ave single 
52Watts sum single 
54Va ave single 
56Va sum single 
58Var ave single 
60Var sum single 
62Pf ave single 
64Pf sum single 
66Phase angle ave single 
68Phase angle sum single 
70Freq single 
72Wh single 
80Vah single 
200Vl 1 2 ( calculated ) single 
202Vl 2 3 ( calculated ) single 
204Vl 3 1 ( calculated ) single 

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection