Schneider Electric EM6400NG, PM2100, PM2200 MODBUS registers: read online

Connect Schneider Electric to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Schneider Electric data logger and record.

Do you not know the meter address? Scan the device address online

Schneider Electric (EM6400NG,PM2100,PM2200) - MODBUS Registers

Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: int64, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
2699Active energy delivered (into load)kWhsingle 
2701Active energy received (out of load)kWhsingle 
2703Active energy delivered + receivedkWhsingle 
2705Active energy delivered receivedkWhsingle 
2707Reactive energy deliveredkvarhsingle 
2709Reactive energy receivedkvarhsingle 
2711Reactive energy delivered + receivedkvarhsingle 
2713Reactive energy delivered receivedkvarhsingle 
2715Apparent energy deliveredkVAhsingle 
2717Apparent energy receivedkVAhsingle 
2719Apparent energy delivered + receivedkVAhsingle 
2721Apparent energy delivered receivedkVAhsingle 
2999Current AAsingle 
3001Current BAsingle 
3003Current CAsingle 
3005Current NAsingle 
3007Current GAsingle 
3009Current avgAsingle 
3011Current unbalance A%single 
3013Current unbalance B%single 
3015Current unbalance C%single 
3017Current unbalance worst%single 
3019Voltage A BVsingle 
3021Voltage B CVsingle 
3023Voltage C AVsingle 
3025Voltage L L avgVsingle 
3027Voltage A NVsingle 
3029Voltage B NVsingle 
3031Voltage C NVsingle 
3035Voltage L N avgVsingle 
3037Voltage unbalance A B%single 
3039Voltage unbalance B C%single 
3041Voltage unbalance C A%single 
3043Voltage unbalance L L worst%single 
3045Voltage unbalance A N%single 
3047Voltage unbalance B N%single 
3049Voltage unbalance C N%single 
3051Voltage unbalance L N worst%single 
3053Active power AkWsingle 
3055Active power BkWsingle 
3057Active power CkWsingle 
3059Active power totalkWsingle 
3061Reactive power Akvarsingle 
3063Reactive power Bkvarsingle 
3065Reactive power Ckvarsingle 
3067Reactive power totalkvarsingle 
3069Apparent power AkVAsingle 
3071Apparent power BkVAsingle 
3073Apparent power CkVAsingle 
3075Apparent power totalkVAsingle 

This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (EM6400) - MODBUS Measurements

Connection and addressing notes

Read function code
03H holding registers
Scaling
none required
Read mode
block (TURBO blocks) or individual parameters
Data format
float and long

Registers in the map: 56 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
3900Va apparent power, totalVAsingle 
3902W active power, totalWsingle 
3904Var reactive power, totalvarsingle 
3906Pf avg pfPFsingle 
3908Vll line to line avg voltageVLLsingle 
3910Vln line to neutral voltageVLNsingle 
3912A avg currentAsingle 
3914F frequency, hzFsingle 
3916VA1 apparent power, phase1VAsingle 
3918W1 active power, phase1Wsingle 
3920Var1 reactive power, phase1varsingle 
3922PF1 pf, phase1PFsingle 
3924V12 voltage phase1 to phase2Vsingle 
3926V1 voltage phase1 to neutralVsingle 
3928A1 current, phase1Asingle 
3930VA2 apparent power, phase2VAsingle 
3932W2 active power, phase2Wsingle 
3934Var2 reactive power, phase2varsingle 
3936PF2 pf, phase2PFsingle 
3938V23 voltage phase2 to phase3Vsingle 
3940V2 voltage phase2 to neutralVsingle 
3942A2 current, phase2Asingle 
3944VA3 apparent power, phase3VAsingle 
3946W3 active power, phase3Wsingle 
3948Var3 reactive power, phase3varsingle 
3950PF3 pf, phase3PFsingle 
3952V31 voltage phase3 to phase1Vsingle 
3954V3 voltage phase3 to neutralVsingle 
3956A3 current, phase3Asingle 
3958Fwdvah forward apparent energyFwdVAhsingle 
3960Fwdwh forward active energyFwdWhsingle 
3962Fwdvarh forward reactive inductive energyFwdVARhsingle 
3964Fwdvarh forward reactive capacitive energyFwdVARhsingle 
3966Revvah reverse apparent energyRevVAhsingle 
3968Revwh reverse active energyRevWhsingle 
3970Revvarh reverse reactive inductive energyRevVARhsingle 
3972Revvarh reverse reactive capacitive energyRevVARhsingle 
3974Present demandPresentsingle 
3976Rising demandRisingsingle 
3978Max mdMaxsingle 
3980Max dm occurrence timeMaxsingle 
3992On hrsOninteger 
3994Fwdrun secsFwdRuninteger 
3996Revrun secsRevRuninteger 
3998Intr number of power interruptionIntrinteger 
3860%V1 voltage thd, phase 1%V1single 
3862%V2 voltage thd, phase 2%V2single 
3864%V3 voltage thd, phase 3%V3single 
3866%A1 current thd, phase 1%A1single 
3868%A2 current thd, phase 2%A2single 

This is not the complete map: 50 of 56 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (EM7200) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Interface
RS-485 (Comm Port M/S)
Default baud rate
9600
Baud rate register
6502, 0 = 4800, 1 = 9600, 2 = 19200, 3 = 38400
Parity
even
Parity register
6503, 0 = even, 1 = odd, 2 = none
Default device address
1
Address register
6501, range 1-247
Default password
0000
Password register
1880, setup password
Protocol register
6500, default 0 = Modbus, 1 = Jbus, 2 = Modbus ASCII 8-bit, 3 = Modbus ASCII 7-bit

Registers in the map: 1788 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, single, utf8(10), utf8(40), word.

MODBUS offsetDescriptionUnitsData typeScale
50Meter model utf8(40) 
1637Present firmware version (dlf format) x.y.t word 
1642Previous firmware version (dlf format) x.y.t word 
1701Present firmware version (dlf format) x.y.t word 
1706Previous firmware version (dlf format) x.y.t word 
1716Bridge code version word 
6000Hmi model present word 
30Meter name utf8(40) 
70Manufacturer utf8(40) 
90Product id number word 
130Serial number dword 
136Hardware revision utf8(10) 
141Production history 01 word 
142Production history 02 word 
143Production history 03 word 
144Production history 04 word 
145Production history 05 word 
146Production history 06 word 
147Production history 07 word 
148Production history 08 word 
149Production history 09 word 
150Production history 10 word 
151Production history 11 word 
152Production history 12 word 
153Production history 13 word 
154Production history 14 word 
155Production history 15 word 
156Production history 16 word 
157Production history 17 word 
158Production history 18 word 
159Production history 19 word 
160Production history 20 word 
161Checksum word 
1638X major word 
1639Y minor word 
1640Z quality word 
1641T internal evolutions word 
1643X major word 
1644Y minor word 
1645Z quality word 
1646T internal evolutions word 
1702X major word 
1703Y minor word 
1704Z quality word 
1705T internal evolutions word 
1707X major word 
1708Y minor word 
1709Z quality word 
1710T internal evolutions word 
1715Checksum word 

This is not the complete map: 50 of 1788 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Schneider Electric (EMB,EME) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Value format
register pairs (e.g. 257/258) with integer and float variants

Registers in the map: 23. function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
256Energy consumption, kwh, low word integer single 
258Energy consumption, kwh, high word integer single 
260Real powerkWsingle 
262Reactive powerkvarsingle 
264Apparant powerkVAsingle 
266Total power factor single 
270Avg voltage, L n, ave of 1 single 
272Avg current, average of 1 single 
274Real power, phase A (same as real power, kw (3)) single 
276Real Power, phase B single 
278Real Power, phase C single 
280Power factor, phase A (same as total pf (6)) single 
282Power Factor, phase B single 
284Power Factor, phase C single 
286Voltage, phase A-B single 
288Voltage, phase B-C single 
290Voltage, phase A-C single 
292Voltage, phase A N (same as avg. L N (8)) single 
294Voltage, phase B-N single 
296Voltage, phase C-N single 
298Current, phase A (same as avg. current (9)) single 
300Current, phase B single 
302Current, phase C single 

Schneider Electric (iEM3000) - Measurement Data

Registers in the map: 84 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: int64, single, word.

MODBUS offsetDescriptionUnitsData typeScale
7274Digital input control mode word 
8905Digital input status (only bit 1 is used): bit word 
9673Digital output control mode status word 
3000I1: phase 1 currentAsingle 
3002I2: phase 2 currentAsingle 
3004I3: phase 3 currentAsingle 
3010CurrentavgAsingle 
3020Voltage L1 L2Vsingle 
3022Voltage L2 L3Vsingle 
3024Voltage L3 L1Vsingle 
3026Voltage ll avgVsingle 
3028Voltage L1 NVsingle 
3030Voltage L2 NVsingle 
3032Voltage L3 NVsingle 
3036Voltage ln avgVsingle 
3054Active power phase 1kWsingle 
3056Active power phase 2kWsingle 
3058Active power phase 3kWsingle 
3060Total active powerkWsingle 
3068Total reactive power (not applicable for iem3150 / iem3250 / iem3350)kvarsingle 
3076Total apparent power (not applicable for iem3150 / iem3250 / iem3350)kVAsingle 
3084Total power factor: 1 < pf single 
3110FrequencyHzsingle 
4191Multitariffs energy active rate word 
3204Total active energy importWhint64 
3208Total active energy export (not applicable for iem3150 / iem3250 / iem3350)Whint64 
3220Total reactive energy import (not applicable for iem3150 / iem3250 / iem3350)varhint64 
3224Total reactive energy export (not applicable for iem3150 / iem3250 / iem3350)varhint64 
3256Partial active energy importWhint64 
3272Partial reactive energy import (not applicable for iem3150 / iem3250 / iem3350)varhint64 
3518Active energy import phase1Whint64 
3522Active energy import phase 2Whint64 
3526Active energy import phase 3Whint64 
3558Input metering accumulation (not applicable for iem3150 / iem3250 / iem3350)Unitint64 
3701Demand method word 
3702Demand interval durationminword 
3766Active power demandkWsingle 
3770Active power peak demandkWsingle 
3782Reactive power demandkvarsingle 
3786Reactive power peak demandkvarsingle 
3798Apparent power demandkVAsingle 
3802Apparent power peak demandkVAsingle 
3814Current I1 demandAsingle 
3818Current I1 peak demandAsingle 
3830Current I2 demandAsingle 
3834Current I2 peak demandAsingle 
3846Current I3 demandAsingle 
3850Current I3 peak demandAsingle 
3878Current avg demandAsingle 
3882Current avg peak demandAsingle 

This is not the complete map: 50 of 84 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.