Socomec Countis E24, E33, E43, E34 MODBUS registers: read online

Connect Socomec to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Socomec data logger and record.

Do you not know the meter address? Scan the device address online

Socomec (Countis E24) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Register addressing
addresses listed in decimal and hex

Registers in the map: 87 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.

MODBUS offsetDescriptionUnitsData typeScale
50007Product software version word 
50018Product version (Major) word 
50019Product version (Minor) word 
50020Product version (Revision) word 
50021Product version (Build) word 
50025Software technical base version (Major) word 
50026Software technical base version (Minor) word 
50027Software technical base version (Revision) word 
50028Customization version (Major) word 
50029Customization version (Minor) word 
50000Product name string(8) 
50004Product order ID (Countis:100, protection:200, atys:300, diris:400) word 
50005Product ID word 
50030Product VLO string(8) 
50034Customization VLO string(8) 
50038Software technical base VLO string(8) 
50042Vendor name string(16) 
50050Product name string(16) 
50058Extended name string(16) 
50514Phase to phase voltage: U12 dword×0.01
50516Phase to phase voltage: U23 dword×0.01
50518Phase to phase voltage: U31 dword×0.01
50520Simple voltage: V1 dword×0.01
50522Simple voltage: V2 dword×0.01
50524Simple voltage: V3 dword×0.01
50528Current: I1 dword×0.001
50530Current: I2 dword×0.001
50532Current: I3 dword×0.001
50534Neutral current: in dword×0.001
50536Active power +/-: P integer×10
50538Reactive power +/-: Q integer×10
50540Apparent power: S dword×10
50542Power factor: -: leading et +: laggingPFinteger×0.001
50544Active power phase 1 +/-: P1 integer×10
50546Active power phase 2 +/-: P2 integer×10
50548Active power phase 3 +/-: P3 integer×10
50550Reactive power phase 1 +/-: Q1 integer×10
50552Reactive power phase 2 +/-: Q2 integer×10
50554Reactive power phase 3 +/-: Q3 integer×10
50556Apparent power phase 1: S1 dword×10
50558Apparent power phase 2: S2 dword×10
50560Apparent power phase 3: S3 dword×10
50562Power factor phase 1 -: leading and +: lagging: PF1 integer×0.001
50564Power factor phase 2 -: leading and +: lagging: PF2 integer×0.001
50566Power factor phase 3 -: leading and +: lagging: PF3 integer×0.001
50770Total positive active energy (no resetable): ea+ dword×1000
50772Total positive reactive energy (no resetable): er + dword×1000
50776Total negative active energy (no resetable): ea- dword×1000
50780Partial positive active energy: ea+ dword×1000
50782Partial positive reactive energy: er + dword×1000

This is not the complete map: 50 of 87 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Socomec (Countis E33, Countis E43) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Network settings block start
register 57344 (0xE000)
Network types
1BL, 2BL, 3BL, 3NBL, 4BL, 4NBL
Hour/date write
function 16, 6 words in one write

Registers in the map: 126 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.

MODBUS offsetDescriptionUnitsData typeScale
50007Product software version word 
50018Product version (Major) word 
50019Product version (Minor) word 
38912Communication board version (Major) word 
38913Communication board version (Minor) word 
38914Communication board version (Revision) word 
38915Communication board version (Build) word 
50000Product name string(8) 
50004Product order ID (Countis:100, protection:200, atys:300, diris:400) word 
50005Product ID word 
50030Product VLO string(8) 
50042Vendor name string(16) 
50050Product name string(16) 
50058Extended name string(16) 
38919Communication board VLO string(8) 
57346Current transformer primary word 
57355Synchronisation top for P+/- Q+/-: time in seconds ( 1mn, 5mn, 8mn, 10mn, 15mn, 20mn, 30mn, 60mn) word 
57602Year word 
50514Phase to phase voltage: U12 dword×0.01
50516Phase to phase voltage: U23 dword×0.01
50518Phase to phase voltage: U31 dword×0.01
50520Simple voltage: V1 dword×0.01
50522Simple voltage: V2 dword×0.01
50524Simple voltage: V3 dword×0.01
50526Frequency: F dword×0.01
50528Current: I1 dword×0.001
50530Current: I2 dword×0.001
50532Current: I3 dword×0.001
50534Neutral current: in dword×0.001
50536Active power +/-: P integer×10
50538Reactive power +/-: Q integer×10
50540Apparent power: S dword×10
50542Power factor: -: leading et +: laggingPFinteger×0.001
50544Active power phase 1 +/-: P1 integer×10
50546Active power phase 2 +/-: P2 integer×10
50548Active power phase 3 +/-: P3 integer×10
50550Reactive power phase 1 +/-: Q1 integer×10
50552Reactive power phase 2 +/-: Q2 integer×10
50554Reactive power phase 3 +/-: Q3 integer×10
50556Apparent power phase 1: S1 dword×10
50558Apparent power phase 2: S2 dword×10
50560Apparent power phase 3: S3 dword×10
50562Power factor phase 1 -: leading and +: lagging: PF1 integer×0.001
50564Power factor phase 2 -: leading and +: lagging: PF2 integer×0.001
50566Power factor phase 3 -: leading and +: lagging: PF3 integer×0.001
50770Total positive active energy (no resetable): ea+ dword×1000
50772Total positive reactive energy (no resetable): er + dword×1000
50776Total negative active energy (no resetable): ea- dword×1000
50780Partial positive active energy: ea+ dword×1000
50782Partial positive reactive energy: er + dword×1000

This is not the complete map: 50 of 126 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Socomec (Countis E34, Countis E44) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Network settings block start
register 57344 (0xE000)
Network types
1BL, 2BL, 3BL, 3NBL, 4BL, 4NBL
Hour/date write
function 16, 6 words in one write

Registers in the map: 124 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.

MODBUS offsetDescriptionUnitsData typeScale
50007Product software version word 
50018Product version (Major) word 
50019Product version (Minor) word 
38912Communication board version (Major) word 
38913Communication board version (Minor) word 
38914Communication board version (Revision) word 
38915Communication board version (Build) word 
50000Product name string(8) 
50004Product order ID (Countis:100, protection:200, atys:300, diris:400) word 
50005Product ID word 
50030Product VLO string(8) 
50042Vendor name string(16) 
50050Product name string(16) 
50058Extended name string(16) 
38919Communication board VLO string(8) 
57346Current transformer primary word 
57355Synchronisation top for P+/- Q+/-: time in seconds ( 1mn, 5mn, 8mn, 10mn, 15mn, 20mn, 30mn, 60mn) word 
57602Year word 
50514Phase to phase voltage: U12 dword×0.01
50516Phase to phase voltage: U23 dword×0.01
50518Phase to phase voltage: U31 dword×0.01
50520Simple voltage: V1 dword×0.01
50522Simple voltage: V2 dword×0.01
50524Simple voltage: V3 dword×0.01
50526Frequency: F dword×0.01
50528Current: I1 dword×0.001
50530Current: I2 dword×0.001
50532Current: I3 dword×0.001
50534Neutral current: in dword×0.001
50536Active power +/-: P integer×10
50538Reactive power +/-: Q integer×10
50540Apparent power: S dword×10
50542Power factor: -: leading et +: laggingPFinteger×0.001
50544Active power phase 1 +/-: P1 integer×10
50546Active power phase 2 +/-: P2 integer×10
50548Active power phase 3 +/-: P3 integer×10
50550Reactive power phase 1 +/-: Q1 integer×10
50552Reactive power phase 2 +/-: Q2 integer×10
50554Reactive power phase 3 +/-: Q3 integer×10
50556Apparent power phase 1: S1 dword×10
50558Apparent power phase 2: S2 dword×10
50560Apparent power phase 3: S3 dword×10
50562Power factor phase 1 -: leading and +: lagging: PF1 integer×0.001
50564Power factor phase 2 -: leading and +: lagging: PF2 integer×0.001
50566Power factor phase 3 -: leading and +: lagging: PF3 integer×0.001
50770Total positive active energy (no resetable): ea+ dword×1000
50772Total positive reactive energy (no resetable): er + dword×1000
50776Total negative active energy (no resetable): ea- dword×1000
50780Partial positive active energy: ea+ dword×1000
50782Partial positive reactive energy: er + dword×1000

This is not the complete map: 50 of 124 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Socomec (Countis E50 E53 E50R E53R) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Info block
address 0
JBUS address
word 52 of the info block at address 0
JBUS baud rate
word 53 of the info block at address 0
Register addressing
addresses listed in decimal and hex

Registers in the map: 82 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, string(16), string(8), word.

MODBUS offsetDescriptionUnitsData typeScale
50007Product software version word 
50018Product version (Major) word 
50019Product version (Minor) word 
50020Product version (Revision) word 
50021Product version (Build) word 
50025Software technical base version (Major) word 
50026Software technical base version (Minor) word 
50027Software technical base version (Revision) word 
50028Customization version (Major) word 
50029Customization version (Minor) word 
50000Product name string(8) 
50004Product order ID (Countis:100, protection:200, atys:300, diris:400) word 
50005Product ID word 
50030Product VLO string(8) 
50034Customization VLO string(8) 
50038Software technical base VLO string(8) 
50042Vendor name string(16) 
50050Product name string(16) 
50058Extended name string(16) 
57346Current transformer primary word 
50512Hour meter dword×0.01
50514Phase to phase voltage: U12 dword×0.01
50516Phase to phase voltage: U23 dword×0.01
50518Phase to phase voltage: U31 dword×0.01
50520Simple voltage: V1 dword×0.01
50522Simple voltage: V2 dword×0.01
50524Simple voltage: V3 dword×0.01
50528Current: I1 dword×0.001
50530Current: I2 dword×0.001
50532Current: I3 dword×0.001
50536Active power +/-: P integer×10
50538Reactive power +/-: Q integer×10
50540Apparent power: S dword×10
50542Power factor: -: leading et +: laggingPFinteger×0.001
50544Active power phase 1 +/-: P1 integer×10
50546Active power phase 2 +/-: P2 integer×10
50548Active power phase 3 +/-: P3 integer×10
50550Reactive power phase 1 +/-: Q1 integer×10
50552Reactive power phase 2 +/-: Q2 integer×10
50554Reactive power phase 3 +/-: Q3 integer×10
50556Apparent power phase 1: S1 dword×10
50558Apparent power phase 2: S2 dword×10
50560Apparent power phase 3: S3 dword×10
50562Power factor phase 1 -: leading and +: lagging: PF1 integer×0.001
50564Power factor phase 2 -: leading and +: lagging: PF2 integer×0.001
50566Power factor phase 3 -: leading and +: lagging: PF3 integer×0.001
50770Total positive active energy (no resetable): ea+ dword×1000
50772Total positive reactive energy (no resetable): er + dword×1000
50774Total apparent energy (no resetable): es dword×1000
50776Total negative active energy (no resetable): ea- dword×1000

This is not the complete map: 50 of 82 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Socomec (Countis E63) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Communication board version
register 38912 (0x9800)
Network settings block start
register 57344 (0xE000)
Network types
1BL, 2BL, 3BL, 3NBL, 4BL, 4NBL
Hour/date write
function 16, 6 words in one write

Registers in the map: 134 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.

MODBUS offsetDescriptionUnitsData typeScale
50007Product software version word 
50018Product version (Major) word 
50019Product version (Minor) word 
50020Product version (Revision) word 
50021Product version (Build) word 
50025Software technical base version (Major) word 
50026Software technical base version (Minor) word 
50027Software technical base version (Revision) word 
50028Customization version (Major) word 
50029Customization version (Minor) word 
38912Communication board version (Major) word 
38913Communication board version (Minor) word 
38914Communication board version (Revision) word 
38915Communication board version (Build) word 
50000Product name string(8) 
50004Product order ID (Countis:100, protection:200, atys:300, diris:400) word 
50005Product ID word 
50030Product VLO string(8) 
50034Customization VLO string(8) 
50038Software technical base VLO string(8) 
50042Vendor name string(16) 
50050Product name string(16) 
50058Extended name string(16) 
38919Communication board VLO string(8) 
57346Current transformer primary word 
57355Synchronisation top for P+/- Q+/-: time in seconds ( 2mn, 5mn, 8mn, 10mn, 15mn, 20mn, 30mn, 60mn) word 
57602Year word 
50770Total positive active energy (no resetable): ea+ dword×1000
50780Partial positive active energy: ea+ dword×1000
50514Phase to phase voltage: U12 dword×0.01
50516Phase to phase voltage: U23 dword×0.01
50518Phase to phase voltage: U31 dword×0.01
50520Simple voltage: V1 dword×0.01
50522Simple voltage: V2 dword×0.01
50524Simple voltage: V3 dword×0.01
50526Frequency: F dword×0.01
50528Current: I1 dword×0.001
50530Current: I2 dword×0.001
50532Current: I3 dword×0.001
50536Active power +/-: P integer×10
50540Apparent power: S dword×10
50542Power factor: -: leading et +: laggingPFinteger×0.001
50544Active power phase 1 +/-: P1 integer×10
50546Active power phase 2 +/-: P2 integer×10
50548Active power phase 3 +/-: P3 integer×10
50556Apparent power phase 1: S1 dword×10
50558Apparent power phase 2: S2 dword×10
50560Apparent power phase 3: S3 dword×10
50562Power factor phase 1 -: leading and +: lagging: PF1 integer×0.001
50564Power factor phase 2 -: leading and +: lagging: PF2 integer×0.001

This is not the complete map: 50 of 134 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.