Socomec (Countis E24) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
50000
Product name
 
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
 
word
50005
Product ID
 
word
50007
Product software version
 
word
50018
Product version (Major)
 
word
50019
Product version (Minor)
 
word
50020
Product version (Revision)
 
word
50021
Product version (Build)
 
word
50025
Software technical base version (Major)
 
word
50026
Software technical base version (Minor)
 
word
50027
Software technical base version (Revision)
 
word
50028
Customization version (Major)
 
word
50029
Customization version (Minor)
 
word
50030
Product VLO
 
string(8)
50034
Customization VLO
 
string(8)
50038
Software technical base VLO
 
string(8)
50042
Vendor name
 
string(16)
50050
Product name
 
string(16)
50058
Extended name
 
string(16)
50514
Phase to phase voltage: U12
 
dword
50516
Phase to phase voltage: U23
 
dword
50518
Phase to phase voltage: U31
 
dword
50520
Simple voltage: V1
 
dword
50522
Simple voltage: V2
 
dword
50524
Simple voltage: V3
 
dword
50528
Current: I1
 
dword
50530
Current: I2
 
dword
50532
Current: I3
 
dword
50534
Neutral current: in
 
dword
50536
Active power +/-: P
 
integer
50538
Reactive power +/-: Q
 
integer
50540
Apparent power: S
 
dword
50542
Power factor: -: leading et +: lagging: PF
 
integer
50544
Active power phase 1 +/-: P1
 
integer
50546
Active power phase 2 +/-: P2
 
integer
50548
Active power phase 3 +/-: P3
 
integer
50550
Reactive power phase 1 +/-: Q1
 
integer
50552
Reactive power phase 2 +/-: Q2
 
integer
50554
Reactive power phase 3 +/-: Q3
 
integer
50556
Apparent power phase 1: S1
 
dword
50558
Apparent power phase 2: S2
 
dword
50560
Apparent power phase 3: S3
 
dword
50562
Power factor phase 1 -: leading and +: lagging: PF1
 
integer
50564
Power factor phase 2 -: leading and +: lagging: PF2
 
integer
50566
Power factor phase 3 -: leading and +: lagging: PF3
 
integer
50770
Total positive active energy (no resetable): ea+
 
dword
50772
Total positive reactive energy (no resetable): er +
 
dword
50776
Total negative active energy (no resetable): ea-
 
dword
50780
Partial positive active energy: ea+
 
dword
50782
Partial positive reactive energy: er +
 
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Socomec (Countis E33, Countis E43) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
50000
Product name
 
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
 
word
50005
Product ID
 
word
50007
Product software version
 
word
50018
Product version (Major)
 
word
50019
Product version (Minor)
 
word
50030
Product VLO
 
string(8)
50042
Vendor name
 
string(16)
50050
Product name
 
string(16)
50058
Extended name
 
string(16)
38912
Communication board version (Major)
 
word
38913
Communication board version (Minor)
 
word
38914
Communication board version (Revision)
 
word
38915
Communication board version (Build)
 
word
38919
Communication board VLO
 
string(8)
57346
Current transformer primary
 
word
57355
Synchronisation top for P+/- Q+/-: time in seconds ( 1mn, 5mn, 8mn, 10mn, 15mn, 20mn, 30mn, 60mn)
 
word
57602
Year
 
word
50514
Phase to phase voltage: U12
 
dword
50516
Phase to phase voltage: U23
 
dword
50518
Phase to phase voltage: U31
 
dword
50520
Simple voltage: V1
 
dword
50522
Simple voltage: V2
 
dword
50524
Simple voltage: V3
 
dword
50526
Frequency: F
 
dword
50528
Current: I1
 
dword
50530
Current: I2
 
dword
50532
Current: I3
 
dword
50534
Neutral current: in
 
dword
50536
Active power +/-: P
 
integer
50538
Reactive power +/-: Q
 
integer
50540
Apparent power: S
 
dword
50542
Power factor: -: leading et +: lagging: PF
 
integer
50544
Active power phase 1 +/-: P1
 
integer
50546
Active power phase 2 +/-: P2
 
integer
50548
Active power phase 3 +/-: P3
 
integer
50550
Reactive power phase 1 +/-: Q1
 
integer
50552
Reactive power phase 2 +/-: Q2
 
integer
50554
Reactive power phase 3 +/-: Q3
 
integer
50556
Apparent power phase 1: S1
 
dword
50558
Apparent power phase 2: S2
 
dword
50560
Apparent power phase 3: S3
 
dword
50562
Power factor phase 1 -: leading and +: lagging: PF1
 
integer
50564
Power factor phase 2 -: leading and +: lagging: PF2
 
integer
50566
Power factor phase 3 -: leading and +: lagging: PF3
 
integer
50770
Total positive active energy (no resetable): ea+
 
dword
50772
Total positive reactive energy (no resetable): er +
 
dword
50776
Total negative active energy (no resetable): ea-
 
dword
50780
Partial positive active energy: ea+
 
dword
50782
Partial positive reactive energy: er +
 
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Socomec (Countis E34, Countis E44) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
50000
Product name
 
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
 
word
50005
Product ID
 
word
50007
Product software version
 
word
50018
Product version (Major)
 
word
50019
Product version (Minor)
 
word
50030
Product VLO
 
string(8)
50042
Vendor name
 
string(16)
50050
Product name
 
string(16)
50058
Extended name
 
string(16)
38912
Communication board version (Major)
 
word
38913
Communication board version (Minor)
 
word
38914
Communication board version (Revision)
 
word
38915
Communication board version (Build)
 
word
38919
Communication board VLO
 
string(8)
57346
Current transformer primary
 
word
57355
Synchronisation top for P+/- Q+/-: time in seconds ( 1mn, 5mn, 8mn, 10mn, 15mn, 20mn, 30mn, 60mn)
 
word
57602
Year
 
word
50514
Phase to phase voltage: U12
 
dword
50516
Phase to phase voltage: U23
 
dword
50518
Phase to phase voltage: U31
 
dword
50520
Simple voltage: V1
 
dword
50522
Simple voltage: V2
 
dword
50524
Simple voltage: V3
 
dword
50526
Frequency: F
 
dword
50528
Current: I1
 
dword
50530
Current: I2
 
dword
50532
Current: I3
 
dword
50534
Neutral current: in
 
dword
50536
Active power +/-: P
 
integer
50538
Reactive power +/-: Q
 
integer
50540
Apparent power: S
 
dword
50542
Power factor: -: leading et +: lagging: PF
 
integer
50544
Active power phase 1 +/-: P1
 
integer
50546
Active power phase 2 +/-: P2
 
integer
50548
Active power phase 3 +/-: P3
 
integer
50550
Reactive power phase 1 +/-: Q1
 
integer
50552
Reactive power phase 2 +/-: Q2
 
integer
50554
Reactive power phase 3 +/-: Q3
 
integer
50556
Apparent power phase 1: S1
 
dword
50558
Apparent power phase 2: S2
 
dword
50560
Apparent power phase 3: S3
 
dword
50562
Power factor phase 1 -: leading and +: lagging: PF1
 
integer
50564
Power factor phase 2 -: leading and +: lagging: PF2
 
integer
50566
Power factor phase 3 -: leading and +: lagging: PF3
 
integer
50770
Total positive active energy (no resetable): ea+
 
dword
50772
Total positive reactive energy (no resetable): er +
 
dword
50776
Total negative active energy (no resetable): ea-
 
dword
50780
Partial positive active energy: ea+
 
dword
50782
Partial positive reactive energy: er +
 
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Socomec (Countis E50 E53 E50R E53R) - Mapping

MODBUS offset
Description
Units
Data type
50000
Product name
 
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
 
word
50005
Product ID
 
word
50007
Product software version
 
word
50018
Product version (Major)
 
word
50019
Product version (Minor)
 
word
50020
Product version (Revision)
 
word
50021
Product version (Build)
 
word
50025
Software technical base version (Major)
 
word
50026
Software technical base version (Minor)
 
word
50027
Software technical base version (Revision)
 
word
50028
Customization version (Major)
 
word
50029
Customization version (Minor)
 
word
50030
Product VLO
 
string(8)
50034
Customization VLO
 
string(8)
50038
Software technical base VLO
 
string(8)
50042
Vendor name
 
string(16)
50050
Product name
 
string(16)
50058
Extended name
 
string(16)
57346
Current transformer primary
 
word
50512
Hour meter
 
dword
50514
Phase to phase voltage: U12
 
dword
50516
Phase to phase voltage: U23
 
dword
50518
Phase to phase voltage: U31
 
dword
50520
Simple voltage: V1
 
dword
50522
Simple voltage: V2
 
dword
50524
Simple voltage: V3
 
dword
50528
Current: I1
 
dword
50530
Current: I2
 
dword
50532
Current: I3
 
dword
50536
Active power +/-: P
 
integer
50538
Reactive power +/-: Q
 
integer
50540
Apparent power: S
 
dword
50542
Power factor: -: leading et +: lagging: PF
 
integer
50544
Active power phase 1 +/-: P1
 
integer
50546
Active power phase 2 +/-: P2
 
integer
50548
Active power phase 3 +/-: P3
 
integer
50550
Reactive power phase 1 +/-: Q1
 
integer
50552
Reactive power phase 2 +/-: Q2
 
integer
50554
Reactive power phase 3 +/-: Q3
 
integer
50556
Apparent power phase 1: S1
 
dword
50558
Apparent power phase 2: S2
 
dword
50560
Apparent power phase 3: S3
 
dword
50562
Power factor phase 1 -: leading and +: lagging: PF1
 
integer
50564
Power factor phase 2 -: leading and +: lagging: PF2
 
integer
50566
Power factor phase 3 -: leading and +: lagging: PF3
 
integer
50770
Total positive active energy (no resetable): ea+
 
dword
50772
Total positive reactive energy (no resetable): er +
 
dword
50774
Total apparent energy (no resetable): es
 
dword
50776
Total negative active energy (no resetable): ea-
 
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

Socomec (Countis E63) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
50000
Product name
 
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
 
word
50005
Product ID
 
word
50007
Product software version
 
word
50018
Product version (Major)
 
word
50019
Product version (Minor)
 
word
50020
Product version (Revision)
 
word
50021
Product version (Build)
 
word
50025
Software technical base version (Major)
 
word
50026
Software technical base version (Minor)
 
word
50027
Software technical base version (Revision)
 
word
50028
Customization version (Major)
 
word
50029
Customization version (Minor)
 
word
50030
Product VLO
 
string(8)
50034
Customization VLO
 
string(8)
50038
Software technical base VLO
 
string(8)
50042
Vendor name
 
string(16)
50050
Product name
 
string(16)
50058
Extended name
 
string(16)
38912
Communication board version (Major)
 
word
38913
Communication board version (Minor)
 
word
38914
Communication board version (Revision)
 
word
38915
Communication board version (Build)
 
word
38919
Communication board VLO
 
string(8)
57346
Current transformer primary
 
word
57355
Synchronisation top for P+/- Q+/-: time in seconds ( 2mn, 5mn, 8mn, 10mn, 15mn, 20mn, 30mn, 60mn)
 
word
57602
Year
 
word
50770
Total positive active energy (no resetable): ea+
 
dword
50780
Partial positive active energy: ea+
 
dword
50514
Phase to phase voltage: U12
 
dword
50516
Phase to phase voltage: U23
 
dword
50518
Phase to phase voltage: U31
 
dword
50520
Simple voltage: V1
 
dword
50522
Simple voltage: V2
 
dword
50524
Simple voltage: V3
 
dword
50526
Frequency: F
 
dword
50528
Current: I1
 
dword
50530
Current: I2
 
dword
50532
Current: I3
 
dword
50536
Active power +/-: P
 
integer
50540
Apparent power: S
 
dword
50542
Power factor: -: leading et +: lagging: PF
 
integer
50544
Active power phase 1 +/-: P1
 
integer
50546
Active power phase 2 +/-: P2
 
integer
50548
Active power phase 3 +/-: P3
 
integer
50556
Apparent power phase 1: S1
 
dword
50558
Apparent power phase 2: S2
 
dword
50560
Apparent power phase 3: S3
 
dword
50562
Power factor phase 1 -: leading and +: lagging: PF1
 
integer
50564
Power factor phase 2 -: leading and +: lagging: PF2
 
integer
There are more MODBUS items for this device. Please download the program to discover all registers.