Stromzahler DRT428M MODBUS registers: read online

Connect Stromzahler to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Stromzahler logging and read.

Do you not know the meter address? Scan the device address online

Stromzahler (DRT428M) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Default baud rate
9600 bps
Baud rate options
1200, 2400, 4800 bps
Default device address
01
Frame check
2-byte CRC
Function codes
03 read parameters
Register addressing
registers map as listed
Data format
float values occupy two consecutive registers

Registers in the map: 80 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: int64, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0Serial number wordformula
4Software version single 
6Hardware version single 
9S0 output rate single 
10Combined code word 
12HOLIDAY-WEEKEND TIME word 
13Cycle time wordformula
14L1 voltageVsingle 
16L2 voltageVsingle 
18L3 voltageVsingle 
20Grid frequencyHzsingle 
22L1 currentAsingle 
24L2 currentAsingle 
26L3 currentAsingle 
28Total active powerkWsingle 
30L1 active powerkWsingle 
32L2 active powerkWsingle 
34L3 active powerkWsingle 
36Total reactive powerkvarsingle 
38L1 reactive powerkvarsingle 
40L2 reactive powerkvarsingle 
42L3 reactive powerkvarsingle 
44Total apparent powerkVAsingle 
46L1 apparent powerkVAsingle 
48L2 apparent powerkVAsingle 
50L3 apparent powerkVAsingle 
52Total power factor single 
54Power factor single 
56Power factor single 
58Power factor single 
60Time int64formula
64Season swtch word 
256Total active energykWhsingle 
258L1 total active energykWhsingle 
260L2 total active energykWhsingle 
262L3 total active energykWhsingle 
264Forward active energykWhsingle 
266L1 forward active energykWhsingle 
268L2 forward active energykWhsingle 
270L3 forward active energykWhsingle 
272Reverse acfive energyhsingle 
274L1 reverse active energykWhsingle 
276L2 reverse active energykWhsingle 
278L3 reverse active energykWhsingle 
280Total reactive energykvarhsingle 
282L1 reactive energykvarhsingle 
284L2 reactive energykvarhsingle 
286L3 reactive energykvarhsingle 
288Forward reactive energykvarhsingle 
290L1 forward reactive energykvarhsingle 

This is not the complete map: 50 of 80 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.