Solis 125K, 185K, Inverter MODBUS registers: read online

Connect Solis to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Solis data logging and capture.

Do you not know the meter address? Scan the device address online

Solis (125K,185K) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Interface
RS-485
0x registers
write only, function 05
1x registers
read only, function 02
3x registers
read only, function 04
4x registers
read/write, functions 03, 06, 10
Register addressing
addresses used as in the message frame (no extra offset)
Byte order
multi-byte fields high byte first
CRC order
low byte first
Error response
function code plus 0x80

Registers in the map: 222 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 2 (discrets). function 4 (input registers). byte order big-endian. data types: bit, dword, integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
2500No grid bit 
2501Grid over voltage bit 
2502Grid under voltage bit 
2503Grid over frequency bit 
2504Grid under frequency bit 
2505Unbalanced grid bit 
2506Gird frequency jitter bit 
2507Over impedance grid bit 
2508Grid current tracking error bit 
2509METER communication fail bit 
2510FailSafe bit 
2516Backup overvoltage fault bit 
2517Backup overload fault bit 
2532Battery not connected bit 
2533Battery overvoltage detection bit 
2534Battery undervoltage detection bit 
2548DC overvoltage bit 
2549DC bus overvoltage bit 
2550DC bus unbalanced voltage bit 
2551DC bus undervoltage bit 
2552DC bus unbalanced voltage 2 bit 
2553DC overcurrent on A circuit bit 
2555DC input interference bit 
2556Grid overcurrent bit 
2557IGBT overcurrent bit 
2558Grid interference 02 bit 
2559AFCI self detection protection bit 
2561Grid current sampling error bit 
2564Grid interference bit 
2565Over DC component bit 
2566Over temperature protection bit 
2567Relay check protection bit 
2568Under temperature protection bit 
2569PV insulation fault bit 
257012V undervoltage protection bit 
2571Leak current protection bit 
2572Leak current self check protection bit 
2573DSP initializing protection bit 
2574DSP B proection bit 
2575Battery overvoltage hardware fault bit 
2576LLC hardware overcurrent bit 
2577Gird transient overcurrent bit 
2578CAN COM fail bit 
2579DSP COM fail bit 
2580Normal operation bit 
2581Initializing bit 
2582Controlled turning OFF bit 
2583Fault leads to OFF turning bit 
2584Stand-by bit 
2585Limited operation (Caused by temperature, frequency etc bit 

This is not the complete map: 50 of 222 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Solis (Inverter) - MODBUS Mapping

Registers in the map: 14. function 4 (input registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
33000Model No. word 
33001DSP version word 
33002HMI version word 
33003Protocol version word 
35000Inverter model definition word 
3004Active powerWdword 
3006Total DC output powerWdword 
3008Total powerkWhdword 
3010Energy generated this monthkWhdword 
3012Energy generated last monthkWhdword 
3014Energy generated todaykWhword×0.1
3015Energy generated yesterdaykWhword×0.1
3016Energy generated this yearkWhdword 
3018Energy generated last yearkWhdword 