ABB (Trio 50,Trio 60) data logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
1000
Inverter ID
 
word
1001
Inverter block modbus map size
 
word
1002
Inverter presence
 
word
1050
Global state
 
word
1051
Alarm state
 
word
1052
DC/DC converter state
 
word
1053
DC/AC converter state
 
word
1054
Derating state
 
word
1070
Daily energy
Wh
dword
1072
Total energy
Wh
dword
1074
Partial energy
Wh
dword
1076
Weekly energy
Wh
dword
1078
Monthly energy
Wh
dword
1080
Yearly energy
Wh
dword
1090
Mean grid voltage (Phase to neutral)
V
single
1092
Mean output current (Phase to neutral)
A
single
1094
Output active power: instantaneous
W
single
1096
Output active power: absolute peak
W
single
1098
Output active power: daily peak
W
single
1100
Output active power: feedback on curtailment applied
W
single
1102
Reactive power: feedback on set point applied
VAr
single
1104
Power factor: feedback on set point applied
 
single
1106
Mean grid frequency
Hz
single
1108
Active power on DC input #1
W
single
1110
Voltage on DC input #1
V
single
1112
Current on DC input #1
A
single
1120
Internal temperature
degC
single
1122
Inverter temperature
degC
single
1126
Isolation resistance
MOhm
single
1128
Max leakage current
A
single
3654
Build version
 
word