Circutor CVM-MINI logging. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
2 | Current, a l1 | mA | dword |
4 | Active power, kw l1 | w | dword |
6 | Reactive power, kvar l1 | w | dword |
74 | Apparent power, kv a l1 | | dword |
8 | Power factor, pf l1 | x | dword |
10 | Voltage phase, v l2 | V | dword |
12 | Current, a l2 | mA | dword |
14 | Active power, kw l2 | w | dword |
16 | Reactive power, kvar l2 | w | dword |
76 | Apparent power, kv a l2 | w | dword |
18 | Power factor, pf l2 | x | dword |
20 | Voltage phase, v l3 | V | dword |
22 | Current, a l3 | mA | dword |
24 | Active power, kw l3 | W | dword |
26 | Reactive power, kvar l3 | W | dword |
78 | Apparent power, kv a l3 | w | dword |
28 | Power factor, pf l3 | x | dword |
80 | Temperature, c | C | dword |
30 | Active power iii, kw iii | w | dword |
32 | Inductive power iii, kvarl iii | w | dword |
34 | Capacitive power iii, kvarc iii | w | dword |
36 | Cos iii, cos iii | x | dword |
38 | Power factor iii, pf iii | x | dword |
40 | Frequency, hz | Hz | dword |
42 | Voltage line l1-l2, v12 | V | dword |
44 | Voltage line l2-l3, v23 | V | dword |
46 | Voltage line l3-l1, v31 | V | dword |
48 | % thd v l1, %thd vl1 | % | dword |
50 | % thd v l2, %thd vl2 | % | dword |
52 | % thd v l3, %thd vl3 | % | dword |
54 | % thd a l1, %thd al1 | % | dword |
56 | % thd a l2, %thd al2 | % | dword |
58 | % thd a l3, %thd al3 | % | dword |
66 | Apparent power iii, kvaiii | w | dword |
68 | Maximum demand, md (pd) | w/VA/mA | dword |
70 | Three-phase current (average, a_avg | mA | dword |
72 | Neutral current, in | mA | dword |
82 | Maximum demand a2, md (pd) | mA | dword |
84 | Maximum demand a3, md (pd) | mA | dword |
60 | Active energy, kw h iii | w | dword |
62 | Inductive reactive energy, kvarl h iii | w | dword |
64 | Capacitive reactive energy, kvarc h iii | w | dword |
86 | Apparent energy, kva h iii | w | dword |
88 | Active energy generated, kw h iii (-) | w | dword |
90 | Inductive energy generated, kvarl h iii (-) | w | dword |
92 | Capacitive energy generated, kvarc h iii (-) | w | dword |
94 | Apparent energy generated, kva h iii (-) | w | dword |
Circutor (CVM-C10) data logging
Circutor CVM144 data logging
Circutor CVM-MINI data logging
Circutor CVM-NRG data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
|