Circutor CVM-96, CVM-C10, CVM144 MODBUS registers: read online

Connect Circutor to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Circutor data logger and record.

Do you not know the meter address? Scan the device address online

Circutor (CVM-96) - Measurement Data

Connection and addressing notes

Protocol
Modbus RTU
Data bits
8
Error check
CRC
Character format
each 8-bit byte carries two hex characters
Function codes
01 read relay states, 03 read words, 04 read words, 05 write one relay
Parameter size
32-bit value read as two 16-bit words

Registers in the map: 152 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0Phase_voltage V1Vdword×0.1
2Current A1Adword×0.001
4Active power kW1Wdword 
6Reactive power kvar1vardword 
8Power factor PF1 dword×0.01
10Phase voltage V2Vdword×0.1
12Current A2Adword×0.001
14Active power kW2Wdword 
16Reactive power kvar3vardword 
18Power factor PF2 dword×0.01
20Phase voltage V3Vdword×0.1
22Current A3Adword×0.001
24Active power kW3Wdword 
26Reactive_power kvar 3vardword 
28Power factor PF3 dword×0.01
30Three-phase active power kW IIIWdword 
32Three-phase inductive power kvarL IIIvardword 
34Three-phase capacitive power kvarC IIIvardword 
36CosF III dword×0.01
38Three-phase power factor PF III dword×0.01
40Frequency (L1) hzHzdword×0.1
42V12Vdword×0.1
44V23Vdword×0.1
46V31Vdword×0.1
48% THD V 1%dword×0.1
50% THD V 2%dword×0.1
52% THD V 3%dword×0.1
54% THD I 1%dword×0.1
56% THD I 2%dword×0.1
58% THD I 3%dword×0.1
60Active energy kWhWhdword 
62Inductive reactive energy kvarh LvarLhdword 
64Capacitive reactive energy kvarh CvarChdword 
66Three phase apparent powerkVAdword 
68Power demandWdword 
70Corriente trifsica AIIIAdword×0.001
72Neutral currentAdword×0.001
82Power demand (L2)Wdword 
84Power demand (L3)Wdword 
500L1 fundamentalAdword×0.001
502L1 harmonic 2%dword 
504L1 harmonic 3%dword 
506L1 harmonic 4%dword 
508L1 harmonic 5%dword 
510L1 harmonic 6%dword 
512L1 harmonic 7%dword 
514L1 harmonic 8%dword 
516L1 harmonic 9%dword 
518L1 harmonic 10%dword 
520L1 harmonic 11%dword 

This is not the complete map: 50 of 152 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Circutor (CVM-C10) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Register addressing
all Modbus memory addresses are hexadecimal
Function codes
03, 04 (measurement variables)

Registers in the map: 101 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
21000A dword 
0L1 phase voltageVdword×0.1
2L1 currentAdword×0.001
4L1 active powerWdword 
6L1 inductive powervardword 
8L1 capacitive powervardword 
10L1 apparent powerVAdword 
12L1 power factor dword×0.01
14Cos L1 dword×0.01
16L2 phase voltageVdword×0.1
18L2 currentAdword×0.001
20L2 active powerWdword 
22L2 inductive powervardword 
24L2 capacitive powervardword 
26L2 apparent powerVAdword 
28L2 power factor dword×0.01
30Cos L2 dword×0.01
32L3 phase voltageVdword×0.1
34L3 currentAdword×0.001
36L3 active powerWdword 
38L3 inductive powervardword 
40L3 capacitive powervardword 
42L3 apparent powerVAdword 
44L3 power factor dword×0.01
46Cos L3 dword×0.01
48Active three-phase powerWdword 
50Inductive three-phase powervardword 
52Capacitive three-phase powervardword 
54Apparent three-phase powerVAdword 
56Three-phase power factor dword×0.01
58Three-phase cos dword×0.01
60L1 frequencyHzdword×0.01
62L1-L2 voltageVdword×0.1
64L2-L3 voltageVdword×0.1
66L3-L1 voltageVdword×0.1
68Neutral current NAdword×0.001
70L1 voltage % THD%dword×0.1
72L2 voltage % THD%dword×0.1
74L3 voltage % THD%dword×0.1
76L1 current % THD%dword×0.1
78L2 current % THD%dword×0.1
80L3 current % THD%dword×0.1
82Maximum demand kW IIIWdword 
84Maximum demand kVA IIIVAdword 
86Maximum demand I AVGAdword×0.001
88Maximum demand I L1Adword×0.001
90Maximum demand I L2Adword×0.001
92Maximum demand I L3Adword×0.001
512Maximum demand kvarL IIIkvarLdword 
514Maximum demand kvarC IIIkvarCdword 

This is not the complete map: 50 of 101 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Circutor CVM144 - MODBUS Registers

Registers in the map: 58 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0Phase voltage - V1Vdword×0.1
2Current - A1 dword 
4Active power - kW1 dword 
6Reactive power - kvar1 dword 
8Power factor - PF1PFdword×0.01
10Phase voltage - V2Vdword×0.1
12Current - A2 dword 
14Active power - kW2 dword 
16Reactive power - kvar2 dword 
18Power factor - PF2PFdword×0.01
20Phase voltage - V3Vdword×0.1
22Current - A3 dword 
24Active power - kW3 dword 
26Reactive power - kvar3 dword 
28Power factor - PF3PFdword×0.01
30Three-phase active power-kWIII dword 
32Three-phase inductive power-kvarL III dword 
34Three-phase capacitive power-kvarC III dword 
36Cos M III dword×0.01
38Three-phase power factor - PF III dword×0.01
40Frequency (L1) - hzHzdword×0.1
42Line voltage L1-L2 - v12Vdword×0.1
44Line voltage L2-L3 - v23Vdword×0.1
46Line voltage L3-L1 - v31Vdword×0.1
48%THD V1%dword×0.1
50%THD V2%dword×0.1
52%THD V3%dword×0.1
54%THD I1%dword×0.1
56%THD I2%dword×0.1
58%THD I3%dword×0.1
60Active energykWhdword 
62Inductive reactive energy - kvarh L dword 
64Capacitive reactive energy - kvarh C dword 
66Three phase apparent power dword 
68Power demand (L1) dword 
70Three-phase current dword 
72Neutral current dword 
74Analog input 1 dword 
76Analog input 2 dword 
78Analog input 3 dword 
80Residual (earth leakage) current dword 
82Power demand (L2) dword 
84Power demand (L3) dword 
500Fundamental dword 
502Harmonic 2 dword 
504Harmonic 3 dword 
506Harmonic 4 dword 
508Harmonic 5 dword 
510Harmonic 6 dword 
512Harmonic 7 dword 

This is not the complete map: 50 of 58 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.