bg

Delta DPM 520, DPM 530 MODBUS registers: read online

Connect Delta to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Delta modbus logging and log.

Do you not know the meter address? Scan the device address online

Delta (DPM 520) - MODBUS Measurements

Registers in the map: 117 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
256Voltage A NVsingle 
258Voltage B NVsingle 
260Voltage C NVsingle 
262Voltage L N avgVsingle 
264Voltage A BVsingle 
266Voltage B CVsingle 
268Voltage C AVsingle 
270Voltage L L avgVsingle 
272Voltage unbalance A N%single 
274Voltage unbalance B N%single 
276Voltage unbalance C N%single 
278Voltage unbalance L N avg%single 
280Voltage unbalance A B%single 
282Voltage unbalance B C%single 
284Voltage unbalance C A%single 
286Voltage unbalance L L avg%single 
288Current AAsingle 
290Current BAsingle 
292Current CAsingle 
294Current avgAsingle 
296Current NAsingle 
298Current unbalance A%single 
300Current unbalance B%single 
302Current unbalance C%single 
304Current unbalance avg%single 
306Power factor total single 
308Power factor A single 
310Power factor B single 
312Power factor C single 
314Displacement power factor total single 
316Displacement power factor A single 
318Displacement power factor B single 
320Displacement power factor C single 
322FrequencyHzsingle 
324Active power totalkWsingle 
326Active power AkWsingle 
328Active power BkWsingle 
330Active power CkWsingle 
332Reactive power totalkvarsingle 
334Reactive power Akvarsingle 
336Reactive power Bkvarsingle 
338Reactive power Ckvarsingle 
340Apparent power totalkVAsingle 
342Apparent power AkVAsingle 
344Apparent power BkVAsingle 
346Apparent power CkVAsingle 
348Active energy deliveredWhdword 
350Active energy receivedWhdword 
352Reactive energy deliveredvarhdword 
354Reactive energy receivedvarhdword 

This is not the complete map: 50 of 117 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Delta (DPM 530) - MODBUS Values

Registers in the map: 283 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single, word.

MODBUS offsetDescriptionUnitsData typeScale
256Voltage A NVsingle 
258Voltage B NVsingle 
260Voltage C NVsingle 
262Voltage L N avgVsingle 
264Voltage A BVsingle 
266Voltage B CVsingle 
268Voltage C AVsingle 
270Voltage L L avgVsingle 
272Voltage unbalance A N%single 
274Voltage unbalance B N%single 
276Voltage unbalance C N%single 
278Voltage unbalance L N avg%single 
280Voltage unbalance A B%single 
282Voltage unbalance B C%single 
284Voltage unbalance C A%single 
286Voltage unbalance L L avg%single 
288Current AAsingle 
290Current BAsingle 
292Current CAsingle 
294Current avgAsingle 
296Current NAsingle 
298Current unbalance A%single 
300Current unbalance B%single 
302Current unbalance C%single 
304Current unbalance avg%single 
306Power factor total single 
308Power factor A single 
310Power factor B single 
312Power factor C single 
314Displacement power factor total single 
316Displacement power factor A single 
318Displacement power factor B single 
320Displacement power factor C single 
322FrequencyHzsingle 
324Active power totalkWsingle 
326Active power AkWsingle 
328Active power BkWsingle 
330Active power CkWsingle 
332Reactive power totalkvarsingle 
334Reactive power Akvarsingle 
336Reactive power Bkvarsingle 
338Reactive power Ckvarsingle 
340Apparent power totalkVAsingle 
342Apparent power AkVAsingle 
344Apparent power BkVAsingle 
346Apparent power CkVAsingle 
348Active energy deliveredWhsingle 
350Active energy receivedWhsingle 
352Reactive energy deliveredvarhsingle 
354Reactive energy receivedvarhsingle 

This is not the complete map: 50 of 283 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection