Dent Instruments PowerScount 3037 MODBUS registers: read online

Connect Dent Instruments to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Dent Instruments logger and poll.

Do you not know the meter address? Scan the device address online

Dent Instruments (PowerScount 3037) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Register base
40001 (holding registers)
Register addressing example
Modbus address 44001 = offset 4000

Registers in the map: 178 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, word.

MODBUS offsetDescriptionUnitsData typeScale
4000System total true energykWhdword 
4002System total true powerkWword 
4003System maximum demand word 
4004Average powerkWword 
4005System maximum instantaneouskWword 
4006System minimum instantaneouskWword 
4007System total reactive energykvarhdword 
4009System total reactive powerkvarword 
4010System total apparent energykVAhdword 
4012System total apparent powerkVAword 
4013System displacement power factorPFword×0.01
4014System apparent power factorPFword×0.01
4015Average of all phases word 
4016Voltage line to lineVword 
4017Voltage line to neutralVword 
4018Phase to phase voltages, L1 word 
4019Phase to phase voltages, L2 word 
4020Phase to phase voltages, L1 word 
4021Line frequencyHzword 
4022Phase true energy, L1kWhdword 
4024Phase true energy, L2kWhdword 
4026Phase true energy, L3kWhdword 
4028Phase true powers, L1kWword 
4029Phase true powers, L2kWword 
4030Phase true powers, L3kWword 
4031Phase reactive energy, L1kvarhdword 
4033Phase reactive energy, L2kvarhdword 
4035Phase reactive energy, L3kvarhdword 
4037Phase reactive powers, L1kvarword 
4038Phase reactive powers, L2kvarword 
4039Phase reactive powers, L3kvarword 
4040Phase apparent energy, L1kVAhdword 
4042Phase apparent energy, L2kVAhdword 
4044Phase apparent energy, L3kVAhdword 
4046Phase apparent powers, L1kVAword 
4047Phase apparent powers, L2kVAword 
4048Phase apparent powers, L3kVAword 
4049Phase displacement power factor, L1PFword 
4050Phase displacement power factor, L2PFword 
4051Phase displacement power factor, L3PFword 
4052Phase apparent power factors, L1PFword 
4053Phase apparent power factors, L2PFword 
4054Phase apparent power factors, L3PFword 
4055Phase currents, L1Aword 
4056Phase currents, L2Aword 
4057Phase currents, L3Aword 
4058Phase to neutral voltages, L1Vword 
4059Phase to neutral voltages, L2Vword 
4060Phase to neutral voltages, L3Vword 
4061Seconds since KWH register was reset dword 

This is not the complete map: 50 of 178 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.