Connect EDMI to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous EDMI logging and read.
Do you not know the meter address? Scan the device address online
EDMI (Atlas MK10) - MODBUS Registers Map
Connection and addressing notes
- Protocol
- Modbus RTU
- Default baud rate
- 9600
- Data bits
- 8
- Stop bits
- 1
- Parity
- none
- Frame format
- 9600 8N1
- Minimum delay between reads
- 6 seconds
- Start address and register count
- even numbers greater than zero
- Maximum registers per read
- 62
- Invalid read request
- meter does not respond
- Register addressing
- 4xxxx (1-based) holding registers
Registers in the map: 31. function 3 (holding registers). byte order big-endian. data types: integer, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 1 | Serial number | | integer | |
| 3 | Export wh total ch0 | | single | |
| 5 | Import wh total ch1 | | single | |
| 7 | Export varh total ch2 | | single | |
| 9 | Import varh total ch3 | | single | |
| 11 | Va | | single | |
| 13 | Vb | | single | |
| 15 | Vc | | single | |
| 17 | Ia | | single | |
| 19 | Ib | | single | |
| 21 | Ic | | single | |
| 23 | Angle a | | single | |
| 25 | Angle b | | single | |
| 27 | Angle C | | single | |
| 29 | Va ia angle | | single | |
| 31 | Va ib angle | | single | |
| 33 | Va ic angle | | single | |
| 35 | Va va angle | | single | |
| 37 | Va vb angle | | single | |
| 39 | Va vc angle | | single | |
| 41 | Phase A | W | single | |
| 43 | Phase B | W | single | |
| 45 | Phase C | W | single | |
| 47 | Phase A vars | | single | |
| 49 | Phase B vars | | single | |
| 51 | Phase C vars | | single | |
| 53 | Phase A | VA | single | |
| 55 | Phase B | VA | single | |
| 57 | Phase C | VA | single | |
| 59 | Frequency | | single | |
| 61 | Power factor | | single | |
EDMI (Atlas MK7) - MODBUS Registers Map
Connection and addressing notes
- Protocol
- Modbus RTU
- Default baud rate
- 9600
- Data bits
- 8
- Stop bits
- 1
- Parity
- none
- Frame format
- 9600 8N1
- Minimum delay between reads
- 6 seconds
- Start address and register count
- even numbers greater than zero
- Maximum registers per read
- 62
- Invalid read request
- meter does not respond
- Register addressing
- 4xxxx (1-based) holding registers
Registers in the map: 15. function 3 (holding registers). byte order big-endian. data types: integer, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 1 | Serial number | | integer | |
| 3 | Export wh total ch0 | | single | |
| 5 | Import wh total ch1 | | single | |
| 7 | Export varh total ch2 | | single | |
| 9 | Import varh total ch3 | | single | |
| 11 | Va | | single | |
| 17 | Ia | | single | |
| 23 | Angle a | | single | |
| 29 | Va ia angle | | single | |
| 35 | Va va angle | | single | |
| 41 | Phase A | W | single | |
| 47 | Phase A vars | | single | |
| 53 | Phase A | VA | single | |
| 59 | Frequency | | single | |
| 61 | Power factor | | single | |
Related MODBUS registers maps
MODBUS Maps Index
EDME (Genius Mk6)
Dent Instruments (PowerScount 3037)
ENTES (EMM)
ENTES (MPR2 Series)