EDMI Atlas MK10, Atlas MK7 MODBUS registers: read online

Connect EDMI to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous EDMI logging and read.

Do you not know the meter address? Scan the device address online

EDMI (Atlas MK10) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus RTU
Default baud rate
9600
Data bits
8
Stop bits
1
Parity
none
Frame format
9600 8N1
Minimum delay between reads
6 seconds
Start address and register count
even numbers greater than zero
Maximum registers per read
62
Invalid read request
meter does not respond
Register addressing
4xxxx (1-based) holding registers

Registers in the map: 31. function 3 (holding registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
1Serial number integer 
3Export wh total ch0 single 
5Import wh total ch1 single 
7Export varh total ch2 single 
9Import varh total ch3 single 
11Va single 
13Vb single 
15Vc single 
17Ia single 
19Ib single 
21Ic single 
23Angle a single 
25Angle b single 
27Angle C single 
29Va ia angle single 
31Va ib angle single 
33Va ic angle single 
35Va va angle single 
37Va vb angle single 
39Va vc angle single 
41Phase AWsingle 
43Phase BWsingle 
45Phase CWsingle 
47Phase A vars single 
49Phase B vars single 
51Phase C vars single 
53Phase AVAsingle 
55Phase BVAsingle 
57Phase CVAsingle 
59Frequency single 
61Power factor single 

EDMI (Atlas MK7) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus RTU
Default baud rate
9600
Data bits
8
Stop bits
1
Parity
none
Frame format
9600 8N1
Minimum delay between reads
6 seconds
Start address and register count
even numbers greater than zero
Maximum registers per read
62
Invalid read request
meter does not respond
Register addressing
4xxxx (1-based) holding registers

Registers in the map: 15. function 3 (holding registers). byte order big-endian. data types: integer, single.

MODBUS offsetDescriptionUnitsData typeScale
1Serial number integer 
3Export wh total ch0 single 
5Import wh total ch1 single 
7Export varh total ch2 single 
9Import varh total ch3 single 
11Va single 
17Ia single 
23Angle a single 
29Va ia angle single 
35Va va angle single 
41Phase AWsingle 
47Phase A vars single 
53Phase AVAsingle 
59Frequency single 
61Power factor single 