Eastron SDM120, SDM220, SDM230 MODBUS registers: read online

Connect Eastron to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Eastron data logger and record.

Do you not know the meter address? Scan the device address online

Eastron (SDM120) - MODBUS Maps

Registers in the map: 10. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0VoltageVsingle 
16CurrentAsingle 
12Active powerWsingle 
18Apparent powerVAsingle 
24Reactive powervarsingle 
30Power factor single 
70FrequencyHzsingle 
72Import active energykWhsingle 
74Export active energykWhsingle 
342Total active energykWhsingle 

Eastron (SDM220) - MODBUS Registers

Registers in the map: 14. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Line to neutralVsingle 
6CurrentAsingle 
12Active powerWsingle 
18Apparent powerVAsingle 
24Reactive powervarsingle 
30Power factor single 
36Phase angledegsingle 
70FrequencyHzsingle 
72Import active energykWhsingle 
74Export active energykWhsingle 
76Import reactive energykvarhsingle 
78Export reactive energykvarhsingle 
342Total active energykWhsingle 
344Total reactive energykvarhsingle 

Eastron (SDM230) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Default baud rate
9600
Stop bits
1
Parity
none
Default device address
1
Baud rate register
40029, 0 = 2400, 1 = 4800, 2 = 9600 (default), 3 = 19200, 4 = 38400
Parity and stop bits register
40019, 0 = no parity with 1 stop bit (default), 1 = even, 2 = odd, 3 = 2 stop bits
Address register
40021, range 1-247
Restart required after change
yes
Function codes
03 read holding, 04 read input, 16 write holding
Register addressing
3X and 4X addresses are 1-based (30001 = offset 0, 40019 = offset 18)

Registers in the map: 22. function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
84Total system power demandWsingle 
86Maximum total system power demandWsingle 
88Current system positive power demandWsingle 
90Maximum system positive power demandWsingle 
92Current system reverse power demandWsingle 
94Maximum system reverse power demandWsingle 
258Current demandAsingle 
0Line to neutralVsingle 
6CurrentAsingle 
12Active powerWsingle 
18Apparent powerVAsingle 
24Reactive powervarsingle 
30Power factor single 
36Phase angledegsingle 
70FrequencyHzsingle 
72Import active energykWhsingle 
74Export active energykWhsingle 
76Import reactive energykvarhsingle 
264Maximum current demandAsingle 
78Export reactive energykvarhsingle 
342Total active energykWhsingle 
344Total reactive energykvarhsingle 

Eastron (SDM320) - MODBUS Measurements

Registers in the map: 240 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single, string.

MODBUS offsetDescriptionUnitsData typeScale
0Line to neutralVsingle 
6CurrentAsingle 
12PowerWsingle 
18Apparent powerVAsingle 
24Reactive powervarsingle 
30Power factor single 
36Phase angledegsingle 
70Frequency of supply voltagesHzsingle 
72Import wh since last resetkWh/MWhsingle 
74Export wh since last resetkWh/MWhsingle 
342TotalkWhsingle 
529Total last 1 month energy, TotalkWhsingle 
533Total last 1 month energy, Rate 1kWhsingle 
537Total last 1 month energy, Rate 2kWhsingle 
545Total last 2 month energy, TotalkWhsingle 
549Total last 2 month energy, Rate 1kWhsingle 
553Total last 2 month energy, Rate 2kWhsingle 
561Total last 3 month energy, TotalkWhsingle 
565Total last 3 month energy, Rate 1kWhsingle 
569Total last 3 month energy, Rate 2kWhsingle 
577Total last 4 month energy, TotalkWhsingle 
581Total last 4 month energy, Rate 1kWhsingle 
585Total last 4 month energy, Rate 2kWhsingle 
593Total last 5 month energy, TotalkWhsingle 
597Total last 5 month energy, Rate 1kWhsingle 
601Total last 5 month energy, Rate 2kWhsingle 
609Total last 6 month energy, TotalkWhsingle 
613Total last 6 month energy, Rate 1kWhsingle 
617Total last 6 month energy, Rate 2kWhsingle 
625Total last 7 month energy, TotalkWhsingle 
629Total last 7 month energy, Rate 1kWhsingle 
633Total last 7 month energy, Rate 2kWhsingle 
641Total last 8 month energy, TotalkWhsingle 
645Total last 8 month energy, Rate 1kWhsingle 
649Total last 8 month energy, Rate 2kWhsingle 
657Total last 9 month energy, TotalkWhsingle 
661Total last 9 month energy, Rate 1kWhsingle 
665Total last 9 month energy, Rate 2kWhsingle 
673Total last 10 month energykWhsingle 
689Total last 11 month energy, TotalkWhsingle 
693Total last 11 month energy, Rate 1kWhsingle 
697Total last 11 month energy, Rate 2kWhsingle 
705Total last 12 month energy, TotalkWhsingle 
709Total last 12 month energy, Rate 1kWhsingle 
713Total last 12 month energy, Rate 2kWhsingle 
2000Import energy rate 1kWhsingle 
2002Import energy rate 2kWhsingle 
2004Import energy rate 3kWhsingle 
2006Import energy rate 4kWhsingle 
2256Export energy rate 1kWhsingle 

This is not the complete map: 50 of 240 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Eastron (SDM630) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Baud rate options
2400, 4800, 9600, 19200, 38400
Function codes
04 read 3X input registers, 03 read and 16 write holding registers
Maximum parameters per transaction
40 (80 registers)
Register count per request
even number

Registers in the map: 87 (the first 52 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: dword, single.

MODBUS offsetDescriptionUnitsData typeScale
22Pulse 1 Divisor single 
64512Serial number dword 
0Phase 1 line to neutralVsingle 
2Phase 2 line to neutralVsingle 
4Phase 3 line to neutralVsingle 
6Phase 1 currentAsingle 
8Phase 2 currentAsingle 
10Phase 3 currentAsingle 
12Phase 1 powerWsingle 
14Phase 2 powerWsingle 
16Phase 3 powerWsingle 
18Phase 1 apparent powerVAsingle 
20Phase 2 apparent powerVAsingle 
24Phase 1 reactive powervarsingle 
26Phase 2 reactive powervarsingle 
28Phase 3 reactive powervarsingle 
30Phase 1 power factor single 
32Phase 2 power factor single 
34Phase 3 power factor single 
36Phase 1 phase angledegsingle 
38Phase 2 phase angledegsingle 
40Phase 3 phase angledegsingle 
42Average line to neutralVsingle 
46Average line currentAsingle 
48Sum of line currentsAsingle 
52Total system powerWsingle 
56Total systemVAsingle 
60Total systemvarsingle 
62Total system power factor single 
66Total system phase angledegsingle 
70Frequency of supply voltagesHzsingle 
72Import wh since last resetkWh/M Whsingle 
74Export wh since last resetkWh/MWhsingle 
76Import varh since last resetkvarh/Mvarhsingle 
78Export varh since last resetkvarh/Mvarhsingle 
80Vah since last resetkVAh/ MVAhsingle 
82Ah since last resetAh/kAhsingle 
84Total system power demandWsingle 
86Maximum total system powerWsingle 
100Total system va demandVAsingle 
102Maximum total system va demandVAsingle 
104Neutral current demandAsingle 
106Maximum neutral current demandAsingle 
200Line 1 to line 2Vsingle 
202Line 2 to line 3Vsingle 
204Line 3 to line 1Vsingle 
206Average line to lineVsingle 
224Neutral currentAsingle 
234Phase 1 l/n volts thd%single 
236Phase 2 l/n volts thd%single 
238Phase 3 l/n volts thd%single 
240Phase 1 current thd%single 

This is not the complete map: 52 of 87 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.