Connect ENTES to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous ENTES logger and poll.
Do you not know the meter address? Scan the device address online
ENTES (MPR2 Series) - MODBUS Maps
Registers in the map: 475 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Voltage L1 N | V | dword | ×0.1 |
| 2 | Voltage L2 N | V | dword | ×0.1 |
| 4 | Voltage L3 N | V | dword | ×0.1 |
| 6 | Voltage L4 N | V | dword | ×0.1 |
| 8 | Voltage L1 L2 | V | dword | ×0.1 |
| 10 | Voltage L2 L3 | V | dword | ×0.1 |
| 12 | Voltage L3 L1 | V | dword | ×0.1 |
| 14 | Current L1 | A | dword | ×0.001 |
| 16 | Current L2 | A | dword | ×0.001 |
| 18 | Current L3 | A | dword | ×0.001 |
| 20 | Current L4 | A | dword | ×0.001 |
| 22 | Neutral current = il1+il2+il3 | A | dword | ×0.001 |
| 24 | Measured frequency | Hz | dword | ×0.01 |
| 26 | Active power L1 N | W | single | |
| 28 | Active power L2 N | W | single | |
| 30 | Active power L3 N | W | single | |
| 32 | Active power L4 N | W | single | |
| 34 | Total import active power | W | single | |
| 36 | Total export active power | W | single | |
| 38 | Active power +/ = P =p1+p2+p3 | W | single | |
| 40 | Reactive power L1 | var | single | |
| 42 | Reactive power L2 | var | single | |
| 44 | Reactive power L3 | var | single | |
| 46 | Reactive power L4 | var | single | |
| 48 | Q1 total reactive power | var | single | |
| 50 | Q2 total reactive power | var | single | |
| 52 | Q3 total reactive power | var | single | |
| 54 | Q4 total reactive power | var | single | |
| 56 | Reactive power +/ = q=Q1+Q2+Q3 | var | single | |
| 58 | Apparent power L1 N | VA | single | |
| 60 | Apparent power L2 N | VA | single | |
| 62 | Apparent power L3 N | VA | single | |
| 64 | Apparent power L4 N | VA | single | |
| 66 | Total import apparent power | VA | single | |
| 68 | Total export apparent power | VA | single | |
| 70 | Apparent power +/ = s=s1+s2+s3 | VA | single | |
| 72 | Power factor L1 | | integer | ×0.001 |
| 74 | Power factor L2 | | integer | ×0.001 |
| 76 | Power factor L3 | | integer | ×0.001 |
| 78 | Power factor L4 | | integer | ×0.001 |
| 80 | Power factor +/ = pf=pfl1+pfl2+pfl3 | | integer | ×0.001 |
| 82 | Cosphi L1 | | integer | ×0.001 |
| 84 | Cosphi L2 | | integer | ×0.001 |
| 86 | Cosphi L3 | | integer | ×0.001 |
| 88 | Cosphi L4 | | integer | ×0.001 |
| 90 | Cos phi = cos_l1 + cos_l2 + cos_l3 | | integer | ×0.001 |
| 92 | Rotation field | | integer | |
| 94 | Voltage unbalance | % | dword | ×0.1 |
| 96 | Current unbalance | % | dword | ×0.1 |
| 98 | L1 phase voltage angle | Angle | dword | ×0.1 |
This is not the complete map: 50 of 475 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
ENTES (MPR3 Series, MPR4 Series) - MODBUS Maps
Registers in the map: 476 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Voltage L1 N | V | dword | ×0.1 |
| 2 | Voltage L2 N | V | dword | ×0.1 |
| 4 | Voltage L3 N | V | dword | ×0.1 |
| 6 | Voltage L4 N | V | dword | ×0.1 |
| 8 | Voltage L1 L2 | V | dword | ×0.1 |
| 10 | Voltage L2 L3 | V | dword | ×0.1 |
| 12 | Voltage L3 L1 | V | dword | ×0.1 |
| 14 | Current L1 | A | dword | ×0.001 |
| 16 | Current L2 | A | dword | ×0.001 |
| 18 | Current L3 | A | dword | ×0.001 |
| 20 | Current L4 | A | dword | ×0.001 |
| 22 | Neutral current = il1+il2+il3 | A | dword | ×0.001 |
| 24 | Measured frequency | Hz | dword | ×0.01 |
| 26 | Active power L1 N | W | single | |
| 28 | Active power L2 N | W | single | |
| 30 | Active power L3 N | W | single | |
| 32 | Active power L4 N | W | single | |
| 34 | Total import active power | W | single | |
| 36 | Total export active power | W | single | |
| 38 | Active power +/ = P =p1+p2+p3 | W | single | |
| 40 | Reactive power L1 | var | single | |
| 42 | Reactive power L2 | var | single | |
| 44 | Reactive power L3 | var | single | |
| 46 | Reactive power L4 | var | single | |
| 48 | Q1 total reactive power | var | single | |
| 50 | Q2 total reactive power | var | single | |
| 52 | Q3 total reactive power | var | single | |
| 54 | Q4 total reactive power | var | single | |
| 56 | Reactive power +/ = q=Q1+Q2+Q3 | var | single | |
| 58 | Apperant power L1 N | VA | single | |
| 60 | Apparent power L2 N | VA | single | |
| 62 | Apparent power L3 N | VA | single | |
| 64 | Apparent power L4 N | VA | single | |
| 66 | Total import apperant power | VA | single | |
| 68 | Total export apperant power | VA | single | |
| 70 | Apperant power +/ = s=s1+s2+s3 | VA | single | |
| 72 | Power factor L1 | | integer | ×0.001 |
| 74 | Power factor L2 | | integer | ×0.001 |
| 76 | Power factor L3 | | integer | ×0.001 |
| 78 | Power factor L4 | | integer | ×0.001 |
| 80 | Power factor +/ = pf=pfl1+pfl2+pfl3 | | integer | ×0.001 |
| 82 | Cosphi L1 | | integer | ×0.001 |
| 84 | Cosphi L2 | | integer | ×0.001 |
| 86 | Cosphi L3 | | integer | ×0.001 |
| 88 | Cosphi L4 | | integer | ×0.001 |
| 90 | Cos phi = cos_l1 + cos_l2 + cos_l3 | | integer | ×0.001 |
| 92 | Rotation field | | integer | |
| 94 | Voltage unbalance | % | dword | ×0.1 |
| 96 | Current unbalance | % | dword | ×0.1 |
| 98 | L1 phase voltage angle | Angle | dword | ×0.1 |
This is not the complete map: 50 of 476 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
ENTES (MPR60) - MODBUS Measurements
Registers in the map: 80 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 16384 | Voltage LN1 | V | dword | ×0.01 |
| 16386 | Voltage LN2 | V | dword | ×0.01 |
| 16388 | Voltage LN3 | V | dword | ×0.01 |
| 16390 | Current LN1 | A | dword | ×0.001 |
| 16392 | Current LN2 | A | dword | ×0.001 |
| 16394 | Current LN3 | A | dword | ×0.001 |
| 16396 | Total current | A | dword | ×0.001 |
| 16398 | Active power L1 | W | integer | ×0.01 |
| 16400 | Active power L2 | W | integer | ×0.01 |
| 16402 | Active power L3 | W | integer | ×0.01 |
| 16404 | Reactive power L1 | var | integer | ×0.01 |
| 16406 | Reactive power L2 | var | integer | ×0.01 |
| 16408 | Reactive power L3 | var | integer | ×0.01 |
| 16410 | Apparent power L1 | VA | dword | ×0.01 |
| 16412 | Apparent power L2 | VA | dword | ×0.01 |
| 16414 | Apparent power L3 | VA | dword | ×0.01 |
| 16416 | Power factor L1 | | integer | ×0.001 |
| 16418 | Power factor L2 | | integer | ×0.001 |
| 16420 | Power factor L3 | | integer | ×0.001 |
| 16422 | Cos L1 | | integer | ×0.001 |
| 16424 | Cos L2 | | integer | ×0.001 |
| 16426 | Cos L3 | | integer | ×0.001 |
| 16428 | Voltage L12 | V | dword | ×0.01 |
| 16430 | Voltage L23 | V | dword | ×0.01 |
| 16432 | Voltage L31 | V | dword | ×0.01 |
| 16434 | Voltage ln | V | dword | ×0.01 |
| 16436 | Voltage ll | V | dword | ×0.01 |
| 16438 | Frequency | Hz | dword | ×0.01 |
| 16440 | Total active power | W | integer | ×0.01 |
| 16442 | Total reactive power | var | integer | ×0.01 |
| 16444 | Total apparent power | VA | dword | ×0.01 |
| 16446 | Thd V1 | % | dword | ×0.1 |
| 16448 | Thd V2 | % | dword | ×0.1 |
| 16450 | Thd V3 | % | dword | ×0.1 |
| 16452 | Thd v3p | % | dword | ×0.1 |
| 16454 | Thd I1 | % | dword | ×0.1 |
| 16456 | Thd I2 | % | dword | ×0.1 |
| 16458 | Thd I3 | % | dword | ×0.1 |
| 16460 | Thd i3p | % | dword | ×0.1 |
| 16462 | Voltage high LN1 | V | dword | ×0.01 |
| 16464 | Voltage high LN2 | V | dword | ×0.01 |
| 16466 | Voltage high LN3 | V | dword | ×0.01 |
| 16468 | Voltage low LN1 | V | dword | ×0.01 |
| 16470 | Voltage low LN2 | V | dword | ×0.01 |
| 16472 | Voltage low LN3 | V | dword | ×0.01 |
| 16474 | Demand current high L1 | A | dword | ×0.001 |
| 16476 | Demand current high L2 | A | dword | ×0.001 |
| 16478 | Demand current high L3 | A | dword | ×0.001 |
| 16480 | Demand current low L1 | A | dword | ×0.001 |
| 16482 | Demand current low L2 | A | dword | ×0.001 |
This is not the complete map: 50 of 80 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
ENTES (MPR63) - MODBUS Measurements
Registers in the map: 80 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 16384 | Voltage LN1 | V | dword | ×0.01 |
| 16386 | Voltage LN2 | V | dword | ×0.01 |
| 16388 | Voltage LN3 | V | dword | ×0.01 |
| 16390 | Current LN1 | A | dword | ×0.001 |
| 16392 | Current LN2 | A | dword | ×0.001 |
| 16394 | Current LN3 | A | dword | ×0.001 |
| 16396 | Total current | A | dword | ×0.001 |
| 16398 | Active power L1 | W | integer | ×0.01 |
| 16400 | Active power L2 | W | integer | ×0.01 |
| 16402 | Active power L3 | W | integer | ×0.01 |
| 16404 | Reactive power L1 | var | integer | ×0.01 |
| 16406 | Reactive power L2 | var | integer | ×0.01 |
| 16408 | Reactive power L3 | var | integer | ×0.01 |
| 16410 | Apparent power L1 | VA | dword | ×0.01 |
| 16412 | Apparent power L2 | VA | dword | ×0.01 |
| 16414 | Apparent power L3 | VA | dword | ×0.01 |
| 16416 | Power factor L1 | | integer | ×0.001 |
| 16418 | Power factor L2 | | integer | ×0.001 |
| 16420 | Power factor L3 | | integer | ×0.001 |
| 16422 | Cos L1 | | integer | ×0.001 |
| 16424 | Cos L2 | | integer | ×0.001 |
| 16426 | Cos L3 | | integer | ×0.001 |
| 16428 | Voltage L12 | V | dword | ×0.01 |
| 16430 | Voltage L23 | V | dword | ×0.01 |
| 16432 | Voltage L31 | V | dword | ×0.01 |
| 16434 | Voltage ln | V | dword | ×0.01 |
| 16436 | Voltage ll | V | dword | ×0.01 |
| 16438 | Frequency | Hz | dword | ×0.01 |
| 16440 | Total active power | W | integer | ×0.01 |
| 16442 | Total reactive power | var | integer | ×0.01 |
| 16444 | Total apparent power | VA | dword | ×0.01 |
| 16446 | Thd V1 | % | dword | ×0.1 |
| 16448 | Thd V2 | % | dword | ×0.1 |
| 16450 | Thd V3 | % | dword | ×0.1 |
| 16452 | Thd v3p | % | dword | ×0.1 |
| 16454 | Thd I1 | % | dword | ×0.1 |
| 16456 | Thd I2 | % | dword | ×0.1 |
| 16458 | Thd I3 | % | dword | ×0.1 |
| 16460 | Thd i3p | % | dword | ×0.1 |
| 16462 | Voltage high LN1 | V | dword | ×0.01 |
| 16464 | Voltage high LN2 | V | dword | ×0.01 |
| 16466 | Voltage high LN3 | V | dword | ×0.01 |
| 16468 | Voltage low LN1 | V | dword | ×0.01 |
| 16470 | Voltage low LN2 | V | dword | ×0.01 |
| 16472 | Voltage low LN3 | V | dword | ×0.01 |
| 16474 | Demand current high L1 | A | dword | ×0.001 |
| 16476 | Demand current high L2 | A | dword | ×0.001 |
| 16478 | Demand current high L3 | A | dword | ×0.001 |
| 16480 | Demand current low L1 | A | dword | ×0.001 |
| 16482 | Demand current low L2 | A | dword | ×0.001 |
This is not the complete map: 50 of 80 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
ENTES (MPR7 Series) - MODBUS Registers Map
Connection and addressing notes
- Communication settings
- holding registers
- Address register
- 32777 (0x8009), range 0-247
- Baud rate register
- 32778 (0x800A), 1 = 38400, 2 = 19200, 3 = 9600, 4 = 4800, 5 = 2400
- Parity register
- 32779 (0x800B), 0 = none, 1 = odd, 2 = even
- Password enable register
- 32780 (0x800C), 0 = disable, 1 = enable
- Password register
- 32781 (0x800D), range 0-9999
Registers in the map: 107 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | L1 phase voltage | V | dword | ×0.1 |
| 2 | L2 phase voltage | V | dword | ×0.1 |
| 4 | L3 phase voltage | V | dword | ×0.1 |
| 6 | L1 phase current | A | dword | ×0.001 |
| 8 | L2 phase current | A | dword | ×0.001 |
| 10 | L3 phase current | A | dword | ×0.001 |
| 12 | Neutral current | A | dword | ×0.001 |
| 14 | L1 L2 phase phase voltage | V | dword | ×0.1 |
| 16 | L2 L3 phase phase voltage | V | dword | ×0.1 |
| 18 | L3 L1 phase phase voltage | V | dword | ×0.1 |
| 20 | L1 phase active power | W | integer | ×0.1 |
| 22 | L2 phase active power | W | integer | ×0.1 |
| 24 | L3 phase active power | W | integer | ×0.1 |
| 26 | L1 phase reactive power | var | integer | ×0.1 |
| 28 | L2 phase reactive power | var | integer | ×0.1 |
| 30 | L3 phase reactive power | var | integer | ×0.1 |
| 32 | L1 phase apparent power | VA | dword | ×0.1 |
| 34 | L2 phase apparent power | VA | dword | ×0.1 |
| 36 | L3 phase apparent power | VA | dword | ×0.1 |
| 38 | L1 phase cos | | integer | ×0.001 |
| 40 | L2 phase cos | | integer | ×0.001 |
| 42 | L3 phase cos | | integer | ×0.001 |
| 44 | Total import active power | W | integer | ×0.1 |
| 46 | Total export active power | W | integer | ×0.1 |
| 48 | Total inductive reactive power | var | integer | ×0.1 |
| 50 | Total capacitive reactive power | var | integer | ×0.1 |
| 52 | Total apparent power | VA | dword | ×0.1 |
| 54 | Average inductive cos | | integer | ×0.001 |
| 56 | Average capacitive cos | | integer | ×0.001 |
| 58 | Frequency | Hz | dword | ×0.01 |
| 88 | Import active energy 1 | Wh | dword | |
| 92 | Export active energy 1 | Wh | dword | |
| 96 | Inductive reactive energy 1 | varh | dword | |
| 100 | Capacitive reactive energy 1 | varh | dword | |
| 104 | Import active energy 2 | Wh | dword | |
| 108 | Export active energy 2 | Wh | dword | |
| 112 | Inductive reactive energy 2 | varh | dword | |
| 116 | Capacitive reactive energy 2 | varh | dword | |
| 118 | L1 phase min. voltage | V | dword | ×0.1 |
| 120 | L2 phase min. voltage | V | dword | ×0.1 |
| 122 | L3 phase min. voltage | V | dword | ×0.1 |
| 124 | L1 L2 phase phase min. voltage | V | dword | ×0.1 |
| 126 | L2 L3 phase phase min. voltage | V | dword | ×0.1 |
| 128 | L3 L1 phase phase min. voltage | V | dword | ×0.1 |
| 130 | L1 phase min. current | A | dword | ×0.001 |
| 132 | L2 phase min. current | A | dword | ×0.001 |
| 134 | L3 phase min. current | A | dword | ×0.001 |
| 136 | L1 phase min. active power | W | integer | ×0.1 |
| 138 | L2 phase min. active power | W | integer | ×0.1 |
| 140 | L3 phase min. active power | W | integer | ×0.1 |
This is not the complete map: 50 of 107 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Related MODBUS registers maps
MODBUS Maps Index
ENTES (MPR1 Series)
EDMI (Atlas MK7)
Earu (DDS661)
Eastron (SDM120)
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.