bg

ENTES - MODBUS Registers Map - Data Logging

The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable ENTES data logging and log.

Do you not know the meter address? Scan the device address online

ENTES (MPR2 Series) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
0
Voltage L1 N
V/10
dword
2
Voltage L2 N
V/10
dword
4
Voltage L3 N
V/10
dword
6
Voltage L4 N
V/10
dword
8
Voltage L1 L2
V/10
dword
10
Voltage L2 L3
V/10
dword
12
Voltage L3 L1
V/10
dword
14
Current L1
mA
dword
16
Current L2
mA
dword
18
Current L3
mA
dword
20
Current L4
mA
dword
22
Neutral current = il1+il2+il3
mA
dword
24
Measured frequency
Hz / 100
dword
26
Active power L1 N
W
single
28
Active power L2 N
W
single
30
Active power L3 N
W
single
32
Active power L4 N
W
single
34
Total import active power
W
single
36
Total export active power
W
single
38
Active power +/ = P =p1+p2+p3
W
single
40
Reactive power L1
var
single
42
Reactive power L2
var
single
44
Reactive power L3
var
single
46
Reactive power L4
var
single
48
Quadrant 1 total reactive power
var
single
50
Quadrant 2 total reactive power
var
single
52
Quadrant 3 total reactive power
var
single
54
Quadrant 4 total reactive power
var
single
56
Reactive power +/ = q=q1+q2+q3
var
single
58
Apparent power L1 N
VA
single
60
Apparent power L2 N
VA
single
62
Apparent power L3 N
VA
single
64
Apparent power L4 N
VA
single
66
Total import apparent power
VA
single
68
Total export apparent power
VA
single
70
Apparent power +/ = s=s1+s2+s3
VA
single
72
Power factor L1
 
integer
74
Power factor L2
 
integer
76
Power factor L3
 
integer
78
Power factor L4
 
integer
80
Power factor +/ = pf=pfl1+pfl2+pfl3
 
integer
82
Cosphi L1
 
integer
84
Cosphi L2
 
integer
86
Cosphi L3
 
integer
88
Cosphi L4
 
integer
90
Cos phi = cos_l1 + cos_l2 + cos_l3
 
integer
92
Rotation field
 
integer
94
Voltage unbalance
%
dword
96
Current unbalance
%
dword
98
L1 phase voltage angle
Angle
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (MPR3 Series, MPR4 Series) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
0
Voltage L1 N
V/10
dword
2
Voltage L2 N
V/10
dword
4
Voltage L3 N
V/10
dword
6
Voltage L4 N
V/10
dword
8
Voltage L1 L2
V/10
dword
10
Voltage L2 L3
V/10
dword
12
Voltage L3 L1
V/10
dword
14
Current L1
mA
dword
16
Current L2
mA
dword
18
Current L3
mA
dword
20
Current L4
mA
dword
22
Neutral current = il1+il2+il3
mA
dword
24
Measured frequency
Hz / 100
dword
26
Active power L1 N
W
single
28
Active power L2 N
W
single
30
Active power L3 N
W
single
32
Active power L4 N
W
single
34
Total import active power
W
single
36
Total export active power
W
single
38
Active power +/ = P =p1+p2+p3
W
single
40
Reactive power L1
var
single
42
Reactive power L2
var
single
44
Reactive power L3
var
single
46
Reactive power L4
var
single
48
Quadrant 1 total reactive power
var
single
50
Quadrant 2 total reactive power
var
single
52
Quadrant 3 total reactive power
var
single
54
Quadrant 4 total reactive power
var
single
56
Reactive power +/ = q=q1+q2+q3
var
single
58
Apperant power L1 N
VA
single
60
Apparent power L2 N
VA
single
62
Apparent power L3 N
VA
single
64
Apparent power L4 N
VA
single
66
Total import apperant power
VA
single
68
Total export apperant power
VA
single
70
Apperant power +/ = s=s1+s2+s3
VA
single
72
Power factor L1
 
integer
74
Power factor L2
 
integer
76
Power factor L3
 
integer
78
Power factor L4
 
integer
80
Power factor +/ = pf=pfl1+pfl2+pfl3
 
integer
82
Cosphi L1
 
integer
84
Cosphi L2
 
integer
86
Cosphi L3
 
integer
88
Cosphi L4
 
integer
90
Cos phi = cos_l1 + cos_l2 + cos_l3
 
integer
92
Rotation field
 
integer
94
Voltage unbalance
%
dword
96
Current unbalance
%
dword
98
L1 phase voltage angle
Angle
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (MPR60) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
16384
Voltage LN1
V
dword
16386
Voltage LN2
V
dword
16388
Voltage LN3
V
dword
16390
Current LN1
A
dword
16392
Current LN2
A
dword
16394
Current LN3
A
dword
16396
Total current
A
dword
16398
Active power L1
W
integer
16400
Active power L2
W
integer
16402
Active power L3
W
integer
16404
Reactive power L1
VAr
integer
16406
Reactive power L2
VAr
integer
16408
Reactive power L3
VAr
integer
16410
Apparent power L1
VA
dword
16412
Apparent power L2
VA
dword
16414
Apparent power L3
VA
dword
16416
Power factor L1
 
integer
16418
Power factor L2
 
integer
16420
Power factor L3
 
integer
16422
Cos L1
 
integer
16424
Cos L2
 
integer
16426
Cos L3
 
integer
16428
Voltage L12
V
dword
16430
Voltage L23
V
dword
16432
Voltage L31
V
dword
16434
Voltage ln
V
dword
16436
Voltage ll
V
dword
16438
Frequency
Hz
dword
16440
Total active power
W
integer
16442
Total reactive power
VAr
integer
16444
Total apparent power
VA
dword
16446
Thd V1
%
dword
16448
Thd V2
%
dword
16450
Thd V3
%
dword
16452
Thd v3p
%
dword
16454
Thd I1
%
dword
16456
Thd I2
%
dword
16458
Thd I3
%
dword
16460
Thd i3p
%
dword
16462
Voltage high LN1
V
dword
16464
Voltage high LN2
V
dword
16466
Voltage high LN3
V
dword
16468
Voltage low LN1
V
dword
16470
Voltage low LN2
V
dword
16472
Voltage low LN3
V
dword
16474
Demand current high L1
A
dword
16476
Demand current high L2
A
dword
16478
Demand current high L3
A
dword
16480
Demand current low L1
A
dword
16482
Demand current low L2
A
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (MPR63) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
16384
Voltage LN1
V
dword
16386
Voltage LN2
V
dword
16388
Voltage LN3
V
dword
16390
Current LN1
A
dword
16392
Current LN2
A
dword
16394
Current LN3
A
dword
16396
Total current
A
dword
16398
Active power L1
W
integer
16400
Active power L2
W
integer
16402
Active power L3
W
integer
16404
Reactive power L1
VAr
integer
16406
Reactive power L2
VAr
integer
16408
Reactive power L3
VAr
integer
16410
Apparent power L1
VA
dword
16412
Apparent power L2
VA
dword
16414
Apparent power L3
VA
dword
16416
Power factor L1
 
integer
16418
Power factor L2
 
integer
16420
Power factor L3
 
integer
16422
Cos L1
 
integer
16424
Cos L2
 
integer
16426
Cos L3
 
integer
16428
Voltage L12
V
dword
16430
Voltage L23
V
dword
16432
Voltage L31
V
dword
16434
Voltage ln
V
dword
16436
Voltage ll
V
dword
16438
Frequency
Hz
dword
16440
Total active power
W
integer
16442
Total reactive power
VAr
integer
16444
Total apparent power
VA
dword
16446
Thd V1
%
dword
16448
Thd V2
%
dword
16450
Thd V3
%
dword
16452
Thd v3p
%
dword
16454
Thd I1
%
dword
16456
Thd I2
%
dword
16458
Thd I3
%
dword
16460
Thd i3p
%
dword
16462
Voltage high LN1
V
dword
16464
Voltage high LN2
V
dword
16466
Voltage high LN3
V
dword
16468
Voltage low LN1
V
dword
16470
Voltage low LN2
V
dword
16472
Voltage low LN3
V
dword
16474
Demand current high L1
A
dword
16476
Demand current high L2
A
dword
16478
Demand current high L3
A
dword
16480
Demand current low L1
A
dword
16482
Demand current low L2
A
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (MPR7 Series) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
0
L1 phase voltage
Vot
dword
2
L2 phase voltage
Vot
dword
4
L3 phase voltage
Vot
dword
6
L1 phase current
Amper
dword
8
L2 phase current
Amper
dword
10
L3 phase current
Amper
dword
12
Neutral current
Amper
dword
14
L1 L2 phase phase voltage
Vot
dword
16
L2 L3 phase phase voltage
Vot
dword
18
L3 L1 phase phase voltage
Vot
dword
20
L1 phase active power
Watt
integer
22
L2 phase active power
Watt
integer
24
L3 phase active power
Watt
integer
26
L1 phase reactive power
Var
integer
28
L2 phase reactive power
Var
integer
30
L3 phase reactive power
Var
integer
32
L1 phase apparent power
VA
dword
34
L2 phase apparent power
VA
dword
36
L3 phase apparent power
VA
dword
38
L1 phase cos
 
integer
40
L2 phase cos
 
integer
42
L3 phase cos
 
integer
44
Total import active power
Watt
integer
46
Total export active power
Watt
integer
48
Total inductive reactive power
Var
integer
50
Total capacitive reactive power
Var
integer
52
Total apparent power
VA
dword
54
Average inductive cos
 
integer
56
Average capacitive cos
 
integer
58
Frequency
Hz
dword
88
Import active energy 1
Wh
dword
92
Export active energy 1
Wh
dword
96
Inductive reactive energy 1
VArh
dword
100
Capacitive reactive energy 1
VArh
dword
104
Import active energy 2
Wh
dword
108
Export active energy 2
Wh
dword
112
Inductive reactive energy 2
VArh
dword
116
Capacitive reactive energy 2
VArh
dword
118
L1 phase min. voltage
Vot
dword
120
L2 phase min. voltage
Vot
dword
122
L3 phase min. voltage
Vot
dword
124
L1 L2 phase phase min. voltage
Vot
dword
126
L2 L3 phase phase min. voltage
Vot
dword
128
L3 L1 phase phase min. voltage
Vot
dword
130
L1 phase min. current
Amper
dword
132
L2 phase min. current
Amper
dword
134
L3 phase min. current
Amper
dword
136
L1 phase min. active power
Watt
integer
138
L2 phase min. active power
Watt
integer
140
L3 phase min. active power
Watt
integer
There are more MODBUS items for this device. Please download the program to discover all registers.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection