bg

ENTES MPR2 Series, MPR3 Series MODBUS registers: read online

Connect ENTES to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous ENTES logger and poll.

Do you not know the meter address? Scan the device address online

ENTES (MPR2 Series) - MODBUS Maps

Registers in the map: 475 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage L1 NVdword×0.1
2Voltage L2 NVdword×0.1
4Voltage L3 NVdword×0.1
6Voltage L4 NVdword×0.1
8Voltage L1 L2Vdword×0.1
10Voltage L2 L3Vdword×0.1
12Voltage L3 L1Vdword×0.1
14Current L1Adword×0.001
16Current L2Adword×0.001
18Current L3Adword×0.001
20Current L4Adword×0.001
22Neutral current = il1+il2+il3Adword×0.001
24Measured frequencyHzdword×0.01
26Active power L1 NWsingle 
28Active power L2 NWsingle 
30Active power L3 NWsingle 
32Active power L4 NWsingle 
34Total import active powerWsingle 
36Total export active powerWsingle 
38Active power +/ = P =p1+p2+p3Wsingle 
40Reactive power L1varsingle 
42Reactive power L2varsingle 
44Reactive power L3varsingle 
46Reactive power L4varsingle 
48Q1 total reactive powervarsingle 
50Q2 total reactive powervarsingle 
52Q3 total reactive powervarsingle 
54Q4 total reactive powervarsingle 
56Reactive power +/ = q=Q1+Q2+Q3varsingle 
58Apparent power L1 NVAsingle 
60Apparent power L2 NVAsingle 
62Apparent power L3 NVAsingle 
64Apparent power L4 NVAsingle 
66Total import apparent powerVAsingle 
68Total export apparent powerVAsingle 
70Apparent power +/ = s=s1+s2+s3VAsingle 
72Power factor L1 integer×0.001
74Power factor L2 integer×0.001
76Power factor L3 integer×0.001
78Power factor L4 integer×0.001
80Power factor +/ = pf=pfl1+pfl2+pfl3 integer×0.001
82Cosphi L1 integer×0.001
84Cosphi L2 integer×0.001
86Cosphi L3 integer×0.001
88Cosphi L4 integer×0.001
90Cos phi = cos_l1 + cos_l2 + cos_l3 integer×0.001
92Rotation field integer 
94Voltage unbalance%dword×0.1
96Current unbalance%dword×0.1
98L1 phase voltage angleAngledword×0.1

This is not the complete map: 50 of 475 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

ENTES (MPR3 Series, MPR4 Series) - MODBUS Maps

Registers in the map: 476 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Voltage L1 NVdword×0.1
2Voltage L2 NVdword×0.1
4Voltage L3 NVdword×0.1
6Voltage L4 NVdword×0.1
8Voltage L1 L2Vdword×0.1
10Voltage L2 L3Vdword×0.1
12Voltage L3 L1Vdword×0.1
14Current L1Adword×0.001
16Current L2Adword×0.001
18Current L3Adword×0.001
20Current L4Adword×0.001
22Neutral current = il1+il2+il3Adword×0.001
24Measured frequencyHzdword×0.01
26Active power L1 NWsingle 
28Active power L2 NWsingle 
30Active power L3 NWsingle 
32Active power L4 NWsingle 
34Total import active powerWsingle 
36Total export active powerWsingle 
38Active power +/ = P =p1+p2+p3Wsingle 
40Reactive power L1varsingle 
42Reactive power L2varsingle 
44Reactive power L3varsingle 
46Reactive power L4varsingle 
48Q1 total reactive powervarsingle 
50Q2 total reactive powervarsingle 
52Q3 total reactive powervarsingle 
54Q4 total reactive powervarsingle 
56Reactive power +/ = q=Q1+Q2+Q3varsingle 
58Apperant power L1 NVAsingle 
60Apparent power L2 NVAsingle 
62Apparent power L3 NVAsingle 
64Apparent power L4 NVAsingle 
66Total import apperant powerVAsingle 
68Total export apperant powerVAsingle 
70Apperant power +/ = s=s1+s2+s3VAsingle 
72Power factor L1 integer×0.001
74Power factor L2 integer×0.001
76Power factor L3 integer×0.001
78Power factor L4 integer×0.001
80Power factor +/ = pf=pfl1+pfl2+pfl3 integer×0.001
82Cosphi L1 integer×0.001
84Cosphi L2 integer×0.001
86Cosphi L3 integer×0.001
88Cosphi L4 integer×0.001
90Cos phi = cos_l1 + cos_l2 + cos_l3 integer×0.001
92Rotation field integer 
94Voltage unbalance%dword×0.1
96Current unbalance%dword×0.1
98L1 phase voltage angleAngledword×0.1

This is not the complete map: 50 of 476 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

ENTES (MPR60) - MODBUS Measurements

Registers in the map: 80 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
16384Voltage LN1Vdword×0.01
16386Voltage LN2Vdword×0.01
16388Voltage LN3Vdword×0.01
16390Current LN1Adword×0.001
16392Current LN2Adword×0.001
16394Current LN3Adword×0.001
16396Total currentAdword×0.001
16398Active power L1Winteger×0.01
16400Active power L2Winteger×0.01
16402Active power L3Winteger×0.01
16404Reactive power L1varinteger×0.01
16406Reactive power L2varinteger×0.01
16408Reactive power L3varinteger×0.01
16410Apparent power L1VAdword×0.01
16412Apparent power L2VAdword×0.01
16414Apparent power L3VAdword×0.01
16416Power factor L1 integer×0.001
16418Power factor L2 integer×0.001
16420Power factor L3 integer×0.001
16422Cos L1 integer×0.001
16424Cos L2 integer×0.001
16426Cos L3 integer×0.001
16428Voltage L12Vdword×0.01
16430Voltage L23Vdword×0.01
16432Voltage L31Vdword×0.01
16434Voltage lnVdword×0.01
16436Voltage llVdword×0.01
16438FrequencyHzdword×0.01
16440Total active powerWinteger×0.01
16442Total reactive powervarinteger×0.01
16444Total apparent powerVAdword×0.01
16446Thd V1%dword×0.1
16448Thd V2%dword×0.1
16450Thd V3%dword×0.1
16452Thd v3p%dword×0.1
16454Thd I1%dword×0.1
16456Thd I2%dword×0.1
16458Thd I3%dword×0.1
16460Thd i3p%dword×0.1
16462Voltage high LN1Vdword×0.01
16464Voltage high LN2Vdword×0.01
16466Voltage high LN3Vdword×0.01
16468Voltage low LN1Vdword×0.01
16470Voltage low LN2Vdword×0.01
16472Voltage low LN3Vdword×0.01
16474Demand current high L1Adword×0.001
16476Demand current high L2Adword×0.001
16478Demand current high L3Adword×0.001
16480Demand current low L1Adword×0.001
16482Demand current low L2Adword×0.001

This is not the complete map: 50 of 80 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

ENTES (MPR63) - MODBUS Measurements

Registers in the map: 80 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
16384Voltage LN1Vdword×0.01
16386Voltage LN2Vdword×0.01
16388Voltage LN3Vdword×0.01
16390Current LN1Adword×0.001
16392Current LN2Adword×0.001
16394Current LN3Adword×0.001
16396Total currentAdword×0.001
16398Active power L1Winteger×0.01
16400Active power L2Winteger×0.01
16402Active power L3Winteger×0.01
16404Reactive power L1varinteger×0.01
16406Reactive power L2varinteger×0.01
16408Reactive power L3varinteger×0.01
16410Apparent power L1VAdword×0.01
16412Apparent power L2VAdword×0.01
16414Apparent power L3VAdword×0.01
16416Power factor L1 integer×0.001
16418Power factor L2 integer×0.001
16420Power factor L3 integer×0.001
16422Cos L1 integer×0.001
16424Cos L2 integer×0.001
16426Cos L3 integer×0.001
16428Voltage L12Vdword×0.01
16430Voltage L23Vdword×0.01
16432Voltage L31Vdword×0.01
16434Voltage lnVdword×0.01
16436Voltage llVdword×0.01
16438FrequencyHzdword×0.01
16440Total active powerWinteger×0.01
16442Total reactive powervarinteger×0.01
16444Total apparent powerVAdword×0.01
16446Thd V1%dword×0.1
16448Thd V2%dword×0.1
16450Thd V3%dword×0.1
16452Thd v3p%dword×0.1
16454Thd I1%dword×0.1
16456Thd I2%dword×0.1
16458Thd I3%dword×0.1
16460Thd i3p%dword×0.1
16462Voltage high LN1Vdword×0.01
16464Voltage high LN2Vdword×0.01
16466Voltage high LN3Vdword×0.01
16468Voltage low LN1Vdword×0.01
16470Voltage low LN2Vdword×0.01
16472Voltage low LN3Vdword×0.01
16474Demand current high L1Adword×0.001
16476Demand current high L2Adword×0.001
16478Demand current high L3Adword×0.001
16480Demand current low L1Adword×0.001
16482Demand current low L2Adword×0.001

This is not the complete map: 50 of 80 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

ENTES (MPR7 Series) - MODBUS Registers Map

Connection and addressing notes

Communication settings
holding registers
Address register
32777 (0x8009), range 0-247
Baud rate register
32778 (0x800A), 1 = 38400, 2 = 19200, 3 = 9600, 4 = 4800, 5 = 2400
Parity register
32779 (0x800B), 0 = none, 1 = odd, 2 = even
Password enable register
32780 (0x800C), 0 = disable, 1 = enable
Password register
32781 (0x800D), range 0-9999

Registers in the map: 107 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
0L1 phase voltageVdword×0.1
2L2 phase voltageVdword×0.1
4L3 phase voltageVdword×0.1
6L1 phase currentAdword×0.001
8L2 phase currentAdword×0.001
10L3 phase currentAdword×0.001
12Neutral currentAdword×0.001
14L1 L2 phase phase voltageVdword×0.1
16L2 L3 phase phase voltageVdword×0.1
18L3 L1 phase phase voltageVdword×0.1
20L1 phase active powerWinteger×0.1
22L2 phase active powerWinteger×0.1
24L3 phase active powerWinteger×0.1
26L1 phase reactive powervarinteger×0.1
28L2 phase reactive powervarinteger×0.1
30L3 phase reactive powervarinteger×0.1
32L1 phase apparent powerVAdword×0.1
34L2 phase apparent powerVAdword×0.1
36L3 phase apparent powerVAdword×0.1
38L1 phase cos integer×0.001
40L2 phase cos integer×0.001
42L3 phase cos integer×0.001
44Total import active powerWinteger×0.1
46Total export active powerWinteger×0.1
48Total inductive reactive powervarinteger×0.1
50Total capacitive reactive powervarinteger×0.1
52Total apparent powerVAdword×0.1
54Average inductive cos integer×0.001
56Average capacitive cos integer×0.001
58FrequencyHzdword×0.01
88Import active energy 1Whdword 
92Export active energy 1Whdword 
96Inductive reactive energy 1varhdword 
100Capacitive reactive energy 1varhdword 
104Import active energy 2Whdword 
108Export active energy 2Whdword 
112Inductive reactive energy 2varhdword 
116Capacitive reactive energy 2varhdword 
118L1 phase min. voltageVdword×0.1
120L2 phase min. voltageVdword×0.1
122L3 phase min. voltageVdword×0.1
124L1 L2 phase phase min. voltageVdword×0.1
126L2 L3 phase phase min. voltageVdword×0.1
128L3 L1 phase phase min. voltageVdword×0.1
130L1 phase min. currentAdword×0.001
132L2 phase min. currentAdword×0.001
134L3 phase min. currentAdword×0.001
136L1 phase min. active powerWinteger×0.1
138L2 phase min. active powerWinteger×0.1
140L3 phase min. active powerWinteger×0.1

This is not the complete map: 50 of 107 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection