Eaton (IQ100 series,IQ130,IQ140,IQ150) logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
16 | Meter type | bit-mapped | word |
17 | Firmware version | | string(4) |
19 | Map version | 0 to 65535 | word |
20 | Meter configuration | bit-mapped | word |
21 | Asic version | 0-65535 | word |
899 | Watts, 3 ph total | Watt | single |
901 | Vars, 3 ph total | VARs | single |
903 | Vas, 3 ph total | VAs | single |
999 | Voits A N | voIts | single |
1001 | Voits B N | volts | single |
1003 | Voits C N | voIts | single |
1005 | Voits A B | volts | single |
1007 | Voits B C | volts | single |
1009 | Voits C A | volts | single |
1011 | Amps A | amps | single |
1013 | Amps B | amps | single |
1015 | Amps C | amps | single |
1017 | Watts, 3 ph total | watts | single |
1019 | Vars, 3 ph total | VARs | single |
1021 | Vas, 3 ph total | VAs | single |
1025 | Frequency | Hz | single |
1027 | Neutral current | amps | single |
1099 | W hours, received | Wh | integer |
1101 | W hours, delivered | Wh | integer |
1103 | W hours, net | Wh | integer |
1105 | W hours, total | Wh | integer |
1107 | Var hours, positive | VARh | integer |
1109 | Var hours, negative | VARh | integer |
1111 | Var hours, net | VARh | integer |
1113 | Var hours, total | VARh | integer |
1115 | Va hours, total | 0 to 99999999 | integer |
1999 | Amps a, average | amps | single |
2001 | Amps b, average | amps | single |
2003 | Amps c, average | amps | single |
2005 | Positive watts, 3 ph, average | watts | single |
2007 | Positive vars, 3 ph, average | VARs | single |
2009 | Negative watts, 3 ph, average | watts | single |
2011 | Negative vars, 3 ph, average | VARs | single |
2013 | Vas, 3 ph, average | -9999 M to +9999 M | single |
2015 | Positive pf, 3 ph, average | -1.00 to +1.00 | single |
2017 | Negative pf, 3 pf, average | -1.00 to +1.00 | single |
3001 | Volts B n, minimum | Volt | single |
3129 | Negative power factor, 3 ph, maximum avg demand | -1.00 to +1.00 | single |
4099 | Phase A current | -1800 to +1800 | smallint |
4100 | Phase B current | -1800 to +1800 | smallint |
4101 | Phase C current | -1800 to +1800 | smallint |
4102 | Angle, volts A B | -1800 to +1800 | smallint |
4103 | Angle, volts B C | -1800 to +1800 | smallint |
4104 | Angle, volts C A | -1800 to +1800 | smallint |
4999 | Meter status | bit-mapped | word |
There are more MODBUS items for this device. Please, download the program. |