bg

ENTES - MODBUS Registers Map - Log & Capture

The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable ENTES logger and read.

Do you not know the meter address? Scan the device address online

ENTES (EMM) - Data

MODBUS offset
Description
Units
Data type
0
Voltage L1-N
V
single
2
Voltage L2-N
V
single
4
Voltage L3-N
V
single
8
Voltage L1-L2
V
single
10
Voltage L2-L3
V
single
12
Voltage L3-L1
V
single
14
Current L1
mA
single
16
Current L2
mA
single
18
Current L3
mA
single
22
Neutral current = IL1+IL2+IL3
mA
single
24
Measured frequency
Hz
single
26
Active power L1-N
W
single
28
Active power L2-N
W
single
30
Active power L3-N
W
single
34
Total import active power
W
single
36
Total export active power
W
single
38
Total active power
W
single
40
Reactive power L1
VAr
single
42
Reactive power L2
VAr
single
44
Reactive power L3
VAr
single
48
Quadrant 1 total reactive power
VAr
single
50
Quadrant 2 total reactive power
VAr
single
52
Quadrant 3 total reactive power
VAr
single
54
Quadrant 4 total reactive power
VAr
single
56
Total reactive power
VAr
single
58
Apperant power L1-N
VAr
single
60
Apparent power L2-N
VAr
single
62
Apparent power L3-N
VAr
single
66
Total import apperant power
VA
single
68
Total export apperant power
VA
single
70
Total apperant power
VA
single
72
Power factor L1
 
single
74
Power factor L2
 
single
76
Power factor L3
 
single
80
Power factor total import
 
single
82
Power factor total export
 
single
84
Power factor total
 
single
86
CosPhi L1
 
single
88
CosPhi L2
 
single
90
CosPhi L3
 
single
98
Cos phi = COS_L1 + COS_L2 + COS_L3
 
single
100
Rotation field
 
single
102
Voltage unbalance
%
single
106
L1 phase voltage angle
Angle
single
108
L2 phase voltage angle
Angle
single
110
L3 phase voltage angle
Angle
single
114
L1 phase current angle
Angle
single
116
L2 phase current angle
Angle
single
118
L3 phase current angle
Angle
single
128
Internal temp
DC
single
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (EPM-07) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
152
L3 phase min. Apparent power
VA
word
154
Total min. Import active power
Watt
integer
156
Total min. Export active power
Watt
integer
158
Total min. Import reactive power
Var
integer
160
Total min. Export reactive power
Var
integer
162
Total min. Apparent power
VA
word
164
L1 phase max. Voltage
Volt
word
166
L2 phase max. Voltage
Volt
word
168
L3 phase max. Voltage
Volt
word
170
L1 L2 phase phase max. Voltage
Volt
word
172
L2 L3 phase phase max. Voltage
Volt
word
174
L3 L1 phase phase max. Voltage
Volt
word
176
L1 phase max. Current
Amper
word
178
L2 phase max. Current
Amper
word
180
L3 phase max. Current
Amper
word
182
L1 phase max. Active power
Watt
integer
184
L2 phase max. Active power
Watt
integer
186
L3 phase max. Active power
Watt
integer
188
L1 phase max. Reactive power
Var
integer
190
L2 phase max. Reactive power
Var
integer
192
L3 phase max. Reactive power
Var
integer
194
L1 phase max. Apparent power
VA
word
196
L2 phase max. Apparent power
VA
word
198
L3 phase max. Apparent power
VA
word
200
Total max. Import active power
Watt
integer
202
Total max. Export active power
Watt
integer
204
Total max. Import reactive power
Var
integer
206
Total max. Export reactive power
Var
integer
208
Total max. Apparent power
VA
word
210
L1 phase max. Current demand
Amper
word
212
L2 phase max. Current demand
Amper
word
214
L3 phase max. Current demand
Amper
word
216
L1 phase import max. Demand active power
Watt
integer
218
L1 phase export max. Demand active power
Watt
integer
220
L2 phase import max. Demand active power
Watt
integer
222
L2 phase export max. Demand active power
Watt
integer
224
L3 phase import max. Demand active power
Watt
integer
226
L3 phase export max. Demand active power
Watt
integer
228
L1 phase import max. Demand reactive power
Var
integer
230
L1 phase export max. Demand reactive power
Var
integer
232
L2 phase import max. Demand reactive power
Var
integer
234
L2 phase export max. Demand reactive power
Var
integer
236
L3 phase import max. Demand reactive power
Var
integer
238
L3 phase export max. Demand reactive power
Var
integer
240
L1 phase max. Demand apparent power
VA
word
242
L2 phase max. Demand apparent power
VA
word
244
L3 phase max. Demand apparent power
VA
word
246
Total import max. Demand active power
Watt
integer
248
Total export max. Demand active power
Watt
integer
250
Total import max. Demand reactive power
Var
integer
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (EPR04) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
20
L1 phase active power
Watt
integer
22
L2 phase active power
Watt
integer
24
L3 phase active power
Watt
integer
26
L1 phase reactive power
Var
integer
28
L2 phase reactive power
Var
integer
30
L3 phase reactive power
Var
integer
32
L1 phase apparent power
VA
dword
34
L2 phase apparent power
VA
dword
36
L3 phase apparent power
VA
dword
38
L1 phase cos
 
integer
40
L2 phase cos
 
integer
42
L3 phase cos
 
integer
44
Total import active power
Watt
integer
46
Total export active power
Watt
integer
48
Total inductive reactive power
Var
integer
50
Total capacitive reactive power
Var
integer
52
Total apparent power
VA
dword
54
Average inductive cos
 
integer
56
Average capacitive cos
 
integer
58
Frequency
Hz
dword
88
Import active energy 1
Wh
int64
92
Export active energy 1
Wh
int64
96
Inductive reactive energy 1
VArh
int64
100
Capacitive reactive energy 1
VArh
int64
104
Import active energy 2
Wh
int64
108
Export active energy 2
Wh
int64
112
Inductive reactive energy 2
VArh
int64
116
Capacitive reactive energy 2
VArh
int64
136
L1 phase min. active power
Watt
integer
138
L2 phase min. active power
Watt
integer
140
L3 phase min. active power
Watt
integer
142
L1 phase min. reactive power
Var
integer
144
L2 phase min. reactive power
Var
integer
146
L3 phase min. reactive power
Var
integer
148
L1 phase min. apparent power
VA
dword
150
L2 phase min. apparent power
VA
dword
152
L3 phase min. apparent power
VA
dword
154
Total min. import active power
Watt
integer
156
Total min. export active power
Watt
integer
158
Total min. import reactive power
Var
integer
160
Total min. export reactive power
Var
integer
162
Total min. apparent power
VA
dword
182
L1 phase max. active power
Watt
integer
184
L2 phase max. active power
Watt
integer
186
L3 phase max. active power
Watt
integer
188
L1 phase max. reactive power
Var
integer
190
L2 phase max. reactive power
Var
integer
192
L3 phase max. reactive power
Var
integer
194
L1 phase max. apparent power
VA
dword
196
L2 phase max. apparent power
VA
dword
There are more MODBUS items for this device. Please download the program to discover all registers.

ENTES (ES32) - MODBUS Registers Map

MODBUS offset
Description
Units
Data type
3
Index
Wh
dword
5
Voltage
V
word
6
Current
mA
word
7
Frequency
Hz
word
8
Power factor
 
word
9
Active power
kW
word
10
Reactive power
kVar
word
11
Apparent power
kVa
word

ENTES (MPR1 Series) - Data

MODBUS offset
Description
Units
Data type
0
Voltage L1 N
V/10
dword
2
Voltage L2 N
V/10
dword
4
Voltage L3 N
V/10
dword
6
Voltage L4 N
V/10
dword
8
Voltage L1 L2
V/10
dword
10
Voltage L2 L3
V/10
dword
12
Voltage L3 L1
V/10
dword
14
Current L1
mA
dword
16
Current L2
mA
dword
18
Current L3
mA
dword
20
Current L4
mA
dword
22
Neutral current = il1+il2+il3
mA
dword
24
Measured frequency
Hz / 100
dword
26
Active power L1 N
W
single
28
Active power L2 N
W
single
30
Active power L3 N
W
single
32
Active power L4 N
W
single
34
Total import active power
W
single
36
Total export active power
W
single
38
Active power +/ = P =p1+p2+p3
W
single
40
Reactive power L1
var
single
42
Reactive power L2
var
single
44
Reactive power L3
var
single
46
Reactive power L4
var
single
48
Quadrant 1 total reactive power
var
single
50
Quadrant 2 total reactive power
var
single
52
Quadrant 3 total reactive power
var
single
54
Quadrant 4 total reactive power
var
single
56
Reactive power +/ = q=q1+q2+q3
var
single
58
Apparent power L1 N
VA
single
60
Apparent power L2 N
VA
single
62
Apparent power L3 N
VA
single
64
Apparent power L4 N
VA
single
66
Total import apparent power
VA
single
68
Total export apparent power
VA
single
70
Apparent power +/ = s=s1+s2+s3
VA
single
72
Power factor L1
 
integer
74
Power factor L2
 
integer
76
Power factor L3
 
integer
78
Power factor L4
 
integer
80
Power factor +/ = pf=pfl1+pfl2+pfl3
 
integer
82
Cosphi L1
 
integer
84
Cosphi L2
 
integer
86
Cosphi L3
 
integer
88
Cosphi L4
 
integer
90
Cos phi = cos_l1 + cos_l2 + cos_l3
 
integer
92
Rotation field
 
integer
94
Voltage unbalance
%
dword
96
Current unbalance
%
dword
98
L1 phase voltage angle
Angle
int64
There are more MODBUS items for this device. Please download the program to discover all registers.

Related MODBUS registers maps

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.

MODBUS COM Port Connection