Enerdis (Enerium 100-200) logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
1280V1Vdword
1282V2Vdword
1284V3Vdword
1286VearthVdword
1288U12Vdword
1290U23Vdword
1292U31Vdword
1294I1Adword
1296I2Adword
1298I3Adword
1300InAdword
1302P1Winteger
1304P2Winteger
1306P3Winteger
1308PWinteger
1310Q1varinteger
1312Q2varinteger
1314Q3varinteger
1316Qvarinteger
1318S1VAdword
1320S2VAdword
1322S3VAdword
1324SVAdword
1326PF1 smallint
1327Quadrant, PF1 word
1328PF2 smallint
1329Quadrant, PF2 word
1330PF3 smallint
1331Quadrant, PF3 word
1332Pf smallint
1333Quadrant, pf word
1334Cos phi, phase 1 smallint
1335Quadrant, cos phi, phase 1 word
1336Cos phi, phase 2 smallint
1337Quadrant, cos phi, phase 2 word
1338Cos phi, phase 3 smallint
1339Quadrant, cos phi, phase 3 word
1340Cos phi, three phase smallint
1341Quadrant, cos phi, three phase word
1342Crest factor, V1 word
1343Crest factor, V2 word
1344Crest factor, V3 word
1345Crest factor, I1 word
1346Crest factor, I2 word
1347Crest factor, I3 word
1348Unbalance of the voltages smallint
1349FrequencyHzword
1536Harmonics, order by order, V1 [0 to 50 word
1587Harmonics, order by order, V2 [0 to 50 word
1638Harmonics, order by order, V3 [0 to 50 word
1689Harmonics, order by order, U12 [0 to 50 word
1740Harmonics, order by order, U23 [0 to 50 word
1791Harmonics, order by order, U31 [0 to 50 word
1842Harmonics, order by order, I1 [0 to 50 word
1893Harmonics, order by order, I2 [0 to 50 word
1944Harmonics, order by order, I3 [0 to 50 word
1995Rank, max. Harmonic, V1 word
1996Rank, max. Harmonic, V2 word
1997Rank, max. Harmonic, V3 word
1998Rank, max. Harmonic, U12 word
1999Rank, max. Harmonic, U23 word
2000Rank, max. Harmonic, U31 word
2001Rank, max. Harmonic, I1 word
2002Rank, max. Harmonic, I2 word
2003Rank, max. Harmonic, I3 word
2004Value, max. Harmonic, V1 word
2005Value, max. Harmonic, V2 word
2006Value, max. Harmonic, V3 word
2007Value, max. Harmonic, U12 word
2008Value, max. Harmonic, U23 word
2009Value, max. Harmonic, U31 word
2010Value, max. Harmonic, I1 word
2011Value, max. Harmonic, I2 word
2012Value, max. Harmonic, I3 word
2013Thd V1 word
2014Thd V2 word
2015Thd V3 word
2016Thd U12 word
2017Thd U23 word
2018Thd U31 word
2019Thd I1 word
2020Thd I2 word
2021Thd I3 word
2304Average of V1Vdword
2306Average of V2Vdword
2308Average of V3Vdword
2310Average of vearthVdword
2312Average of U12Vdword
2314Average of U23Vdword
2316Average of U31Vdword
2318Average of I1Adword
2320Average of I2Adword
2322Average of I3Adword
2324Average of inAdword
2326Average of p1, receiver modeWdword
2328Average of p1, generator modeWdword
2330Average of p2, receiver modeWdword
2332Average of p2, generator modeWdword
2334Average of p3, receiver modeWdword
2336Average of p3, generator modeWdword
There are more MODBUS items for this device. Please, download the program.