FF LE-01, LE-03MQ MODBUS registers: read online

Connect FF to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous FF modbus logging and log.

Do you not know the meter address? Scan the device address online

FF (LE-01) - Measurement Data

Connection and addressing notes

Protocol
Modbus RTU
Interface
RS-485
Default baud rate
9600 bps
Parity
none
Default device address
1
Function codes
03 read holding registers
Register addressing
table lists HEX and DEC addresses
Data format
INT16 or INT32 values scaled by the multiplier column

Registers in the map: 27. function 3 (holding registers). byte order big-endian. data types: integer, smallint.

MODBUS offsetDescriptionUnitsData typeScale
256VoltageVinteger×0.001
258CurrentAinteger×0.001
260Active powerWinteger 
262Apparent powerVAinteger 
264Reactive powervarinteger 
266FrequencyHzsmallint×0.1
267Power factor smallint×0.001
270Total consumed (imported) active energykWhinteger×0.01
280Total returned (exported) active energykWhinteger×0.01
290Total active energykWhinteger×0.01
300Total consumed (imported) reactive en- ergykvarhinteger×0.01
310Total returned (exported) reactive energykvarhinteger×0.01
320Total reactive energykvarhinteger×0.01
330Total reactive energy in the first quadrantkvarhinteger×0.01
340Total reactive energy in the second quad- rantkvarhinteger×0.01
350Total reactive energy in the third quad- rantkvarhinteger×0.01
360Total reactive energy in the fourth quad- rantkvarhinteger×0.01
370Resettable auxiliary active energy meterkWhinteger×0.01
372Resettable auxiliary reactive energy meterkvarhinteger×0.01
374Consumed (imported) active power de- mandWinteger×0.1
376Maximum consumed (imported) active power demandWinteger×0.1
378Returned (exported) active power demandWinteger×0.1
380Maximum returned (exported) active power demandWinteger×0.1
384Consumed (imported) reactive power de- mandvarinteger×0.1
386Maximum consumed (imported) reactive power demandvarinteger×0.1
388Returned (exported) reactive power de- mandvarinteger×0.1
390Maximum returned (exported) reactive power demandvarinteger×0.1

FF (LE-03MQ) - MODBUS Mapping

Registers in the map: 67 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0L1 (L-n) phase voltageVsingle 
2L2 (L-n) phase voltageVsingle 
4L3 (L-n) phase voltageVsingle 
6L1 current strengthAsingle 
8L2 current strengthAsingle 
10L3 current strengthAsingle 
12L1 active powerWsingle 
14L2 active powerWsingle 
16L3 active powerWsingle 
18L1 apparent powerVAsingle 
20L2 apparent powerVAsingle 
22L3 apparent powerVAsingle 
24L1 reactive powervarsingle 
26L2 reactive powervarsingle 
28L3 reactive powervarsingle 
30L1 power factor single 
32L2 power factor single 
34L3 power factor single 
36L1 phase angledegsingle 
38L2 phase angledegsingle 
40L3 phase angledegsingle 
42Average phase voltage among phase and neutral wireVsingle 
46Average line currentAsingle 
48Sum of phase currentsAsingle 
52Total system powerWsingle 
56Total systemVAsingle 
60Total systemvarsingle 
62Total system power factor (*1) single 
66Total system phase angledegsingle 
70Frequency of supply voltagesHzsingle 
72Imported active energykWh/ MWhsingle 
74Exported active energykWh/MWhsingle 
76Imported reactive energykvarh/Mvarhsingle 
78Exported reactive energykvarh/Mvarhsingle 
80Apparent powerkVah/ MVAhsingle 
82Ah since last resetAh/kAhsingle 
84Total system power demand (*2)Wsingle 
86Maximum total system power demand (*2)Wsingle 
100Total system VA demand (*2)VAsingle 
102Maximum total system VA demandVAsingle 
104Neutral current demandAsingle 
106Maximum neutral current demandAsingle 
200L1-L2 interphase voltageWsingle 
202L2-L3 interphase voltageWsingle 
204L3-L1 interphase voltageWsingle 
206Average interphase voltageWsingle 
224Neutral currentAsingle 
234Phase 1 L/N volts THD%single 
236Phase 2 L/N volts THD%single 
238Phase 3 L/N volts THD%single 

This is not the complete map: 50 of 67 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.