Fronius Power Meter (210,211.212,213) logging. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
40005 | Manufacturer | | string(32) |
40021 | Device model | | string(32) |
40037 | Options | | string(16) |
40045 | Sw version of meter | | string(16) |
40053 | Serialnumber of the meter | | string(32) |
40069 | Modbus device address | | word |
40072 | Ac total current value | | single |
40074 | Ac phase A current value | | single |
40076 | Ac phase B current value | | single |
40078 | Ac phase C current value | | single |
40080 | Ac voltage average phase to neutral value | | single |
40082 | Ac voltage phase A to neutral value | | single |
40084 | Ac voltage phase B to neutral value | | single |
40086 | Ac voltage phase C to neutral value | | single |
40088 | Ac voltage average phase to phase value | | single |
40090 | Ac voltage phase ab value | | single |
40092 | Ac voltage phase bc value | | single |
40094 | Ac voltage phase ca value | | single |
40096 | Ac frequency value | Hz | single |
40098 | Ac power value | | single |
40100 | Ac power phase A value | | single |
40102 | Ac power phase B value | | single |
40104 | Ac power phase C value | | single |
40106 | Ac apparent power value | VA | single |
40108 | Ac apparent power phase A value | VA | single |
40110 | Ac apparent power phase B value | VA | single |
40112 | Ac apparent power phase C value | VA | single |
40114 | Ac reactive power value | VAr | single |
40116 | Ac reactive power phase A value | VAr | single |
40118 | Ac reactive power phase B value | VAr | single |
40120 | Ac reactive power phase C value | VAr | single |
40122 | Power factor value | | single |
40124 | Power factor phase A value | | single |
40126 | Power factor phase B value | | single |
40128 | Power factor phase C value | | single |
40130 | Total watt hours exported | Wh | single |
40132 | Total watt hours exported phase A | Wh | single |
40134 | Total watt hours exported phase B | Wh | single |
40136 | Total watt hours exported phase C | Wh | single |
40138 | Total watt hours imported | Wh | single |
40140 | Total watt hours imported phase A | Wh | single |
40142 | Total watt hours imported phase B | Wh | single |
40144 | Total watt hours imported phase C | Wh | single |
40146 | Total va hours exported | VA | single |
40148 | Total va hours exported phase A | VA | single |
40150 | Total va hours exported phase B | VA | single |
40152 | Total va hours exported phase C | VA | single |
40154 | Total va hours imported | VA | single |
40156 | Total va hours imported phase A | VA | single |
40158 | Total va hours imported phase B | VA | single |
There are more MODBUS items for this device. Please, download the program. |
Fronius Power Meter (210,211.212,213) data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.