MODBUS offsetDescriptionUnitsData type
40005Manufacturer string(32)
40021Device model string(32)
40037Options string(16)
40045Sw version of meter string(16)
40053Serialnumber of the meter string(32)
40069Modbus device address word
40072Ac total current value single
40074Ac phase A current value single
40076Ac phase B current value single
40078Ac phase C current value single
40080Ac voltage average phase to neutral value single
40082Ac voltage phase A to neutral value single
40084Ac voltage phase B to neutral value single
40086Ac voltage phase C to neutral value single
40088Ac voltage average phase to phase value single
40090Ac voltage phase ab value single
40092Ac voltage phase bc value single
40094Ac voltage phase ca value single
40096Ac frequency valueHzsingle
40098Ac power value single
40100Ac power phase A value single
40102Ac power phase B value single
40104Ac power phase C value single
40106Ac apparent power valueVAsingle
40108Ac apparent power phase A valueVAsingle
40110Ac apparent power phase B valueVAsingle
40112Ac apparent power phase C valueVAsingle
40114Ac reactive power valueVArsingle
40116Ac reactive power phase A valueVArsingle
40118Ac reactive power phase B valueVArsingle
40120Ac reactive power phase C valueVArsingle
40122Power factor value single
40124Power factor phase A value single
40126Power factor phase B value single
40128Power factor phase C value single
40130Total watt hours exportedWhsingle
40132Total watt hours exported phase AWhsingle
40134Total watt hours exported phase BWhsingle
40136Total watt hours exported phase CWhsingle
40138Total watt hours importedWhsingle
40140Total watt hours imported phase AWhsingle
40142Total watt hours imported phase BWhsingle
40144Total watt hours imported phase CWhsingle
40146Total va hours exportedVAsingle
40148Total va hours exported phase AVAsingle
40150Total va hours exported phase BVAsingle
40152Total va hours exported phase CVAsingle
40154Total va hours importedVAsingle
40156Total va hours imported phase AVAsingle
40158Total va hours imported phase BVAsingle
40160Total va hours imported phase CVAsingle
40194Events dword

Fronius Power Meter (210,211.212,213) data logging