Fronius Power Meter (210,211.212,213) data logger - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
40005
Manufacturer
 
string(32)
40021
Device model
 
string(32)
40037
Options
 
string(16)
40045
Sw version of meter
 
string(16)
40053
Serialnumber of the meter
 
string(32)
40069
Modbus device address
 
word
40072
Ac total current value
 
single
40074
Ac phase A current value
 
single
40076
Ac phase B current value
 
single
40078
Ac phase C current value
 
single
40080
Ac voltage average phase to neutral value
 
single
40082
Ac voltage phase A to neutral value
 
single
40084
Ac voltage phase B to neutral value
 
single
40086
Ac voltage phase C to neutral value
 
single
40088
Ac voltage average phase to phase value
 
single
40090
Ac voltage phase ab value
 
single
40092
Ac voltage phase bc value
 
single
40094
Ac voltage phase ca value
 
single
40096
Ac frequency value
Hz
single
40098
Ac power value
 
single
40100
Ac power phase A value
 
single
40102
Ac power phase B value
 
single
40104
Ac power phase C value
 
single
40106
Ac apparent power value
VA
single
40108
Ac apparent power phase A value
VA
single
40110
Ac apparent power phase B value
VA
single
40112
Ac apparent power phase C value
VA
single
40114
Ac reactive power value
VAr
single
40116
Ac reactive power phase A value
VAr
single
40118
Ac reactive power phase B value
VAr
single
40120
Ac reactive power phase C value
VAr
single
40122
Power factor value
 
single
40124
Power factor phase A value
 
single
40126
Power factor phase B value
 
single
40128
Power factor phase C value
 
single
40130
Total watt hours exported
Wh
single
40132
Total watt hours exported phase A
Wh
single
40134
Total watt hours exported phase B
Wh
single
40136
Total watt hours exported phase C
Wh
single
40138
Total watt hours imported
Wh
single
40140
Total watt hours imported phase A
Wh
single
40142
Total watt hours imported phase B
Wh
single
40144
Total watt hours imported phase C
Wh
single
40146
Total va hours exported
VA
single
40148
Total va hours exported phase A
VA
single
40150
Total va hours exported phase B
VA
single
40152
Total va hours exported phase C
VA
single
40154
Total va hours imported
VA
single
40156
Total va hours imported phase A
VA
single
40158
Total va hours imported phase B
VA
single
There are more MODBUS items for this device. Please download the program to discover all registers.

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.