Integra Ci1, Ci3, Ri3 MODBUS registers: read online

Connect Integra to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Integra logger and poll.

Do you not know the meter address? Scan the device address online

Integra Ci1 - MODBUS Maps

Registers in the map: 8. function 3 (holding registers). byte order big-endian. data types: word.

MODBUS offsetDescriptionUnitsData typeScale
1Lo_egy_imp_powWhword×0.1
2Hi_egy_imp_powkhword×100
3Lo_egy_exp_powWhword×0.1
4Hi_egy_exp_powkWhword×100
5Lo_egy_imp_varvarhword×0.1
6Hi_egy_imp_varkvarhword×100
7Lo_egy_exp_varvarhword×0.1
8Hi_egy_exp_varkvarhword×100

Integra Ci3-Ri3 - MODBUS Measurements

Connection and addressing notes

Point mapping
METASYS N2 point mapping table
Register addressing
ADFPoint values (1 to 72) used as map offsets
ADF point numbering
one-based in the JCI compliance test software, zero-based on the network

Registers in the map: 67 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: word.

MODBUS offsetDescriptionUnitsData typeScale
1V1Vword 
2V2Vword 
3V3Vword 
4A1Aword 
5A2Aword 
6A3Aword 
7Kp1kWword 
8Kp2kWword 
9Kp3kWword 
10Kva1kVAword 
11Kva2kVAword 
12Kva3kVAword 
13Kvar1kvarword 
14Kvar2kvarword 
15Kvar3kvarword 
19Pa1degword 
20Pa2degword 
21Pa3degword 
22AnAword 
23V12Vword 
24V23Vword 
25V31Vword 
26VlnavgVword 
27AavgAword 
28AsumAword 
29VllavgVword 
30KpsumkWword 
31KvasumkVAword 
32Kvarsumkvarword 
34Patotdegword 
35FreqHzword 
36Lo_egy_imp_powkWhword×0.1
37Hi_egy_imp_powMWhword×100
38Lo_egy_exp_powkWhword×0.1
39Hi_egy_exp_powMWhword×100
40Lo_egy_imp_varkvarhword×0.1
41Hi_egy_imp_varMvarhword×100
42Lo_egy_exp_varkvarhword×0.1
43Hi_egy_exp_varMvarhword×100
44Lo_egy_vakAhword×0.1
45Hi_egy_vaMVAhword×100
46Lo_egy_ampAhword×0.1
47Hi_egy_ampkAhword×100
48Kpsum_dmdkWword 
49Kpsum_max_dmdkWword 
50Kvasum_dmdkVAword 
51Kvasum_max_dmdkVAword 
52A1_dmdAword 
53A1_max_dmdAword 
54A2_dmdAword 

This is not the complete map: 50 of 67 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.