Iskra ECS3, MT880, CM-f3e MODBUS registers: read online

Connect Iskra to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Iskra logger and poll.

Do you not know the meter address? Scan the device address online

Iskra (ECS3) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Interface variants
Basic and Full
Register addressing
register addresses used directly as map offsets
Speed register
4112
Parity register
4113
Stop bits register
4114
Device address register
4115
Value format register
4117
Unsupported quantities
returned as 0

Registers in the map: 69 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, word.

MODBUS offsetDescriptionUnitsData typeScale
4099Device type word 
4100Firmware version word 
4101Range overflow alarm word 
4102Running tariff dword 
4104PID bytes 1 and 2 word 
4105PID bytes 3 and 4 word 
4106PID bytes 5 and 6 word 
4107PID bytes 7 and 8 word 
4108PID bytes 9 and 10 word 
4109PID bytes 11 and 12 word 
4110PID bytes 13 and 14 word 
4119Active energy 1st phase T1, impkWhint64formula
4123Active energy 2nd phase T1, impkWhint64formula
4127Active energy 3rd phase T1, impkWhint64formula
4131Active energy sum T1, impkWhint64formula
4135Active energy 1st phase T2, impkWhint64formula
4139Active energy 2nd phase T2, impkWhint64formula
4143Active energy 3rd phase T2, impkWhint64formula
4147Active energy sum T2, impkWhint64formula
4151Active power 1st phase dword 
4153Active power 2nd phase dword 
4155Active power 3rd phase dword 
4157Active power sum int64formula
4161Active energy 1st phase T1, expkWhint64formula
4165Active energy 2nd phase T1, expkWhint64formula
4169Active energy 3rd phase T1, expkWhint64formula
4173Active energy sum T1, expkWhint64formula
4177Active energy 1st phase T2, expkWhint64formula
4181Active energy 2nd phase T2, expkWhint64formula
4185Active energy 3rd phase T2, expkWhint64formula
4189Active energy sum T2, expkWhint64formula
4193Reactive energy 1st phase T1, impkvarhint64formula
4197Reactive energy 2nd phase T1, impkvarhint64formula
4201Reactive energy 3rd phase T1, impkvarhint64formula
4205Reactive energy sum T1, impkvarhint64formula
4209Reactive energy 1st phase T2, impkvarhint64formula
4213Reactive energy 2nd phase T2, impkvarhint64formula
4217Reactive energy 3rd phase T2, impkvarhint64formula
4221Reactive energy sum T2, impkvarhint64formula
4225Reactive energy 1st phase T1, expkvarhint64formula
4229Reactive energy 2nd phase T1, expkvarhint64formula
4233Reactive energy 3rd phase T1, expkvarhint64formula
4237Reactive energy sum T1, expkvarhint64formula
4241Reactive energy 1st phase T2, expkvarhint64formula
4245Reactive energy 2nd phase T2, expkvarhint64formula
4249Reactive energy 3rd phase T2, expkvarhint64formula
4253Reactive energy sum T2, expkvarhint64formula
4257Reactive power 1st phasekvardword 
4259Reactive power 2nd phasekvardword 
4261Reactive power 3rd phasekvardword 

This is not the complete map: 50 of 69 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Iskra (MT880,CM-f3e) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Function codes
03 read holding registers
Register addressing
register numbers start at 0 and are used directly as map offsets
Data format
16-bit integer, 32-bit long, IEEE 754 float, 64-bit double
Energy and demand scaling
10x relative to the meter measurement resolution (100 mWh default)
Configuration
Modbus parameters are set over the module web GUI

Registers in the map: 168 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: double, integer, single.

MODBUS offsetDescriptionUnitsData typeScale
0Device id 1, manufacturing number integer 
2Current system time integer 
5Current system date integer 
8Active energy import (+a) double 
12Active energy export (a) double 
16Reactive energy import (+r) double 
20Reactive energy export ( r) double 
24Reactive energy Q1 (+ri) double 
28Reactive energy Q2 (+rc) double 
32Reactive energy Q3 ( ri) double 
36Reactive energy Q4 ( rc) double 
40Apparent energy import (+va) (Q1 + Q4) double 
44Apparent energy export (Q2 + Q3)VAdouble 
48Active energy import (+a) L1 double 
52Active energy import (+a) L2 double 
56Active energy import (+a) L3 double 
60Active energy export ( a) L1 double 
64Active energy export ( a) L2 double 
68Active energy export ( a) L3 double 
72Reactive energy import (+r) L1 double 
76Reactive energy import (+r) L2 double 
80Reactive energy import (+r) L3 double 
84Reactive energy export ( r) L1 double 
88Reactive energy export ( r) L2 double 
92Reactive energy export ( r) L3 double 
96Reactive energy Q1 (+ri) L1 double 
100Reactive energy Q1 (+ri) L2 double 
104Reactive energy Q1 (+ri) L3 double 
108Reactive energy Q2 (+rc) L1 double 
112Reactive energy Q2 (+rc) L2 double 
116Reactive energy Q2 (+rc) L3 double 
120Reactive energy Q3 ( ri) L1 double 
124Reactive energy Q3 ( ri) L2 double 
128Reactive energy Q3 ( ri) L3 double 
132Reactive energy Q4 ( rc) L1 double 
136Reactive energy Q4 ( rc) L2 double 
140Reactive energy Q4 ( rc) L3 double 
144Apparent energy import (+va) (Q1 + Q4) L1 double 
148Apparent energy import (+va) (Q1 + Q4) L2 double 
152Apparent energy import (+va) (Q1 + Q4) L3 double 
156Apparent energy export (Q2 + Q3) L1VAdouble 
160Apparent energy export (Q2 + Q3) L2VAdouble 
164Apparent energy export (Q2 + Q3) L3VAdouble 
168Instantaneous active power (|+a|+| a|) single 
170Instantaneous active import power (+a) single 
172Instantaneous active import power (+a) L1 single 
174Instantaneous active import power (+a) L2 single 
176Instantaneous active import power (+a) L3 single 
178Instantaneous active export power ( a) single 
180Instantaneous active export power ( a) L1 single 

This is not the complete map: 50 of 168 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.