Landis Gyr E650, Gateway, Meter 1 MODBUS registers: read online

Connect Landis Gyr to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Landis Gyr data logger and record.

Do you not know the meter address? Scan the device address online

Landis Gyr (E650,Gateway,Meter 1) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Meter values
holding register area
Meter values copy
4x20000 holding register area
Register addressing
base 1
Word order
some masters must swap words to read the values correctly

Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, smallint.

MODBUS offsetDescriptionUnitsData typeScale
40015Hours: format hhmmss smallint 
40017Data format aammgg smallint 
40019Meter serial number (read by dlms) smallint 
40021Reset meter count single 
40023Total active energy a+ single 
40025Total active energy previous month A + single 
40027Total active energy slot 1 a+ single 
40029Total active energy slot 1 previous month A + single 
40031Total active energy slot 2 a+ single 
40033Total active energy slot 2 previous month A + single 
40035Total active energy slot 3 a+ single 
40037Total active energy slot 3 previous month A + single 
40039Total active energy slot 4 a+ single 
40041Total active energy slot 4 previous month A + single 
40043Total active energy A single 
40045Total active energy previous month A single 
40047Total active energy slot 1 A single 
40049Total active energy slot 1 previous month A single 
40051Total active energy slot 2 A single 
40053Total active energy slot 2 previous month A single 
40055Total active energy slot 3 A single 
40057Total active energy slot 3 previous month A single 
40059Total active energy slot 4 A single 
40061Total active energy slot 4 previous month A single 
40063Reactive total energy Q1 single 
40065Reactive total energy previous month Q1 single 
40067Reactive total energy slot 1 Q1 single 
40069Reactive total energy slot 1 previous month Q1 single 
40071Reactive total energy slot 2 Q1 single 
40073Reactive total energy slot 2 previous month Q1 single 
40075Reactive total energy slot 3 Q1 single 
40077Reactive total energy slot 3 previous month Q1 single 
40079Reactive total energy slot 4 Q1 single 
40081Reactive total energy slot 4 previous month Q1 single 
40083Reactive total energy Q2 single 
40085Reactive total energy previous month Q2 single 
40087Reactive total energy slot 1 Q2 single 
40089Reactive total energy slot 1 previous month Q2 single 
40091Reactive total energy slot 2 Q2 single 
40093Reactive total energy slot 2 previous month Q2 single 
40095Reactive total energy slot 3 Q2 single 
40097Reactive total energy slot 3 previous month Q2 single 
40099Reactive total energy slot 4 Q2 single 
40101Reactive total energy slot 4 previous month Q2 single 
40103Reactive total energy Q3 single 
40105Reactive total energy previous month Q3 single 
40107Reactive total energy slot 1 Q3 single 
40109Reactive total energy slot 1 previous month Q3 single 
40111Reactive total energy slot 2 Q3 single 
40113Reactive total energy slot 2 previous month Q3 single 

This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Landis Gyr (E650,Gateway,Meter 2) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus
Meter values
holding register area
Meter values copy
4x20000 holding register area
Register addressing
base 1
Word order
some masters must swap words to read the values correctly

Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, smallint.

MODBUS offsetDescriptionUnitsData typeScale
40215Hours: format hhmmss smallint 
40217Data format aammgg smallint 
40219Meter serial number (read by dlms) smallint 
40221Reset meter count single 
40223Total active energy a+ single 
40225Total active energy previous month A + single 
40227Total active energy slot 1 a+ single 
40229Total active energy slot 1 previous month A + single 
40231Total active energy slot 2 a+ single 
40233Total active energy slot 2 previous month A + single 
40235Total active energy slot 3 a+ single 
40237Total active energy slot 3 previous month A + single 
40239Total active energy slot 4 a+ single 
40241Total active energy slot 4 previous month A + single 
40243Total active energy A single 
40245Total active energy previous month A single 
40247Total active energy slot 1 A single 
40249Total active energy slot 1 previous month A single 
40251Total active energy slot 2 A single 
40253Total active energy slot 2 previous month A single 
40255Total active energy slot 3 A single 
40257Total active energy slot 3 previous month A single 
40259Total active energy slot 4 A single 
40261Total active energy slot 4 previous month A single 
40263Reactive total energy Q1 single 
40265Reactive total energy previous month Q1 single 
40267Reactive total energy slot 1 Q1 single 
40269Reactive total energy slot 1 previous month Q1 single 
40271Reactive total energy slot 2 Q1 single 
40273Reactive total energy slot 2 previous month Q1 single 
40275Reactive total energy slot 3 Q1 single 
40277Reactive total energy slot 3 previous month Q1 single 
40279Reactive total energy slot 4 Q1 single 
40281Reactive total energy slot 4 previous month Q1 single 
40283Reactive total energy Q2 single 
40285Reactive total energy previous month Q2 single 
40287Reactive total energy slot 1 Q2 single 
40289Reactive total energy slot 1 previous month Q2 single 
40291Reactive total energy slot 2 Q2 single 
40293Reactive total energy slot 2 previous month Q2 single 
40295Reactive total energy slot 3 Q2 single 
40297Reactive total energy slot 3 previous month Q2 single 
40299Reactive total energy slot 4 Q2 single 
40301Reactive total energy slot 4 previous month Q2 single 
40303Reactive total energy Q3 single 
40305Reactive total energy previous month Q3 single 
40307Reactive total energy slot 1 Q3 single 
40309Reactive total energy slot 1 previous month Q3 single 
40311Reactive total energy slot 2 Q3 single 
40313Reactive total energy slot 2 previous month Q3 single 

This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Landis Gyr (E650,Gateway,Meter 3) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Meter values
holding register area
Meter values copy
4x20000 holding register area
Register addressing
base 1
Word order
some masters must swap words to read the values correctly

Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, smallint.

MODBUS offsetDescriptionUnitsData typeScale
40415Hours: format hhmmss smallint 
40417Data format aammgg smallint 
40419Meter serial number (read by dlms) smallint 
40421Reset meter count single 
40423Total active energy a+ single 
40425Total active energy previous month A + single 
40427Total active energy slot 1 a+ single 
40429Total active energy slot 1 previous month A + single 
40431Total active energy slot 2 a+ single 
40433Total active energy slot 2 previous month A + single 
40435Total active energy slot 3 a+ single 
40437Total active energy slot 3 previous month A + single 
40439Total active energy slot 4 a+ single 
40441Total active energy slot 4 previous month A + single 
40443Total active energy A single 
40445Total active energy previous month A single 
40447Total active energy slot 1 A single 
40449Total active energy slot 1 previous month A single 
40451Total active energy slot 2 A single 
40453Total active energy slot 2 previous month A single 
40455Total active energy slot 3 A single 
40457Total active energy slot 3 previous month A single 
40459Total active energy slot 4 A single 
40461Total active energy slot 4 previous month A single 
40463Reactive total energy Q1 single 
40465Reactive total energy previous month Q1 single 
40467Reactive total energy slot 1 Q1 single 
40469Reactive total energy slot 1 previous month Q1 single 
40471Reactive total energy slot 2 Q1 single 
40473Reactive total energy slot 2 previous month Q1 single 
40475Reactive total energy slot 3 Q1 single 
40477Reactive total energy slot 3 previous month Q1 single 
40479Reactive total energy slot 4 Q1 single 
40481Reactive total energy slot 4 previous month Q1 single 
40483Reactive total energy Q2 single 
40485Reactive total energy previous month Q2 single 
40487Reactive total energy slot 1 Q2 single 
40489Reactive total energy slot 1 previous month Q2 single 
40491Reactive total energy slot 2 Q2 single 
40493Reactive total energy slot 2 previous month Q2 single 
40495Reactive total energy slot 3 Q2 single 
40497Reactive total energy slot 3 previous month Q2 single 
40499Reactive total energy slot 4 Q2 single 
40501Reactive total energy slot 4 previous month Q2 single 
40503Reactive total energy Q3 single 
40505Reactive total energy previous month Q3 single 
40507Reactive total energy slot 1 Q3 single 
40509Reactive total energy slot 1 previous month Q3 single 
40511Reactive total energy slot 2 Q3 single 
40513Reactive total energy slot 2 previous month Q3 single 

This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Landis Gyr (E650,Gateway,Meter 4) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Register area
holding registers
Secondary register area
4x20000 holding registers
Register addressing
table addresses are base 1
Word order
some masters must swap words to read the values correctly

Registers in the map: 113 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, smallint.

MODBUS offsetDescriptionUnitsData typeScale
40615Hours: format hhmmss smallint 
40617Data format aammgg smallint 
40619Meter serial number (read by dlms) smallint 
40621Reset meter count single 
40623Total active energy a+ single 
40625Total active energy previous month A + single 
40627Total active energy slot 1 a+ single 
40629Total active energy slot 1 previous month A + single 
40631Total active energy slot 2 a+ single 
40633Total active energy slot 2 previous month A + single 
40635Total active energy slot 3 a+ single 
40637Total active energy slot 3 previous month A + single 
40639Total active energy slot 4 a+ single 
40641Total active energy slot 4 previous month A + single 
40643Total active energy A single 
40645Total active energy previous month A single 
40647Total active energy slot 1 A single 
40649Total active energy slot 1 previous month A single 
40651Total active energy slot 2 A single 
40653Total active energy slot 2 previous month A single 
40655Total active energy slot 3 A single 
40657Total active energy slot 3 previous month A single 
40659Total active energy slot 4 A single 
40661Total active energy slot 4 previous month A single 
40663Reactive total energy Q1 single 
40665Reactive total energy previous month Q1 single 
40667Reactive total energy slot 1 Q1 single 
40669Reactive total energy slot 1 previous month Q1 single 
40671Reactive total energy slot 2 Q1 single 
40673Reactive total energy slot 2 previous month Q1 single 
40675Reactive total energy slot 3 Q1 single 
40677Reactive total energy slot 3 previous month Q1 single 
40679Reactive total energy slot 4 Q1 single 
40681Reactive total energy slot 4 previous month Q1 single 
40683Reactive total energy Q2 single 
40685Reactive total energy previous month Q2 single 
40687Reactive total energy slot 1 Q2 single 
40689Reactive total energy slot 1 previous month Q2 single 
40691Reactive total energy slot 2 Q2 single 
40693Reactive total energy slot 2 previous month Q2 single 
40695Reactive total energy slot 3 Q2 single 
40697Reactive total energy slot 3 previous month Q2 single 
40699Reactive total energy slot 4 Q2 single 
40701Reactive total energy slot 4 previous month Q2 single 
40703Reactive total energy Q3 single 
40705Reactive total energy previous month Q3 single 
40707Reactive total energy slot 1 Q3 single 
40709Reactive total energy slot 1 previous month Q3 single 
40711Reactive total energy slot 2 Q3 single 
40713Reactive total energy slot 2 previous month Q3 single 

This is not the complete map: 50 of 113 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.