MODBUS offsetDescriptionUnitsData type
40415Hours: format hhmmss smallint
40417Data format aammgg smallint
40419Meter serial number (read by dlms) smallint
40421Reset meter count single
40423Total active energy a+ single
40425Total active energy previous month A + single
40427Total active energy slot 1 a+ single
40429Total active energy slot 1 previous month A + single
40431Total active energy slot 2 a+ single
40433Total active energy slot 2 previous month A + single
40435Total active energy slot 3 a+ single
40437Total active energy slot 3 previous month A + single
40439Total active energy slot 4 a+ single
40441Total active energy slot 4 previous month A + single
40443Total active energy A single
40445Total active energy previous month A single
40447Total active energy slot 1 A single
40449Total active energy slot 1 previous month A single
40451Total active energy slot 2 A single
40453Total active energy slot 2 previous month A single
40455Total active energy slot 3 A single
40457Total active energy slot 3 previous month A single
40459Total active energy slot 4 A single
40461Total active energy slot 4 previous month A single
40463Reactive total energy Q1 single
40465Reactive total energy previous month Q1 single
40467Reactive total energy slot 1 Q1 single
40469Reactive total energy slot 1 previous month Q1 single
40471Reactive total energy slot 2 Q1 single
40473Reactive total energy slot 2 previous month Q1 single
40475Reactive total energy slot 3 Q1 single
40477Reactive total energy slot 3 previous month Q1 single
40479Reactive total energy slot 4 Q1 single
40481Reactive total energy slot 4 previous month Q1 single
40483Reactive total energy Q2 single
40485Reactive total energy previous month Q2 single
40487Reactive total energy slot 1 Q2 single
40489Reactive total energy slot 1 previous month Q2 single
40491Reactive total energy slot 2 Q2 single
40493Reactive total energy slot 2 previous month Q2 single
40495Reactive total energy slot 3 Q2 single
40497Reactive total energy slot 3 previous month Q2 single
40499Reactive total energy slot 4 Q2 single
40501Reactive total energy slot 4 previous month Q2 single
40503Reactive total energy Q3 single
40505Reactive total energy previous month Q3 single
40507Reactive total energy slot 1 Q3 single
40509Reactive total energy slot 1 previous month Q3 single
40511Reactive total energy slot 2 Q3 single
40513Reactive total energy slot 2 previous month Q3 single
40515Reactive total energy slot 3 Q3 single
40517Reactive total energy slot 3 previous month Q3 single
40519Reactive total energy slot 4 Q3 single
40521Reactive total energy slot 4 previous month Q3 single
40523Reactive total energy Q4 single
40525Reactive total energy previous month Q4 single
40527Reactive total energy slot 1 Q4 single
40529Reactive total energy slot 1 previous month Q4 single
40531Reactive total energy slot 2 Q4 single
40533Reactive total energy slot 2 previous month Q4 single
40535Reactive total energy slot 3 Q4 single
40537Reactive total energy slot 3 previous month Q4 single
40539Reactive total energy slot 4 Q4 single
40541Reactive total energy slot 4 previous month Q4 single
40543Power max slot 1 A + single
40545Power max slot 1 previous month A + single
40547Power max slot 2 A + single
40549Power max slot 2 previous month A + single
40551Power max slot 3 A + single
40553Power max slot 3 previous month A + single
40555Power max slot 4 A + single
40557Power max slot 4 previous month A + single
40559Power max slot 1 A single
40561Power max slot 1 previous month A single
40563Power max slot 2 A single
40565Power max slot 2 previous month A single
40567Power max slot 3 A single
40569Power max slot 3 previous month A single
40571Power max slot 4 A single
40573Power max slot 4 previous month A single
40575Internal signal control status single
40577Internal operation status single
40579Voltage phase 1 single
40581Voltage phase 2 single
40583Voltage phase 3 single
40585Power failure counter phase1 single
40587Power failure counter phase2 single
40589Power failure counter phase3 single
40591Power failure total counter for phase 1,2,3 single
40593Overvoltage event number phase1 single
40595Overvoltage event number phase2 single
40597Overvoltage event number phase3 single
40599Current L1 single
40601Current L2 single
40603Current L3 single
40605Frequency single
40607Reactive imported energy single
40609Reactive imported energy previous month single
40611Reactive exported energy single
40613Reactive exported energy previous month single
There are more MODBUS items for this device. Please, download the program.