bg

Lifasa MCA PLUS II MODBUS registers: read online

Connect Lifasa to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Lifasa modbus logging and log.

Do you not know the meter address? Scan the device address online

Lifasa (MCA PLUS II) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Address format
hexadecimal
Function codes
03 read holding registers, 04 read input registers
Write example
slave address 0x0A (10) with function 0x05

Registers in the map: 133 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0L1 phase voltageVdword×0.1
2L1 currentAdword×0.001
4L1 active powerWdword 
6L1 inductive powervardword 
8L1 capacitive powervardword 
10L1 apparent powerVAdword 
12L1 power factor dword×0.01
14Cos L1 dword×0.01
16L2 phase voltageVdword×0.1
18L2 currentAdword×0.001
20L2 active powerWdword 
22L2 inductive powervardword 
24L2 capacitive powervardword 
26L2 apparent powerVAdword 
28L2 power factor dword×0.01
30Cos L2 dword×0.01
32L3 phase voltageVdword×0.1
34L3 currentAdword×0.001
36L3 active powerWdword 
38L3 inductive powervardword 
40L3 capacitive powervardword 
42L3 apparent powerVAdword 
44L3 power factor dword×0.01
46Cos L3 dword×0.01
48Active three-phase powerWdword 
50Inductive three-phase powervardword 
52Capacitive three-phase powervardword 
54Apparent three-phase powerVAdword 
56Three-phase power factor dword×0.01
58Three-phase cos dword×0.01
60L1 frequencyHzdword×0.01
62L1-L2 voltageVdword×0.1
64L2-L3 voltageVdword×0.1
66L3-L1 voltageVdword×0.1
68Neutral current NAdword×0.001
70L1 voltage % THD%dword×0.1
72L2 voltage % THD%dword×0.1
74L3 voltage % THD%dword×0.1
76L1 current % THD%dword×0.1
78L2 current % THD%dword×0.1
80L3 current % THD%dword×0.1
82Maximum demand kW IIIWdword 
84Maximum demand kVA IIIVAdword 
86Maximum demand I AVGAdword×0.001
88Maximum demand I L1Adword×0.001
90Maximum demand I L2Adword×0.001
92Maximum demand I L3Adword×0.001
512Maximum demand kvarL IIIkvarLdword 
514Maximum demand kvarC IIIkvarCdword 
94Consumed active energy kW) dword 

This is not the complete map: 50 of 133 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Lifasa (Master Control Var Fast) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Address format
hexadecimal
Function code
04 read input registers

Registers in the map: 98 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0L1 phase voltageVdword×0.01
2L1 currentAdword×0.001
4L1 active powerWdword 
6L1 inductive reactive powervarLdword 
8L1 capacitive reactive powervarCdword 
10L1 reactive powervardword 
12L1 apparent powerVAdword 
14L1 reactive power consumedvardword 
16L1 reactive power generatedvardword 
18L1 power factor dword 
20L1 cos dword 
22L1 kW sign dword 
24L1 kvar sign dword 
26L2 phase voltageVdword×0.01
28L2 currentAdword×0.001
30L2 active powerWdword 
32L2 inductive reactive powervarLdword 
34L2 capacitive reactive powervarCdword 
36L2 reactive powervardword 
38L2 apparent powerVAdword 
40L2 reactive power consumedvardword 
42L2 reactive power generatedvardword 
44L2 power factor dword 
46L2 cos dword 
48L2 kW sign dword 
50L2 kvar sign dword 
52L3 phase voltageVdword×0.01
54L3 currentAdword×0.001
56L3 active powerWdword 
58L3 inductive reactive powervarLdword 
60L3 capacitive reactive powervarCdword 
62L3 reactive powervardword 
64L3 apparent powerVAdword 
66L3 reactive power consumedvardword 
68L3 reactive power generatedvardword 
70L3 power factor dword 
72L3 cos dword 
74L3 kW sign dword 
76L3 kvar sign dword 
78Three-phase voltageVdword×0.01
80Three-phase currentAdword×0.001
82Three-phase active powerWdword 
84Three-phase inductive powervarLdword 
86Three-phase capacitive powervarCdword 
88Three-phase reactive powervardword 
90Three-phase apparent powerVAdword 
92Three-phase reactive power consumedvardword 
94Three-phase reactive power generatedvardword 
96Three-phase power factor dword 
98Three-phase cos dword 

This is not the complete map: 50 of 98 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Lifasa (Master Control Var) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Address format
hexadecimal
Function code
04 read input registers

Registers in the map: 98 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword.

MODBUS offsetDescriptionUnitsData typeScale
0L1 phase voltageVdword×0.01
2L1 currentAdword×0.001
4L1 active powerWdword 
6L1 inductive reactive powervarLdword 
8L1 capacitive reactive powervarCdword 
10L1 reactive powervardword 
12L1 apparent powerVAdword 
14L1 reactive power consumedvardword 
16L1 reactive power generatedvardword 
18L1 power factor dword 
20L1 cos dword 
22L1 kW sign dword 
24L1 kvar sign dword 
26L2 phase voltageVdword×0.01
28L2 currentAdword×0.001
30L2 active powerWdword 
32L2 inductive reactive powervarLdword 
34L2 capacitive reactive powervarCdword 
36L2 reactive powervardword 
38L2 apparent powerVAdword 
40L2 reactive power consumedvardword 
42L2 reactive power generatedvardword 
44L2 power factor dword 
46L2 cos dword 
48L2 kW sign dword 
50L2 kvar sign dword 
52L3 phase voltageVdword×0.01
54L3 currentAdword×0.001
56L3 active powerWdword 
58L3 inductive reactive powervarLdword 
60L3 capacitive reactive powervarCdword 
62L3 reactive powervardword 
64L3 apparent powerVAdword 
66L3 reactive power consumedvardword 
68L3 reactive power generatedvardword 
70L3 power factor dword 
72L3 cos dword 
74L3 kW sign dword 
76L3 kvar sign dword 
78Three-phase voltageVdword×0.01
80Three-phase currentAdword×0.001
82Three-phase active powerWdword 
84Three-phase inductive powervarLdword 
86Three-phase capacitive powervarCdword 
88Three-phase reactive powervardword 
90Three-phase apparent powerVAdword 
92Three-phase reactive power consumedvardword 
94Three-phase reactive power generatedvardword 
96Three-phase power factor dword 
98Three-phase cos dword 

This is not the complete map: 50 of 98 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Related MODBUS registers maps