Lovato Electric RGK800, RGK900, RGK Series MODBUS registers: read online

Connect Lovato Electric to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Lovato Electric data logger and record.

Do you not know the meter address? Scan the device address online

Lovato Electric (RGK800,RGK900,RGK Series) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Interface
serial
Function codes
03 read holding registers, 04 read input registers
Register addressing
hexadecimal with an H suffix, for example 0002H
Data format
32-bit values occupy 2 words
Register clone
one register is documented as a clone of Modbus function 17

Registers in the map: 157 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
2L1 phase voltage - mainsVdword×0.01
4L2 phase voltage - mainsVdword×0.01
6L3 phase voltage - mainsVdword×0.01
8L1 phase voltage - generatorVdword×0.01
10L2 phase voltage - generatorVdword×0.01
12L3 phase voltage - generatorVdword×0.01
14L1 currentAdword×0.0001
16L2 currentAdword×0.0001
18L3 currentAdword×0.0001
20Neutral currentAdword×0.0001
22L1-L2 voltage - mainsVdword×0.01
24L2-L3 voltage - mainsVdword×0.01
26L3-L1 voltage - mainsVdword×0.01
28L1-L2 voltage - generatorVdword×0.01
30L2-L3 voltage - generatorVdword×0.01
32L3-L1 voltage - generatorVdword×0.01
34L1 active power - mainsWinteger×0.01
36L2 active power - mainsWinteger×0.01
38L3 active power - mainsWinteger×0.01
40L1 active power - generatorWinteger×0.01
42L2 active power - generatorWinteger×0.01
44L3 active power - generatorWinteger×0.01
46L1 reactive power - mainsvarinteger×0.01
48L2 reactive power - mainsvarinteger×0.01
50L3 reactive power - mainsvarinteger×0.01
52L1 reactive power - generatorvarinteger×0.01
54L2 reactive power - generatorvarinteger×0.01
56L3 reactive power - generatorvarinteger×0.01
58L1 apparent power - mainsVAdword×0.01
60L2 apparent power - mainsVAdword×0.01
62L3 apparent power - mainsVAdword×0.01
64L1 apparent power - generatorVAdword×0.01
66L2 apparent power - generatorVAdword×0.01
68L3 apparent power - generatorVAdword×0.01
70L1 power factor - mains integer×0.0001
72L2 power factor - mains integer×0.0001
74L3 power factor - mains integer×0.0001
76L1 power factor - generator integer×0.0001
78L2 power factor - generator integer×0.0001
80L3 power factor - generator integer×0.0001
82Eqv. phase voltage - mainsVdword×0.01
84Eqv. phase-to-phase voltage - mainsVdword×0.01
86Frequency - mainsHzdword×0.001
88Eqv. phase voltage - generatorVdword×0.01
90Eqv. phase-to-phase voltage - generatorVdword×0.01
92Frequency - generatorHzdword×0.001
94Eqv power factor - mains integer×0.0001
100Eqv power factor - generator integer×0.0001
106Eqv. active power - mainsWinteger×0.01
108Eqv. reactive power - mainsvarinteger×0.01

This is not the complete map: 50 of 157 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.