Masibus (PM2160-3P3W) - MODBUS Registers
MODBUS offset
Description
Units
Data type
2
1 2. Pf
dword
6
3 2. Pf
dword
8
A. Pf
dword
10
Vrms 12
dword
12
Vrms 3*1
dword
14
Vrms 2*3
dword
16
A vrms
dword
24
1. Irms
dword
28
3. Irms
dword
30
A. Irms
dword
34
1 2. Watt
dword
38
3 2. Watt
dword
40
S. Watt
dword
42
1 2. Var
dword
46
3 2. Var
dword
48
S. Var
dword
50
1 2. Va
dword
54
3 2. Va
dword
56
S. Va
dword
58
1 2. Wh import
dword
62
3 2. Wh import
dword
64
T. Wh import
dword
66
1 2. Wh export
dword
70
3 2. Wh export
dword
72
T. Wh export
dword
74
1 2. Varh import
dword
78
3 2. Varh import
dword
80
T. Varh import
dword
82
1 2. Varh export
dword
86
3 2. Varh export
dword
88
T. Varh export
dword
90
1 2. Vah
dword
94
3 2. Vah
dword
96
T. Vah
dword
98
Rising demand
dword
100
Real date
dword
102
Real time
dword
104
Maximum demand
dword
106
Md date
dword
108
Md time
dword
110
1 2. Phase angle
dword
114
3 2. Phase angle
dword
116
V. Unbalance
dword
118
1. Unbalance
dword
2000
Frequency
dword
2002
1. Vrms
dword
2004
2. Vrms
dword
2006
3. Vrms
dword
2008
A. Vrms
dword
2010
1. Irms
dword
There are more MODBUS items for this device. Please download the program to discover all registers.
Masibus (PM2160-3P4W) - Mapping
MODBUS offset
Description
Units
Data type
2
1. Pf
dword
4
2. Pf
dword
6
3. Pf
dword
8
A. Pf
dword
10
1. Vrms
dword
12
2. Vrms
dword
14
3. Vrms
dword
16
A. Vrms
dword
18
Vrms 1*2
dword
20
Vrms 2*3
dword
22
Vrms 31
dword
24
1. Irms
dword
26
2. Irms
dword
28
3. Irms
dword
30
A. Irms
dword
34
1. Watt
dword
36
2. Watt
dword
38
3. Watt
dword
40
S. Watt
dword
42
1. Var
dword
44
2.var
dword
46
3.var
dword
48
S.var
dword
50
1.va
dword
52
2.va
dword
54
3.va
dword
56
S.va
dword
58
1.wh import
dword
60
2.wh import
dword
62
3.wh import
dword
64
T.wh import
dword
66
1.wh export
dword
68
2.wh export
dword
70
3.wh export
dword
72
T.wh export
dword
74
1. Varh import
dword
76
2. Varh import
dword
78
3. Varh import
dword
80
T. Varh import
dword
82
1. Varh export
dword
84
2. Varh export
dword
86
3. Varh export
dword
88
T. Varh export
dword
90
1.vah
dword
92
2.vah
dword
94
3.vah
dword
96
T.vah
dword
98
Rising demand
dword
100
Real date
dword
102
Realtime
dword
There are more MODBUS items for this device. Please download the program to discover all registers.
Related MODBUS registers maps
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
MODBUS COM Port Connection
Feature Not Supported
Your current browser does not support the Web Serial API required to access local COM ports. Please use a Chromium-based browser like Google Chrome, Microsoft Edge, or Opera.