Lovato Electric - MODBUS Registers Map - Data Logging
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Lovato Electric data logging and capture.
Lovato Electric (RGK800) - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
2
L1 phase voltage - mains
V
dword
4
L2 phase voltage - mains
V
dword
6
L3 phase voltage - mains
V
dword
8
L1 phase voltage - generator
V
dword
10
L2 phase voltage - generator
V
dword
12
L3 phase voltage - generator
V
dword
14
L1 current
A
dword
16
L2 current
A
dword
18
L3 current
A
dword
20
Neutral current
A
dword
22
L1-L2 voltage - mains
V
dword
24
L2-L3 voltage - mains
V
dword
26
L3-L1 voltage - mains
V
dword
28
L1-L2 voltage - generator
V
dword
30
L2-L3 voltage - generator
V
dword
32
L3-L1 voltage - generator
V
dword
34
L1 active power - mains
W
integer
36
L2 active power - mains
W
integer
38
L3 active power - mains
W
integer
40
L1 active power - generator
W
integer
42
L2 active power - generator
W
integer
44
L3 active power - generator
W
integer
46
L1 reactive power - mains
Var
integer
48
L2 reactive power - mains
Var
integer
50
L3 reactive power - mains
Var
integer
52
L1 reactive power - generator
Var
integer
54
L2 reactive power - generator
Var
integer
56
L3 reactive power - generator
Var
integer
58
L1 apparent power - mains
VA
dword
60
L2 apparent power - mains
VA
dword
62
L3 apparent power - mains
VA
dword
64
L1 apparent power - generator
VA
dword
66
L2 apparent power - generator
VA
dword
68
L3 apparent power - generator
VA
dword
70
L1 power factor - mains
integer
72
L2 power factor - mains
integer
74
L3 power factor - mains
integer
76
L1 power factor - generator
integer
78
L2 power factor - generator
integer
80
L3 power factor - generator
integer
82
Eqv. phase voltage - mains
V
dword
84
Eqv. phase-to-phase voltage - mains
V
dword
86
Frequency - mains
Hz
dword
88
Eqv. phase voltage - generator
V
dword
90
Eqv. phase-to-phase voltage - generator
V
dword
92
Frequency - generator
Hz
dword
94
Eqv power factor - mains
integer
100
Eqv power factor - generator
integer
106
Eqv. active power - mains
W
integer
108
Eqv. reactive power - mains
Var
integer
There are more MODBUS items for this device. Please download the program to discover all registers.
Related MODBUS registers maps
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.
MODBUS COM Port Connection
Feature Not Supported
Your current browser does not support the Web Serial API required to access local COM ports. Please use a Chromium-based browser like Google Chrome, Microsoft Edge, or Opera.