Connect RISH to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous RISH logging and read.
Do you not know the meter address? Scan the device address online
RISH (EM DC) - MODBUS Mapping
Connection and addressing notes
- Protocol
- Modbus RTU
- Interface
- RS-485 (2-wire)
- Data bits
- 8
- Stop bits
- 1 with parity, 1 or 2 without parity
- Parity
- even or odd
- Baud rate
- user selectable 4800, 9600, 19200, 38400, 57600 bps
- Device address range
- 1-247
- Broadcast address
- 0 not allowed
- Function codes
- 03, 04, 16 (0x10)
- Data format
- 32-bit IEEE 754 float, two consecutive 16-bit registers per parameter
- Byte order
- most significant byte first
- CRC error check
- enabled
- Maximum parameters per query
- 40
- Maximum response latency
- 200 ms
- Register addressing
- 3X (30001+) and 4X (44097+)
Registers in the map: 101 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Voltage | V | single | |
| 2 | Current CH1 | A | single | |
| 4 | Current CH2 | A | single | |
| 6 | Current CH3 | A | single | |
| 8 | Current CH4 | A | single | |
| 10 | Power CH1 | | single | |
| 12 | Power CH2 | | single | |
| 14 | Power CH3 | | single | |
| 16 | Power CH4 | | single | |
| 18 | Total import power | | single | |
| 20 | Total export power | | single | |
| 22 | Energy imp CH1 | | single | |
| 24 | Energy imp CH2 | | single | |
| 26 | Energy imp CH3 | | single | |
| 28 | Energy imp CH4 | | single | |
| 30 | Energy exp CH1 | | single | |
| 32 | Energy exp CH2 | | single | |
| 34 | Energy exp CH3 | | single | |
| 36 | Energy exp CH4 | | single | |
| 38 | Total import energy | | single | |
| 40 | Total export energy | | single | |
| 58 | Amp hour imp CH1 | | single | |
| 60 | Amp hour imp CH2 | | single | |
| 62 | Amp hour imp CH3 | | single | |
| 64 | Amp hour imp CH4 | | single | |
| 66 | Amp hour exp CH1 | | single | |
| 68 | Amp hour exp CH2 | | single | |
| 70 | Amp hour exp CH3 | | single | |
| 72 | Amp hour exp CH4 | | single | |
| 74 | Total ImportAH | | single | |
| 76 | Total ExportAH | | single | |
| 78 | Import power demand CH1 | | single | |
| 80 | Import power demand CH2 | | single | |
| 82 | Import power demand CH3 | | single | |
| 84 | Import power demand CH4 | | single | |
| 86 | Export power demand CH1 | | single | |
| 88 | Export power demand CH2 | | single | |
| 90 | Export power demand CH3 | | single | |
| 92 | Export power demand CH4 | | single | |
| 94 | Total import power demand | | single | |
| 96 | Total export power demand | | single | |
| 98 | Import current demand CH1 | A | single | |
| 100 | Import current demand CH2 | A | single | |
| 102 | Import current demand CH3 | A | single | |
| 104 | Import current demand CH4 | A | single | |
| 106 | Export current demand CH1 | A | single | |
| 108 | Export current demand CH2 | A | single | |
| 110 | Export current demand CH3 | A | single | |
| 112 | Export current demand CH4 | A | single | |
| 114 | Total import current demand | A | single | |
This is not the complete map: 50 of 101 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
RISH (EM1300,EM2300,EM13XX,EM23XX) - MODBUS Maps
Connection and addressing notes
- Protocol
- Modbus
- Register addressing
- 3X (30001+) for measured parameters
- Data format
- two consecutive 16-bit registers per parameter
- Modbus start address
- given in hex per parameter
Registers in the map: 163 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Volts 1 | | single | |
| 2 | Volts 2 | | single | |
| 4 | Volts 3 | | single | |
| 6 | Current 1 | | single | |
| 8 | Current 2 | | single | |
| 10 | Current 3 | | single | |
| 12 | W1 | | single | |
| 14 | W2 | | single | |
| 16 | W3 | | single | |
| 18 | VA 1 | | single | |
| 20 | VA 2 | | single | |
| 22 | VA 3 | | single | |
| 24 | VAR 1 | | single | |
| 26 | VAR 2 | | single | |
| 28 | VAR 3 | | single | |
| 30 | PF 1 | | single | |
| 32 | PF 2 | | single | |
| 34 | PF 3 | | single | |
| 36 | Phase angle 1 | | single | |
| 38 | Phase angle 2 | | single | |
| 40 | Phase angle 3 | | single | |
| 42 | Volts av g | | single | |
| 44 | Volts sum | | single | |
| 46 | Current avg | | single | |
| 48 | Current sum | | single | |
| 50 | Watt avg | | single | |
| 52 | Watt sum | | single | |
| 54 | VA av g | | single | |
| 56 | VA sum | | single | |
| 58 | VAR av g | | single | |
| 60 | VAR sum | | single | |
| 62 | PF avg | | single | |
| 64 | PF sum | | single | |
| 66 | Phase angle avg | | single | |
| 68 | Phase angle sum | | single | |
| 70 | Freq | | single | |
| 72 | Wh import / utility | | single | |
| 74 | Wh export / gen | | single | |
| 76 | Capacitive / utility | varh | single | |
| 78 | Inductive / gen | varh | single | |
| 80 | VAh / vah utility | | single | |
| 82 | VAh gen (Only 2340) | | single | |
| 84 | W demand (Import / utility / gen) | | single | |
| 86 | W max demand (Import / utility) | | single | |
| 88 | W demand (Export) | | single | |
| 90 | W max demand (Export / gen) | | single | |
| 92 | Old W max demand (Import / utility) | | single | |
| 94 | Old W max demand (Export / gen) | | single | |
| 96 | Old VA utility max demand | | single | |
| 98 | Old A utility max demand | | single | |
This is not the complete map: 50 of 163 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
RISH (LM1350,LM1360) - MODBUS Registers
Connection and addressing notes
- Register addressing
- 3X and 4X addresses for measured parameters
- Modbus start address
- given in hex
- Data format
- two registers per parameter
- Energy values
- 32-bit integers, separate table
Registers in the map: 359 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | 1 | | single | |
| 2 | 2 | | single | |
| 4 | 3 | | single | |
| 6 | 4 | | single | |
| 8 | 5 | | single | |
| 10 | 6 | | single | |
| 12 | 7 | | single | |
| 14 | 8 | | single | |
| 16 | 9 | | single | |
| 18 | 10 | | single | |
| 20 | 11 | | single | |
| 22 | 12 | | single | |
| 24 | 13 | | single | |
| 26 | 14 | | single | |
| 28 | 15 | | single | |
| 30 | 16 | | single | |
| 32 | 17 | | single | |
| 34 | 18 | | single | |
| 36 | 19 | | single | |
| 38 | 20 | | single | |
| 40 | 21 | | single | |
| 42 | 22 | | single | |
| 44 | 23 | | single | |
| 46 | 24 | | single | |
| 48 | 25 | | single | |
| 50 | 26 | | single | |
| 52 | 27 | | single | |
| 54 | 28 | | single | |
| 56 | 29 | | single | |
| 58 | 30 | | single | |
| 60 | 31 | | single | |
| 62 | 32 | | single | |
| 64 | 33 | | single | |
| 66 | 34 | | single | |
| 68 | 35 | | single | |
| 70 | 36 | | single | |
| 72 | 37 | | single | |
| 74 | 38 | | single | |
| 76 | 39 | | single | |
| 78 | 40 | | single | |
| 80 | 41 | | single | |
| 84 | 43 | | single | |
| 86 | 44 | | single | |
| 88 | 45 | | single | |
| 90 | 46 | | single | |
| 92 | 47 | | single | |
| 94 | 48 | | single | |
| 96 | 49 | | single | |
| 98 | 50 | | single | |
| 100 | 51 | | single | |
This is not the complete map: 50 of 359 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
RISH (RM1300,RM2300) - MODBUS Registers Map
Connection and addressing notes
- Protocol
- Modbus
- Register addressing
- 3X (30001+) for measured parameters
- Data format
- two consecutive 16-bit registers per parameter
Registers in the map: 157 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Volts 1 | | single | |
| 2 | Volts 2 | | single | |
| 4 | Volts 3 | | single | |
| 6 | Current 1 | | single | |
| 8 | Current 2 | | single | |
| 10 | Current 3 | | single | |
| 12 | W1 | | single | |
| 14 | W2 | | single | |
| 16 | W3 | | single | |
| 18 | Va 1 | | single | |
| 20 | Va 2 | | single | |
| 22 | Va 3 | | single | |
| 24 | Var 1 | | single | |
| 26 | Var 2 | | single | |
| 28 | Var 3 | | single | |
| 30 | Pf 1 | | single | |
| 32 | Pf 2 | | single | |
| 34 | Pf 3 | | single | |
| 36 | Phase angle 1 | | single | |
| 38 | Phase angle 2 | | single | |
| 40 | Phase angle 3 | | single | |
| 42 | Volts av g | | single | |
| 44 | Volts sum | | single | |
| 46 | Current avg | | single | |
| 48 | Current sum | | single | |
| 50 | Watt avg | | single | |
| 52 | Watt sum | | single | |
| 54 | Va av g | | single | |
| 56 | Va sum | | single | |
| 58 | Var av g | | single | |
| 60 | Var sum | | single | |
| 62 | Pf avg | | single | |
| 64 | Pf sum | | single | |
| 66 | Phase angle avg | | single | |
| 68 | Phase angle sum | | single | |
| 70 | Freq | | single | |
| 72 | Wh import / utility | | single | |
| 74 | Wh export / gen | | single | |
| 76 | Capacitive / utility | varh | single | |
| 78 | Inductive / gen | varh | single | |
| 80 | Vah / vah utility | | single | |
| 82 | Vah gen (only 2340) | | single | |
| 84 | W demand (import / utility / gen) | | single | |
| 86 | W max demand (import / utility) | | single | |
| 88 | W demand (export) | | single | |
| 90 | W max demand (export / gen) | | single | |
| 92 | Old W max demand (import / utility) | | single | |
| 94 | Old W max demand (export / gen) | | single | |
| 96 | Old va utility max demand | | single | |
| 98 | Old A utility max demand | | single | |
This is not the complete map: 50 of 157 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
RISH (RM3430i) - Measurement Data
Connection and addressing notes
- Protocol
- Modbus
- Register addressing
- 3X (30001+) for measured parameters
- Data format
- two consecutive 16-bit registers per parameter
- Settings registers
- 4X
- Settings access
- code 03 reads a setting, code 16 writes or changes it
- Response example function code
- 04
Registers in the map: 62 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Volts 1 | | single | |
| 2 | Volts 2 | | single | |
| 4 | Volts 3 | | single | |
| 6 | Current 1 | | single | |
| 8 | Current 2 | | single | |
| 10 | Current 3 | | single | |
| 12 | W1 | | single | |
| 14 | W2 | | single | |
| 16 | W3 | | single | |
| 18 | VA1 | | single | |
| 20 | VA2 | | single | |
| 22 | VA3 | | single | |
| 24 | Var1 | | single | |
| 26 | Var2 | | single | |
| 28 | Var3 | | single | |
| 30 | PF1 | | single | |
| 32 | PF2 | | single | |
| 34 | PF3 | | single | |
| 36 | Phase angle 1 | | single | |
| 38 | Phase angle 2 | | single | |
| 40 | Phase angle 3 | | single | |
| 42 | Volts ave | | single | |
| 44 | Volts sum | | single | |
| 46 | Current ave | | single | |
| 48 | Current sum | | single | |
| 50 | Watts ave | | single | |
| 52 | Watts sum | | single | |
| 54 | Va ave | | single | |
| 56 | Va sum | | single | |
| 58 | Var ave | | single | |
| 60 | Var sum | | single | |
| 62 | Pf ave | | single | |
| 64 | Pf sum | | single | |
| 66 | Phase angle ave | | single | |
| 68 | Phase angle sum | | single | |
| 70 | Freq | | single | |
| 72 | Wh import | | single | |
| 74 | Wh export | | single | |
| 76 | Varh import | | single | |
| 78 | Varh export | | single | |
| 80 | Vah | | single | |
| 132 | Volts ave max | | single | |
| 134 | Volts ave min | | single | |
| 140 | Current ave max | | single | |
| 142 | Current ave min | | single | |
| 144 | Active import energy | Wh | single | |
| 146 | Active export energy | Wh | single | |
| 148 | Reactive import energy | varh | single | |
| 150 | Reactive export energy | varh | single | |
| 152 | Apparent energy | VAh | single | |
This is not the complete map: 50 of 62 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.